- 2 - 

AL300ULXJ Installation Guide

Overview:

Altronix AL300ULXJ power supply converts a 115VAC, 60Hz input to a 12VDC or 24VDC output.

Features:

Agency Listings:

•  UL Listed: 

 UL294*

  Access Control Systems.

 UL603

 

Power Supplies for use with 

   

Burglar-Alarm Systems. 

 UL1069

   Hospital Signaling and 

   

Nurse Call Equipment. 

 UL1481

   Power Supplies for Fire

    

Protective Signaling Systems.

•  cUL Listed:

 

  CSA Standard C22.2 No.205-M1983,

  Signal Equipment.

• CSFM

 - California State Fire Marshal Approved.

•  NFPA 72 Compliant 

  (Fire-Protective Signaling Service).

Input:

•  Input 115VAC, 60Hz, 3.5A.

•  Input fuse rated @ 5A/250V.

Output:

•  Class 2 Rated power-limited output.

•  12VDC or 24VDC selectable output.

  Fire Alarm applications outputs are “Special 

 Applications” 

(refer to Appendix A, pg. 6).

  Burglar Alarm Applications (UL 603):

  12VDC = 10VDC-13.2VDC.

  24VDC = 20VDC-26.4VDC.

Output 

(cont’d)

:

•  2.5A total supply current at 12VDC or 24VDC. 

  Do not exceed total output rating of 2.5A @ 

  12VDC or 24VDC per unit.

•  Output fuse rated @ 15A/32V.

•  Filtered and electronically regulated output(s).

•  Short circuit and thermal overload protection.

LED Indicators:

•  AC input, DC output and Battery LED indicators.

Battery Backup:

•  Built-in charger for sealed lead acid or 

  gel type batteries.

•  Automatic switch over to stand-by battery 

  when AC fails.

•  Maximum charge current 0.7A.

•  Zero voltage drop when switched over to 

  battery backup.

Supervision:

•  AC fail supervision (form “C” contacts). 

•  Low battery and battery presence supervision

  (form “C” contacts).

Additional Features:

•  Power supply, enclosure, cam lock and battery leads.

•  For grey enclosure add “G” suffix to the part number.

*Access Control Performance Levels: 

Destructive Attack - I; Endurance - IV; Line Security - I; 

Stand-by Power - IV.

Power Supply Output Specifications:

Output VDC

Switch Position

12VDC

SW1 - ON 

(Fig. 1c, pg. 5)

24VDC

SW1 - OFF 

(Fig. 1c, pg. 5)

Stand-by Specifications 

(total current shown)

:

Output

4 hr. of Stand-by and

5 Minutes of Alarm

24 hr. of Stand-by and

5 Minutes of Alarm

60 hr. of Stand-by and

5 Minutes of Alarm

12VDC / 40AH Battery

Stand-by = 2.5A

Alarm = 2.5A

Stand-by = 1.0A

Alarm = 2.5A

Stand-by = 300mA

Alarm = 2.5A

24VDC / 12AH Battery

Stand-by = 200mA

Alarm = 2.5A

24VDC / 40AH Battery

Stand-by = 2.5A

Alarm = 2.5A

Stand-by = 1.0A

Alarm = 2.5A

Stand-by = 300mA

Alarm = 2.5A

ON

OFF - 24V

ON - 12V

Summary of Contents for AL300ULXJG

Page 1: ...add a G suffix to the part number AL300ULXJ Power Supply Charger Installation Guide Rev 030619 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ ...

Page 2: ...t s Short circuit and thermal overload protection LED Indicators AC input DC output and Battery LED indicators Battery Backup Built in charger for sealed lead acid or gel type batteries Automatic switch over to stand by battery when AC fails Maximum charge current 0 7A Zero voltage drop when switched over to battery backup Supervision AC fail supervision form C contacts Low battery and battery pre...

Page 3: ...to Appendix A pg 6 4 Measure output voltage before connecting devices This helps avoiding potential damage When servicing the unit AC mains should be removed 5 Connect devices to the terminals marked DC Fig 1 pg 5 6 For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired ...

Page 4: ...Relay normally ener gized when AC power is present Contact rating 1A 28VDC AC Fail condition will report approximately within one 1 minute after loss of AC To delay report for 6 hours cut jumper J1 on the Power Supply Board AC trouble output delay option If this mode is selected the Power Supply Board must be reset by removing all power to it for 30 seconds Bat Fail NC C NO Indicates low battery c...

Page 5: ...against risk of electric shock and fire hazard replace fuse with the same type and rating Do not expose to rain or moisture CAUTION Optional rechargeable stand by batteries must match the power supply output voltage setting Keep power limited wiring separate from non power limited Use minimum 0 25 spacing 115VAC power mains non power limited Optional Rechargeable Stand by Battery Optional Recharge...

Page 6: ...ric w 135o Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24 volt Photoelectric I3 0 05 23 4WT B 12 24 volt Photoelectric I3 w Therm 0 05 23 4WTA B 12 24 volt I3 Photo w Therm Sounder 0 05 35 4WTR B 12 ...

Page 7: ...AL300ULXJ Installation Guide 7 Notes ...

Page 8: ...5 38 1mm 1 5 38 1mm 1 5 38 1mm 2 5 63 5mm 2 5 63 5mm 14 5 368 3mm 14 5 368 3mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm Enclosure Dimensions H x W x D approximate 18 x 14 5 x 4 625 457 2mm x 368 3mm x 117 5mm Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info al...

Reviews: