Altronix eFlow102NA8 Installation Manual Download Page 4

 

- 4 - 

eFlowNA8 Series Installation Guide

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, 

The Canadian Electrical Code, Part I, Part II, and with all local codes and authorities having jurisdiction. 

The product must be located indoors within the protected premises. 

 

Power Supply Board Stand-by Battery Specifications 

(pg. 3)

 

Power Supply Board LED Diagnostics 

(pg. 6)

 

Access Power Controller LED Diagnostics 

(pg. 6)

 

Power Supply Board Terminal Identification 

(pg. 7)

 

Access Power Controller Terminal Identification 

(pg. 7)

 

Power Supply Board Output Voltage Settings 

(pg. 8)

 

Access Power Controller Typical Application Diagram 

(pg. 8)

 

FACP/Optional Power Supply Hook-up Diagrams 

(pg. 11-12)

1.  Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in 

 

the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the 

 

enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two 

 

holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper 

 

keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pg. 11)

. Secure enclosure to earth ground. 

2.  Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, N] 

(Fig. 3, pg. 9)

. Do not use 

 

terminal marked [G]. Use 14 AWG or larger for all power connections. Secure green wire lead attached to the 

 

chassis to earth ground. The AC LED (Green) will illuminate, indicating power is present. This light can be 

 

seen through the LED lens on the door of the enclosure.

 

Keep power-limited wiring separate from non power-limited wiring. 

 

Minimum 0.25” spacing must be provided 

(Fig. 3, pg. 9)

.

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing 

 

equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified 

 

service personnel.

3.  Select desired DC output voltage by setting SW1 to the appropriate position on the power supply board 

 

(eFlow4NA8 and eFlow6NA8) 

(Fig. 1, pg. 8). 

eFlow102NA8 power supply is factory set at 12VDC. 

 

eFlow104NA8 power supply is factory set at 24VDC.

4.  Measure the output voltage of the unit before connecting any devices to ensure proper operation.

 

Improper or high voltage will damage these devices.

5. 

Output options 

(Fig. 2, pg. 8)

:

 

The unit will provide either eight (8) switched power outputs, eight (8) dry form “C” outputs, or any

 

combination of both switched power and form “C” outputs.

 

(a)  Fail-Safe Switched Power outputs: 

 

    For Fail-Safe operation connect the positive (+) input of the access control devices to terminal 

 

    marked [NC]. Connect the negative (–) input of the access control devices to terminal marked [COM].

 

(b)  Fail-Secure Switched Power outputs:

 

    For Fail-Secure operation connect the positive (+) input of the access control devices to terminal 

 

    marked [NO]. Connect the negative (–) input of the access control devices to terminal marked [COM].

 

(c)  Form “C” outputs:

 

    When form “C” outputs are desired, the corresponding output fuses (1-8) of each ACM8 board must 

 

    be removed.

6. 

ACM8 Auxiliary Power outputs (unswitched):

 

Connect access control devices that require constant power to terminals marked [C] positive (+) and 

 

[COM] negative (–). Outputs can be used to provide power for card readers, keypads etc.

 

eFlow Auxiliary outputs (unswitched):

 

For auxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm 

 

Interface. Connect device to terminals marked [+ AUX –] 

(Fig. 3, pg. 9).

7. 

Input trigger options 

(Fig. 2, pg. 8)

:

 

(a)  Normally Open [NO] input trigger:

 

    Inputs 1-8 are activated by normally open or open collector sink inputs. Connect access control panel 

 

    outputs, keypads, push buttons, REX PIRs, etc. to terminals marked [IN] and [GND]. 

 

(b)  Open Collector Sink inputs:

 

    Connect the access control panel open collector sink positive (+) to terminals marked [IN] and the 

 

    negative (–) to terminals marked [GND].

Summary of Contents for eFlow102NA8

Page 1: ...A8 4A 12VDC or 24VDC Eight 8 Fused Outputs eFlow6NA8 6A 12VDC or 24VDC Eight 8 Fused Outputs eFlow102NA8 10A 12VDC Eight 8 Fused Outputs eFlow104NA8 10A 24VDC Eight 8 Fused Outputs eFlowNA8 Series Access Power Controllers with Power Supply Chargers Models Include Rev eACM050919 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ...

Page 2: ... eFlow6NA8 3 5A 5A 250V 10A 32V 10 0 13 2 20 19 26 4 10 03 13 2 20 19 26 4 5 3A 5 6A 8 2 5A 10A 250V 3 5A 250V eFlow102NA8 3 5A 5A 250V 15A 32V 10 03 13 2 10 03 13 2 9 3A 8 2 5A 10A 250V 3 5A 250V eFlow104NA8 4 5A 6 3A 250V 15A 32V 20 17 26 4 20 17 26 4 9 6A 8 2 5A 10A 250V 3 5A 250V eFlow4NA8 only This unit is classified as Power Limited stand alone power supply with stand by battery and it is su...

Page 3: ...For output voltage and supply current refer to eFlowNA8 Series Configuration Chart pg 2 Auxiliary Power Limited output rated 1A unswitched Overvoltage protection Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 54A Automatic switch over to stand by battery when AC fails Transfer to stand by battery power is instantaneous with no interruption Supervised Fire Alar...

Page 4: ...r servicing equipment There are no user serviceable parts inside Refer installation and servicing to qualified service personnel 3 Select desired DC output voltage by setting SW1 to the appropriate position on the power supply board eFlow4NA8 and eFlow6NA8 Fig 1 pg 8 eFlow102NA8 power supply is factory set at 12VDC eFlow104NA8 power supply is factory set at 24VDC 4 Measure the output voltage of th...

Page 5: ... 24VDC operation battery leads included Use batteries Casil CL1270 12V 7AH CL12120 12V 12AH CL12400 12V 40AH CL12650 12V 65AH batteries or UL recognized BAZR2 and BAZR8 batteries of an appropriate rating 11 Battery and AC Supervision outputs Fig 3 pg 9 It is required to connect supervisory trouble reporting devices to outputs marked AC Fail BAT Fail supervisory relay outputs marked NC C NO to appr...

Page 6: ... 8 pg 10 or Normally Closed Fig 10 pg 10 latching operation it is necessary to reset the Fire Alarm Disconnect by activating the Normally Closed reset switch Output Voltage Test Under normal load conditions the DC output voltage should be checked for proper voltage level refer to eFlowNA8 series Configuration Chart pg 2 Battery Test Under normal load conditions check that the battery is fully char...

Page 7: ...ntroller Terminal Legend Function Description Power 12VDC or 24VDC from power supply charger factory connected These terminals are paralleled to the Control terminals Control These terminals are paralleled to the Power terminals They can be connected to an external Listed power limited access control power supply to provide isolated operating power for the devices Not evaluated by UL Jumpers J1 an...

Page 8: ... req d AC or DC Power Supply optional NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 TRG FACP NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J1 J3 TRG...

Page 9: ...r all other models Battery and AC Supervision Circuit power limited power limited Input power limited Observe polarity Battery Connections non power limited Green Flying Lead Unswitched 120VAC power mains non power limited Optional Rechargeable Stand by Battery for UL294 Applications Note 12V batteries required for ULC S319 installations Optional Rechargeable Stand by Battery for UL294 Application...

Page 10: ... wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian installations use shielded wiring for all connections Note Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire Fig 4a Fig 4 Fig ...

Page 11: ...in alarm condition Fig 5 Optional hook up using two 2 isolated power supply inputs Only applicable on eFlow4NA8 not evaluated by UL J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC LOCK POWER ISOLATED POWER INPUT 12 OR 24 VAC OR VDC ACM8 POWER CUT JUMPER FROM FACP OUTPUT CIRCUIT FACP OUTPUT EOL TRG FACP NO C NC FACP INTERFACE N O TRIGGER INPUT TRG FACP NO C NC FACP INTERFACE ...

Page 12: ... TRG FACP Fig 9 Normally Closed Non Latching FACP trigger input Fig 10 Normally Closed Latching FACP trigger input with reset This output has not been evaluated by UL Fig 8 Normally Open FACP Latching trigger input with reset This output has not been evaluated by UL N C RESET SWITCH N O TRIGGER INPUT JUMPER TRG NO C NC FACP Hook Up Diagrams ...

Page 13: ...eFlowNA8 Series Installation Guide 13 Notes ...

Page 14: ... 14 eFlowNA8 Series Installation Guide Notes ...

Page 15: ... 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Enclosure Dimensions BC400 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info al...

Page 16: ...remote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output state change and unit temperature Access control and user managment Restrict read write Restrict users to specific resources Two 2 integral network controlled Form C Relays Three 3 programmable inpu...

Reviews: