background image

Overview: 

The AL600UL3/AL600UL3X Triple Output Power Supply/Charger is specifically designed for use with access control 
and fire-protective signaling systems and accessories. The AL600UL3/AL600UL3X converts a 115VAC 60Hz input into 
three (3) outputs (see specifications)

Specifications: 

Agency Listings: 

• 

 

UL

 

Listed

 

for

 

Access

 

Control

 

System

 

Units

 

(UL 294) and UL Listed Standard for Safety for Fire 
Protective Signaling Systems (UL 1481). 

• 

 

cUL

 

Listed:

 

CSA Standard C22.2 No.205-M1983, 

Signal Equipment. 

• 

 

MEA

 

- NYC

 

Department

 

of

 

Buildings

 

Approved.

 

• 

 

CSFM

 

- California

 

State

 

Fire

 

Marshal

 

Approved.

 

• 

 

NFPA

 

72

 

compliant

 

(Fire-Protective

 

Signaling

 

Service).

 

Input: 

• 

 

Input

 

115VAC

 

/

 

60Hz,

 

3.5

 

amp.

 

• 

 

AC

 

input

 

and

 

DC

 

output

 

LED

 

indicators.

 

Output: 

• 

 

Class

 

2

 

Rated

 

power-limited

 

outputs

 

(5VDC and 12VDC only). 

• 

 

1.75

 

amp

 

continuous

 

supply

 

current

 

at

 

5VDC and 12VDC regulated outputs. 

• 

 

3

 

amp

 

continuous

 

supply

 

current

 

at

 

24VDC

 

(for Fire-Protective Signaling use Special applications)

• 

 

Filtered

 

and

 

electronically

 

regulated

 

outputs.

 

100 mV p/p output ripple. 

Output 

(cont’d.)

• 

 

Short

 

circuit

 

and

 

thermal

 

overload

 

protection.

 

Battery Backup 

• 

 

Built-in

 

charger

 

for

 

sealed

 

lead

 

acid

 

or

 

gel

 

type

 

batteries.

 

• 

 

Automatic

 

switch

 

over

 

to

 

stand-by

 

battery

 

when

 

AC fails. 

• 

 

Maximum

 

charge

 

current

 

0.7

 

amp.

 

• 

 

Zero

 

voltage

 

drop

 

when

 

switched

 

over

 

to

 

battery

 

backup.

 

Supervision: 

• 

 

AC

 

fail

 

supervision

 

(form

 

“C”

 

contacts).

 

• 

 

Low

 

battery

 

and

 

battery

 

presence

 

supervision

 

(form “C” contacts). 

Additional Features: 

 

Power

 

supply,

 

enclosure,

 

cam

 

lock

 

and

 

battery

 

leads.

 

• 

 

Enclosure

 

accommodates

 

up

 

to

 

two

 

(2)

 

7AH

 

batteries.

 

Enclosure

 

dimensions

 

(H

 

x

 

W

 

x

 

D):

 

AL600UL3 
13.5”

 

x

 

13”

 

x

 

3.25”

 

(342.9mm

 

x

 

330.2mm

 

x

 

82.55mm)

 

AL600UL3X 
15.5”

 

x

 

12”

 

x

 

4.5”

 

(393.7mm

 

x

 

304.8mm

 

x

 

114.3mm).

 

Stand-by Specifications 

(Current is specified on AL3XB input)

Output 

4 hr. of Stand-by & 

5 Minutes of Alarm 

24 hr. of Stand-by & 

5 Minutes of Alarm 

60 hr. of Stand-by & 

5 Minutes of Alarm 

5VDC - 1.75 amp 

5VDC - 0.3 amp 

5VDC - 0.1 amp 

24VDC / 40AH Battery 

12VDC - 1.75 amp 

12VDC - 0.3 amp 

12VDC - 0.1 amp 

24VDC - 3 amp 

24VDC - 0.3 amp 

24VDC - 0.1 amp 

Installation Instructions: 

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local 
codes and authorities having jurisdiction.  Product is intended for indoor use only. 
1.  Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the 

enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s 
upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the 
enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two 
upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 7-8)
Secure enclosure to earth ground. It is recommended to first review the following tables for screw terminals, switch 
selection and LED status indications. This will greatly facilitate installation hook-up. 
Carefully review: 
Stand-by Specifications 

(pg. 2) 

LED Diagnostics 

(pg. 4) 

Terminal Identification Table 

(pg. 4) 

2.  Connect AC power (115VAC 60Hz) to the terminals marked [L, N] (Fig. 1, pg. 3). Use 14 AWG or larger for all 

power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG for power-limited circuits 
(AC Fail/Low Battery reporting). 
Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery Wires). 
Minimum 0.25” spacing must be provided. 
For Fire Alarm applications the outputs are “Special Applications” only, see list (refer to Appendix A, pg. 5)

3.  Measure output voltage before connecting devices. This helps avoiding potential damage. 

- 2 -

AL600UL3/AL600UL3X 

                    Available from A1 Security Cameras 

    www.a1securitycameras.com email: [email protected]

Summary of Contents for AL600UL3

Page 1: ...stallation Guide For a red enclosure add an R suffix to the part e g AL600UL3R Altronix Corp 140 58th St Brooklyn NY LISTED SECURITY SIGNALING LISTED Available from A1 Security Cameras www a1securityc...

Page 2: ...d by 5 Minutes of Alarm 60 hr of Stand by 5 Minutes of Alarm 5VDC 1 75 amp 5VDC 0 3 amp 5VDC 0 1 amp 24VDC 40AH Battery 12VDC 1 75 amp 12VDC 0 3 amp 12VDC 0 1 amp 24VDC 3 amp 24VDC 0 3 amp 24VDC 0 1 a...

Page 3: ...t AC Delay jumper Fig 1a pg 3 9 Please ensure that the cover is secured with the provided Key Lock Fig 1 CAUTION De energize unit prior to servicing For continued protection against risk of electric s...

Page 4: ...d Bat Battery Status ON Normal operating condition OFF Battery fail low battery Terminal Identification AL600ULXB Power Supply Charger Terminal Legend Function Description L G N 115VAC 60 Hz DC 24VDC...

Page 5: ...0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24 volt Pho...

Page 6: ...Notes 6 AL600UL3 AL600UL3X Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com...

Page 7: ...30mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm 1 0 25mm 1 0 10 5 1 0 1 0 25mm 0 75 19mm 0 75 19mm 0 9375 24mm 0 9375 24mm 11 0...

Page 8: ...14mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23 310 64mm 4 615 117 22mm 1 5 1 5 4 615 4 615 1 25 38 1mm 117 22mm 117 22mm 38 1mm Altronix is not responsible for any...

Reviews: