Altronix AL602ULADAJ Installation Manual Download Page 3

 

AL602ULADAJ Installation Guide 

- 3 -

Overview:

Altronix AL602ULADAJ is an extremely cost effective 6.5A remote power supply/battery charger. It may be connected 

to any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC such 

as strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power to support 

system accessories. The unit delivers electronically regulated and filtered 24 volt power to Class B or Class A NAC 

loop circuits. The 6.5A max. alarm current can be divided between the four (4) outputs for powering NAC devices. 

Each output is rated at 2.5A max., and can be independently programmed for Steady, Temporal Code 3 or Strobe 

Synchronization. All outputs may be programmed for Input to Output Follower Mode (output will follow input). An 

individual output of 4A is achieved by paralleling 2 outputs. In non-alarm condition independent loop supervision for 

Class A and/or Class B FACP NAC circuits is provided. In the event of a loop trouble, the FACP will be notified via the 

steered input (Input 1 or Input 2). In addition, there are common trouble output terminals (NC, C, NO) which are used 

to indicate general loop/system trouble. A common trouble input is provided for optional NC (normally closed) devices 

to report trouble to the FACP. Two (2) FACP signaling outputs can be employed and directed to control supervision 

and power delivery to any combination of the four (4) outputs. 

Specifications:

 Agency  Listings:

•  UL Listed Control Units and Accessories for 

  Fire Systems (UL 864). 

•  MEA - NYC Department of Buildings Approved.

•  CSFM - California State Fire Marshal Approved.

•  FM - Factory Mutual Approved.

•  NFPA 72 Compliant.

Input:

•   Power input 120VAC, 60 Hz, 4A.

•  Two (2) Class A or two (2) Class B FACP inputs.

•  Two (2) NC dry contact trigger inputs.

• 

Input Ratings:

  INP1 and INP2: 

     

8-30VDC 6.5mA max from FACP. 

     

12V 6.5mA, 24V 6.5mA from FACP.

Output:

•  24VDC @ 6.5A max total alarm current.

•  2.5A max current per output.

•  Separate 1.0A auxiliary output.

•  Two (2) outputs may be paralleled for more power 

  on an indicating circuit 

(see 02 Application Guide).

•  Programmable supervised indicating circuit outputs:

  Four (4) Class B or Two (2) Class A or 

  One (1) Class A and Two (2) Class B 

 

(see 02 Application Guide).

•   Thermal and short circuit protection with auto reset. 

Battery Backup:

•  Charging voltage is 26.2-26.4VDC.

•   Built-in charger for sealed lead acid or 

  gel type batteries. 

•   Automatic switchover to stand-by battery when 

  AC fails.

•  Zero voltage drop when switching over to 

  battery backup. 

Supervision: 

•  AC fail supervision (form “C” contact, 1A/28VDC). 

  Factory set for 30 seconds with optional 2.5 to 3 

  hour delay setting (field selectable).

•  Instant local AC trouble reporting relay

  (form “C” contact, 1A/28VDC).

•  Battery presence and low battery supervision 

  (form “C” contact, 1A/28VDC).

Visual Indicators: 

•  Input and output status LED indicators. 

Special Features: 

•  2-wire horn/strobe Sync mode allows 

  audible notification appliances (horns) and 

  visual notification appliances (strobes) to be 

  silenced/deactivated at the same time.

•  Sync protocols include Potter/Amseco, Gentex

®

  System Sensor

®

, and CooperWheelock

®

•  Temporal Code 3, Steady Mode, Input to Output

  Follower Mode (maintains synchronization of 

  notification appliances circuit).

•  Compatible with 12VDC or 24VDC fire panels. 

•  Output loop supervision steered to Input 1 or Input 2.

•  Signal circuit trouble memory (helps identify 

  intermittent loop problems).

•  Common trouble input and output for external 

  trouble signals tie-in.

•  Ground fault detection. 

•  Unit includes power supply, red enclosure, 

  cam lock, and battery leads.

Enclosure Dimensions 

(approx. H x W x D)

:

  18” x 14.5” x 4.5” 

  (457.2mm x 368.3mm x 114.3mm).

WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. 

This installation should be made by qualified service personnel and should conform to all local codes.

Summary of Contents for AL602ULADAJ

Page 1: ...nstallation Guide see Application Guide for additional information Rev 111819 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ ...

Page 2: ...g 5 Amount of Notification Appliances per NAC pg 6 Terminal Identification Table AL800LGK9E Logic Board pg 6 AL600ADA Power Supply Board pg 7 LED Diagnostics pg 7 Battery Calculation Worksheet pg 8 Hookup Diagram pg 9 Optional Hookups pg 10 Maintenance pg 10 Appendix A Compatible UL cUL Listed Devices for Synchronization A 1 Strobes Horns and Horn Strobes pg 11 Appendix B UL Listed Compatible Devi...

Page 3: ...INP1 and INP2 8 30VDC 6 5mA max from FACP 12V 6 5mA 24V 6 5mA from FACP Output 24VDC 6 5A max total alarm current 2 5A max current per output Separate 1 0A auxiliary output Two 2 outputs may be paralleled for more power on an indicating circuit see 02 Application Guide Programmable supervised indicating circuit outputs Four 4 Class B or Two 2 Class A or One 1 Class A and Two 2 Class B see 02 Appli...

Page 4: ...4 Stand by Specifications pg 4 Output Programming Selection Table pg 5 Sync Mode Selection Table pg 5 Terminal Identification Table pgs 6 7 LED Status Indication Table pg 7 1 Mount the unit in the desired location Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure Install two upper fasteners and screws in the wall with the screw heads protruding Place the enc...

Page 5: ... mode is designed to work with the Amseco series of horns strobes and horn strobes to provide a means of synchronizing the Temporal coded horns synchronizing the flash timing of the strobe allowing audible notification appliances horns and visual notification appliances strobes to be silenced deactivated at the same time Gentex Sync Mode Gentex is a registered trademark of Gentex Corporation 1 2 3...

Page 6: ...ugh OUT4 Output Programming Selection Table pg 5 Note these inputs are unidirectional and will not report a trouble condition to the FACP OUT1 OUT2 OUT3 OUT4 Supervised Notification appliances are connected to these regulated outputs see 02 Application Guide pg 2 4 Each power limited output will supply 2 5A Two 2 outputs may be connected in parallel for a maximum NAC output capability of 4A Total ...

Page 7: ... Low battery condition will report at approximately 21VDC Battery presence detection will report with in 180 seconds after battery remains undetected missing or removed A restored battery will report within 30 seconds LED Diagnostics AL600ADA Power Supply Board Red DC Green AC Power Supply Status ON ON Normal operating condition ON OFF Loss of AC Stand by battery is supplying power OFF ON No DC ou...

Page 8: ...Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 6 5A 6500mA 0mA mA D Total alarm current mA mA E Total current ratings converted to amperes line D x 0 001 A A F Number of standby hours 24 for NFPA 72 Chapter 1 1 5 2 5 H G Multiply lines E and F Total stand by AH AH H Alarm sounding period in hours For example 5 minutes 0 0833 hours ...

Page 9: ... 1 ON 1 Compatible Special Application Devices See Compatibility List Non Supervised Class E This connection is used to monitor AC and Bat Fail and will cause a simultaneous trouble condition to the FACP s IN1 and IN2 Non Supervised Class E AC Local Input Fuse Power Limited Supervised Power Limited Common trouble output to Digital Communicator or Local Annunciator Dry output Contact Form C contact...

Page 10: ...O C should connect to the host control panel for local annunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to remain inactive For optional hookups see Fig 2b Maintenance Unit should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions...

Page 11: ...C2R UL SCRH UL SPSCWVH P UL SRHK R UL P2RHK P UL PC2R P UL SCRH P UL SPSR UL SRK UL P2RHK R UL PC2RH UL SCRH SP UL SPSR P UL SRK P UL P2RK UL PC2RH P UL SCRHK UL SPSRH UL SRK R UL P2RK P UL PC2RH SP UL SCRK UL SPSRH P UL SW UL P2RK R UL PC2RHK UL SCW UL SPSRHK UL SW ALERT UL P2W UL PC2RK UL SCW CLR ALERT UL SPSRK UL SW CLR ALERT UL P2W P UL PC2W UL SCW P UL SPSRK P UL SW P UL P2W SP UL PC2W P UL S...

Page 12: ...75PWR UL GECG24PWR W UL WSSPK24 15 75AWR AWW UL WSSPKA24 15 75PWW UL GECR24PWR W UL GES24 177WR UL WSSPKB24 15 75PWR UL GCSA24PCR W UL GES24 177WW UL WSSPKB24 15 75PWW UL GCSB24PCR W UL GES24 15 75WR UL WSSPKG24 15 75PWR UL GCSG24PCR W UL GES24 15 75WW UL WSSPKG24 15 75PWW UL GCSR24PCR W UL GEC24 177WR UL WSSPKR24 15 75PWR UL GCCA24PCR W UL GEC24 177WW UL WSSPKR24 15 75PWW UL Potter Amseco CM24CR ...

Page 13: ...FR UL cUL CH90 24MCC FW UL cUL E90H 24MCCH FW UL cUL LHSW A UL cUL RSS 24MCWH FW UL cUL CH90 24MCCH FR UL cUL EET90 24MCCH FR UL cUL LHSW AL UL cUL RSSA 24MCC NW UL CH90 24MCCH FW UL cUL ET 1010 R UL LHSW N UL cUL RSSA 24MCCH NW UL E50 241575W FW UL cUL ET 1010 W UL LSPSTR UL cUL RSSB 24MCC NW UL E50 24MCWH FR UL cUL ET70 241575W FR UL cUL LSPSTR AL UL cUL RSSB 24MCCH NW UL E50 24MCWH FW UL cUL ET...

Page 14: ...B 2 below lists relays compatible with AL602ULADAJ AUX output and Outputs 1 8 when programmed as AUX Manufacturer Model Current mA Manufacturer Model Current mA System Sensor PR 1 15 System Sensor R 20T 40 PR 2 30 R 24T 40 PR 3 30 R 10E 23 EOLR 1 30 R 14E 23 R 10T 23 R 20E 40 R 14T 23 R 24E 40 ...

Page 15: ...AL602ULADAJ Installation Guide 15 Notes ...

Page 16: ...02ULADAJ H03U MEMBER 6 0 152 4mm 1 5 38 1mm 2 5 63 5mm 1 0 25 4mm 2 75 69 9mm 2 75 69 9mm 4 5 114 3mm 4 5 114 3mm 14 5 368 3mm 1 0 25 4mm 1 5 38 1mm 8 5 215 9mm 18 0 457 2mm 18 0 457 2mm 18 0 457 2mm 1 25 31 75mm 1 25 31 75mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 2 5 63 5mm 2 5 63 5mm 14 5 368 3mm 14 5 368 3mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm Enclosure Dimensions H x W...

Reviews: