- 6 -
LPS3WP Series
LED Diagnostics:
Red (DC)
Green (AC)
Power Supply Status
ON
ON
Normal operating condition .
ON
OFF
Loss of AC . Stand-by battery is supplying power .
OFF
ON
No DC output .
OFF
OFF
Loss of AC . Discharged or no stand-by battery . No DC output .
Terminal Identification:
Terminal Legend
Function/Description
AC AC
Low voltage AC input:
LPS3WP12 - 16 .5VAC/56VA
LPS3WP24 - 28VAC/100VA .
–
BAT +
Stand-by battery connections .
–
DC +
LPS3WP12 - 12VDC @ 2 .5A continuous output .
LPS3WP24 - 24VDC @ 2 .5A continuous output .
The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user
to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may
be of sufficient magnitude to constitute an electric shock .
The exclamation point within an equilateral triangle is intended to alert the user to the presence of
important operating and maintenance (servicing) instructions in the literature accompanying
the appliance .
CAUTION: To reduce the risk of electric shock do not open
enclosure . There are no user serviceable parts inside .
Refer servicing to qualified service personnel .