eFlowNB - Power Supply/Chargers 

- 5 -

Wiring:

Use 18 AWG or larger for all low voltage power connections.
Note: Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery)

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test:  Under normal load conditions, the DC output voltage should be checked for 
 

proper voltage level.

Battery Test: 

Under normal load conditions check that the battery is fully charged, check specified 

 

voltage (12VDC @ 13.2 or 24VDC @ 26.4) both at the battery terminal and at the 

 

board terminals marked [– BAT +] to ensure that there is no break in the battery 

 

connection wires.

Replacing Batteries: 

Disconnect existing batteries. Connect battery to the terminals marked [– BAT +].

 

Use two (2) 12VDC batteries connected in series for 24VDC operation.

LED Diagnostics:

Red (DC)

Clear (AC1) / 
Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

Terminal
Legend

Function/Description

L, G, N

Connect 120VAC 60Hz to these terminals: L to hot, N to neutral, 
G to ground (non power-limited) (Fig. 1a, pg. 4).

– DC +
(Fig. 1h, pg. 4)

eFlow4NB: 

12VDC or 24VDC @ 4A continuous output (Power-Limited output).

eFlow6NB: 

12VDC or 24VDC @ 6A continuous output (Non Power-Limited output).

eFlow102NB:  12VDC @ 10A continuous output (Non Power-Limited output).
eFlow104NB:  24VDC @ 10A continuous output (Non Power-Limited output).

Trigger EOL
Supervised

Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open,
normally closed from an FACP output circuit (Power-Limited input) (Fig. 1d, pg. 4).

NO, GND
RESET

FACP interface latching or non-latching (Power-Limited) (Fig. 1c, pg. 4).

+ AUX –

Auxiliary Power-Limited output rated @ 1A (unswitched) (Power-Limited output) 
(Fig. 1f, pg. 4).

AC Fail 
NC, C, NO

Indicates loss of AC power, e.g. connect to audible device or alarm panel. 
Relay normally energized when AC power is present. 
Contact rating 1A @ 30VDC (Power-Limited) (Fig. 1b, pg. 4).

Bat Fail
NC, C, NO

Indicates low battery condition, e.g. connect to alarm panel. 
Relay normally energized when DC power is present. Contact rating 1A @ 30VDC. 
A removed battery is reported within 5 minutes.
Battery reconnection is reported within 1 minute (Power-Limited) (Fig. 1b, pg. 4).

– BAT +

Stand-by battery connections. Maximum charge current 1.54A (non power-limited) 
(Fig. 1g, pg. 4).

Summary of Contents for eFlow104NB

Page 1: ...Rev EFNB 10182016 Power Supply Charger Boards Installation Guide Models Include eFlow4NB eFlow102NB 12 or 24VDC 4A 12VDC 10A eFlow6NB eFlow104NB 12 or 24VDC 6A 24VDC 10A More than just power TM...

Page 2: ...ted Agency Listings UL Listed Sub Assembly for US Installations UL 294 UL Listed for Access Control System Units UL 603 UL Listed for Power Supplies for Use with Burglar Alarms Systems UL 1481 UL List...

Page 3: ...10 Mins 6A 12AH 1A 6A 0 3A 6A 35 Mins 6A 40AH 6A 6A 1 2A 6A Over 4 Hours 6A 65AH 6A 6A 1 5A 6A Over 4 Hours 6A eFlow102NB Battery Burg Applications 4 hr Stand by 15 min Alarm Fire Applications 24 hr...

Page 4: ...Low Power Disconnect or Fire Alarm Interface Connect device to terminals marked AUX Fig 1f pg 4 6 For Access Control applications batteries are optional When batteries are not used a loss of AC will...

Page 5: ...escription L G N Connect 120VAC 60Hz to these terminals L to hot N to neutral G to ground non power limited Fig 1a pg 4 DC Fig 1h pg 4 eFlow4NB 12VDC or 24VDC 4A continuous output Power Limited output...

Page 6: ...Enclosures eFlow4NB eFlow4N Maximal11F BC300 BC400 BC800 Maximal Trove1 and Trove2 eFlow6NB eFlow6N Maximal33F BC300 BC400 BC800 Maximal Trove1 and Trove2 eFlow102NB eFlow102N Maximal55F BC300 BC400 B...

Page 7: ...x is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Ma...

Page 8: ...te control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output st...

Reviews: