Altronix MaxFit3F8AP Installation Manual Download Page 4

 

- 4 -  

MaxFit3_5F8AP

MaxFit7F5AP: NEC Power-Limited Wiring Requirements

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at 
least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit 
wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application 
may require different conduit knockouts to be used. Any conduit knockouts may be used. For power-limited applications use of conduit is 
optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). Optional 
UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods. For Canadian installations use 
shielded wiring for all connections. 
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 3a).

Fig. 3

Supervisory Connections, Aux. DC Output to Devices and

Fire Alarm Interface (power-limited)

Input 120VAC, 60Hz

(non power-limited)

DC Output

(non power-limited)

Supervisory

Connections

(power-limited)

ACM8 Outputs

to Devices

(non power-

limited)

PD8UL Outputs

to Devices

(non power-

limited)

Connect red battery lead to the terminal marked [+ BAT] and to the [positive (+)] terminal of the battery.

Connect black battery lead to terminal marked [BAT –] and to the [negative (–)] terminal of the battery.

Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.

12AH Rechargeable batteries are the largest batteries that can fit in this enclosure. 

A UL listed external battery enclosure must be used if using the 40AH or 65AH batteries.

Optional

Rechargeable

Stand-by Batteries

for UL294

Applications

  

Note:

12V batteries

are required for

ULC-S319

installations.

Tamper Switch

OUTPUT 1     OUTPUT 2         OUTPUT 3         OUTPUT 4          OUTPUT 5        OUTPUT 6         OUTPUT 7        OUTPUT 

8

NC  C  NO COM NC C NO COM  NC  C  NO COM NC C NO COM  NC  C  NO COM NC C NO COM  NC  C NO COM NC C NO COM

 IN  GND IN GND IN GND IN GND

IN  GND IN GND IN  GND IN GND

1            2           3          

4

5           6           7           

8

 INPUT TRIGGER

10A 250V

+INP-  T + RET-

NO  C   NC

FACP            INTERFACE

Power   Control

-      +      -      +

F1                   F2                  F3                   F4                   F5                   F6                   F7

                   F8

MAIN

TRG

FACP

1  2  3  

4

1  2  3  

4

ONON

1  2  3  

4

1  2  3  

4

ONON

N

COMMON   POWER   OUTPUT

S

P

FUSED    POWER    OUTPUT

S

8

D1

INPU

T

P        

N

R1

LE

D

ACM8

PD8UL

eFlow102NB

–   DC   +

–   BAT   +

L         G          

N

External

Jacketed

Shield

Incorrect Wire

Handling

Correct Wire

Handling

Pull back

external jacketed

shield approx. 1/2”.

Wire

Insulation

Solid Copper

Conductors

Fig. 3a