6.  Connect appropriate signaling notification devices to AC Fail supervisory relay outputs marked [N.C., N.O., C]. 
 

Note: To meet UL requirements, AC Supervisory outputs must be connected to the zone of Alarm Control Panel or to 

 

visual AC trouble indicator. 

7.  For Access Control Device and Fire Alarm Interface connections see Application Diagrams, pg. 4 and Terminal
 

Identification Chart, pg. 3

8.  Secure enclosure door with the screws supplied to assure proper ground.

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage level 
(see Power Supply Output Specifications Chart, pg. 1).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at the 
battery terminal and at the board terminals marked [+ BAT -- ] to ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharge is 0.40A.
Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.

LED Diagnostics:

Red (DC)

Green (AC)

(on front door)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Battery backup is powering output.

OFF

ON

No DC output. 

OFF

OFF

Loss of AC. Discharged or missing stand-by battery. No DC output.

SW1

VR1

+ BAT --

AC

AC

LOCK +  COM - AUX +

FACP

AUX -

NC

NO

C

TRG1 TRG2

SW1  ON -24V

 

OFF - 12V

NC 

  

  

NO

AC 
FAIL

XFMR

Green 

Lead

(ground)

Stand-by

Battery

(optional)

Constant output

(not affected

by trigger) 

Switched

DC output

(trigger control) 

Black

Lead

White

Lead 

115VAC input

60 Hz,

0.6A

AC

DC

JUMPER

Reset

Switch

AC Power

LED

AC

Molex

Connector

ON

- 2 - 

AL175ULX2

Reviews: