Altronix Maximal3V Installation Manual Download Page 5

 

Maximal3V / Maximal5V / Maximal7V Access Power Controllers (Fused) 

- 5 -

9 . 

FACP Dry form “C” output (Fig. 2b, pg. 7):

 

FACP form “C” contacts can be use to trigger reporting or signaling devices . These contact switch

 

upon a fire alarm input trigger to the ACM8 boards .

10 . 

Stand-by Battery Connections (Figs. 3-7, pgs. 8-12):

 

For Access Control applications batteries are optional . If batteries are not used a loss of AC will result in 

 

the loss of output voltage . Batteries must be lead acid or gel type . Connect one (1) 12VDC battery to the 

 

terminals marked [+ BAT –] for 12VDC operation (Fig. 3a, pg. 8) . Use two (2) 12VDC batteries wired in 

 

series for 24VDC operation . 

11 . 

Battery and AC Supervision outputs (Figs. 3-4, pgs. 8-9):

 

It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT FAIL] 

 

supervisory relay outputs marked [NC, C, NO] to appropriate visual notification devices . 

 

Use 22 AWG to 18 AWG for AC Fail and Low/No Battery reporting . 

12 . 

Installation of tamper switch (Not Included) (Figs. 3b-4a, pgs. 8-9):

 

Mount UL Listed tamper switch (Honeywell Model 112 or equivalent) at the top of the enclosure . Slide 

 

the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Figs. 3b 

 

and 4a, pgs. 8-9) . Connect tamper switch wiring to the Access Control Panel input or the appropriate UL 

 

Listed reporting device . To activate alarm signal open the door of the enclosure .

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

 

FACP Supervision: 

To ensure proper connection and operation of the Fire Alarm disconnect 

 

 

 

hookup please follow the appropriate procedure below:

 

Normally Open Input: 

Placing a short between terminals marked [T] and [+ INP] will trigger the 

 

 

 

Fire Alarm Disconnect . Remove the short to reset .

 

Normally Closed Input: 

Removing the wire from terminal marked [INP –] will trigger the Fire 

 

 

 

Alarm Disconnect . Replace the wire to terminal marked [INP –] to reset .

 

FACP Signal Circuit Input:  It is necessary to trigger the Fire Alarm System .

 

 

 

In all of the above scenarios the green TRG LED of the ACM8s will 

 

 

 

illuminate . All outputs selected for Fire Alarm Disconnect will activate 

 

 

 

releasing locking devices .

    

Note: All outputs [OUT 1 - OUT 8] must be in a normal (de-energized) 

 

 

 

condition prior to testing . When the unit is configured for Normally Open 

    

(Fig. 10, pg. 13) or Normally Closed (Fig. 12, pg. 14) latching operation it 

 

 

 

is necessary to reset the Fire Alarm Disconnect by activating the 

 

 

 

Normally Closed reset switch .

 

Output Voltage Test: 

Under normal load conditions the DC output voltage should be checked 

 

 

 

for proper voltage level 

    

(Power Supply Board Stand-by Battery Specifications, pg. 7).

 

Battery Test: 

Under normal load conditions check that the battery is fully charged, check 

 

 

 

specified voltage at the battery terminals and at the board terminals marked 

 

 

 

[+ BAT –] to ensure that there is no break in the battery connection wires .

    

Note: AL600XB220 and AL1012XB220 Power Supply Board maximum 

 

 

 

charge current is 0 .7A . 

 

 

 

AL1024XB2V Power Supply Board maximum charge current is 3 .6A .

 

 

 

Expected battery life is 5 years, however it is recommended to change 

 

 

 

batteries within 4 years or less if necessary .

Power Supply Board LED Diagnostics:

LED

Power Supply Status

Red (DC)

Green (AC)

ON

ON

Normal operating condition .

ON

OFF

Loss of AC . Stand-by battery supplying power .

OFF

ON

No DC output . Short circuit or thermal overload condition . 

OFF

OFF

No DC output . Loss of AC . Discharged battery .

Red (Bat)

Battery Status

ON

Normal operating condition .

OFF

Battery fail/low battery .

Summary of Contents for Maximal3V

Page 1: ...M Access Power Controllers Installation Guide Models Include Maximal3V 12VDC 5A or 24VDC 5 4A Sixteen 16 fuse protected outputs Maximal5V 12VDC 9A Sixteen 16 fuse protected outputs Maximal7V 24VDC 9 4...

Page 2: ...wer Controller Terminal Identification pg 6 Power Supply Board Stand by Battery Specifications pg 6 Power Supply Board Output Voltage Settings pg 7 Access Power Controller Typical Application Diagram...

Page 3: ...ated 5A 28VDC or VAC d Any combination of the above Sixteen 16 Access Control System trigger inputs Input trigger options a Sixteen 16 normally open NO dry trigger inputs b Sixteen 16 open collector i...

Page 4: ...oper or high voltage will damage these devices 5 Output options Fig 2 pg 7 The unit will provide either sixteen 16 switched power outputs sixteen 16 dry form C outputs or any combination of both switc...

Page 5: ...acing a short between terminals marked T and INP will trigger the Fire Alarm Disconnect Remove the short to reset Normally Closed Input Removing the wire from terminal marked INP will trigger the Fire...

Page 6: ...Fig 4 pg 9 Access Power Controller Terminal Identification Terminal Legend Function Description Power 12VDC or 24VDC input from power supply board Control Not applicable TRIGGER INPUT 1 INPUT 8 IN GN...

Page 7: ...his application corresponding fuse F8 must be removed Keypad NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LE...

Page 8: ...3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 TRG NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC...

Page 9: ...4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J1 J3 FACP INTERFACE 10A 250V 1 2 3 4 O N 1 2 3 4 O N NC C N...

Page 10: ...require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable...

Page 11: ...require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable...

Page 12: ...require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable...

Page 13: ...E FACP Hook Up Diagrams Fig 8 Polarity reversal input from FACP signaling circuit output polarity is referenced in alarm condition N O TRIGGER INPUT TRG NO C NC FACP INTERFACE Fig 9 Normally Open Non...

Page 14: ...rs Fused JUMPER N C DRY TRIGGER INPUT TRG NO C NC FACP INTERFACE Fig 11 Normally Closed Non Latching FACP trigger input N C TRIGGER INPUT N C RESET SWITCH JUMPER TRG Fig 12 Normally Closed Latching FA...

Page 15: ...Maximal3V Maximal5V Maximal7V Access Power Controllers Fused 15 Notes...

Page 16: ...50 8mm 2 50 8mm 6 25 158 75mm 6 25 158 75mm 4 101 6mm 4 101 6mm 2 50 8mm 4 101 6mm 8 9 226 06mm 8 4 213 36mm 7 177 8mm 7 177 8mm 7 177 8mm 8 4 213 36mm 8 5 215 9mm 8 5 215 9mm 7 5 190 5mm 10 254mm 1 5...

Reviews: