6. Connect appropriate signaling notification devices to AC Fail supervisory relay outputs marked [N.C., N.O., C].
Note: To meet UL requirements, AC Supervisory outputs must be connected to the zone of Alarm Control Panel or to
visual AC trouble indicator.
7. For Access Control Device and Fire Alarm Interface connections see Application Diagrams, pg. 4 and Terminal
Identification Chart, pg. 3.
8. Secure enclosure door with the screws supplied to assure proper ground.
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage level
(see Power Supply Output Specifications Chart, pg. 1).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at the
battery terminal and at the board terminals marked [+ BAT -- ] to ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharge is 0.40A.
Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.
LED Diagnostics:
Red (DC)
Green (AC)
(on front door)
Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Battery backup is powering output.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or missing stand-by battery. No DC output.
SW1
VR1
+ BAT --
AC
AC
LOCK + COM - AUX +
FACP
AUX -
NC
NO
C
TRG1 TRG2
SW1 ON -24V
OFF - 12V
NC
C
NO
AC
FAIL
XFMR
Green
Lead
(ground)
Stand-by
Battery
(optional)
Constant output
(not affected
by trigger)
Switched
DC output
(trigger control)
Black
Lead
White
Lead
115VAC input
60 Hz,
0.6A
AC
DC
JUMPER
Reset
Switch
AC Power
LED
AC
Molex
Connector
ON
- 2 -
AL175ULX2