background image

 

- 2 - 

ALTV615DC1016 Series Installation Guide

Overview:

ALTV615DC1016 Series DC CCTV Power Supplies provide 6-15VDC distributed via sixteen (16) fuse or PTC 

protected outputs for powering CCTV cameras, heaters, and other video accessories.

Sixteen (16) Output ALTV615DC1016 Reference Chart:

Altronix 

Model Number

Total

Output 

Current 

(Power)

Output 

Voltage

Number

of

Outputs

PTC

Protected

Outputs

(auto-

resettable)

Fuse 

Protected

Outputs

Output 

Current

(max. per

output)

115VAC

50/60Hz

Input

Current

ALTV615DC1016

10A

6-15VDC

16

P

3.5A

1.9A

ALTV615DC1016CB

10A

6-15VDC

16

P

2.5A

1.9A

Specifications:

Input:

•  Input 115VAC, 50/60 Hz, 1.9A.

Output:

•  Sixteen (16) fuse or PTC protected outputs.

•  6VDC to 15VDC field adjustable.

•  10A total continuous supply current.

•  Filtered and electronically regulated outputs.

Features:

•  AC input and DC output LED indicators.

•  Illuminated power disconnect circuit breaker 

  with manual reset. 

•  Unit maintains camera synchronization.

•   Ease of installation saves time and eliminates 

  costly labor.

Enclosure Dimensions 

(H x W x D approx.)

:

  13.5” x 13” x 3.25”

  (342.9mm x 330.2mm x 82.6mm)

Installation Instructions:

1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 

  in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 

  the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower 

  two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s 

  upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pg. 4)

. Secure enclosure to earth ground. 

2. Connect AC power to the two black and two white flying leads of the transformer 

(Fig. 1, pg. 3)

.

  Units with line cord installed skip Step #2.

3. Plug the line cord into a grounded AC receptacle 

(Fig. 1b, pg. 3)

.

4. Adjust output voltage (unit is factory set at 12VDC): use the trimpot on the power supply board 

  prior to connecting CCTV devices 

(Fig. 1a, pg. 3)

.

5. Measure output voltage before connecting devices. This helps avoiding potential damage.

  Terminals marked [1P - 16P] are positive (+) and terminals marked [1N - 16N] are negative (–).

 

CAUTION: Determine the maximum operating voltage of the equipment being powered before 

  adjusting the output voltage.

6.

 

Connect devices to terminals marked [1P - 1N] through [16P - 16N] on PD16W/PD16WCB board 

 

(Fig. 1, pg. 3)

,

 

carefully observing correct polarity.

7. Green LED will illuminate when unit is powered.

8. Upon completion of the wiring, secure enclosure door with screws (supplied).

  Caution: Equipment must be installed/serviced by authorized/trained personnel only. 

  Shut branch circuit power before installing/servicing equipment.

WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or 

moisture. This installation should be made by qualified service personnel and should 

conform to the National Electrical Code and all local codes.