- 4 -
42 ULADA Application Guide
5. Synchronizing NAC Power Extender Using Built-in Sync Protocol:
AL642/AL842/1042ULADA, R1042ULADA have built-in protocols to support Potter/Amseco, Gentex
®
, System
Sensor
®
, CooperWheelock
®
two-wire synchronizable devices, therefore an external sync module is not required
(Output Programming Selection Table, pg. 6)
. In these modes, Input 1 is always used to activate visual notification
appliances (strobes), and Input 2 is used to activate and silence audible notification appliances (strobes).
Note:
Input 1 has to be activated in all the configurations.
Fig. 5a
For continuous loop circuit use 2.2K EOL (Altronix Model# AL-EOL22).
NAC Power Extender:
DIP Switches set for desired Sync Protocol (ex. Gentex
®
,
System Sensor
®
, Amseco, CooperWheelock
®
).
FACP
(Fire Alarm
Control Panel)
2.2K
EOL
2.2K
EOL
2.2K
EOL
+ AUX1 ----
+ OUT1 ----
+ LOOP1 ----
+ LOOP2 ----
+ OUT2 ----
+ OUT3 ----
+ LOOP3 ----
+ LOOP4 ----
+ OUT4 ----
+ RET1 ----
+ IN1 ----
+ RET2 ----
+ IN2 ----
C "DRY2" NC
C "DRY1" NC
+ AUX1 ----
EOL or
Next Device.
For Class A
configuration
return to FACP
EOL or
Next Device.
For Class A
configuration
return to FACP
NAC Power Extender:
DIP Switches set to Input to Output Follower Mode
2.2K
EOL
2.2K
EOL
2.2K
EOL
+ AUX1 ----
+ OUT1 ----
+ LOOP1 ----
+ LOOP2 ----
+ OUT2 ----
+ OUT3 ----
+ LOOP3 ----
+ LOOP4 ----
+ OUT4 ----
+ RET1 ----
+ IN1 ----
+ RET2 ----
+ IN2 ----
C "DRY2" NC
C "DRY1" NC
+ AUX1 ----
Control Circuit
No Notification Appliances Allowed
To EOL or next
NAC Power Extender
For Class A configuration
return to + LOOP4 -