AL1012X220 series

 

Note:

 When servicing the unit, AC mains should be removed.

5.  For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the    

 

loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.

6.  Connect appropriate signaling notification devices to terminals marked [AC FAIL] and [BAT FAIL] 

(Fig. 1, pg. 5)

 

 

supervisory relay outputs.

 

Note:

 When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay must be used to 

 

provide a visual indication of AC power on.

Wiring:

USE 14 AWG or larger for all power connections.

Note:

 Take care to keep power-limited circuits separate from non power-limited wiring (220VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

 Under normal load conditions the DC output voltage should be checked for proper voltage level.

Battery Test:

 Under normal load conditions check that the battery is fully charged, check specified voltage both at the

battery terminal and at the board terminals marked [– BAT +] to ensure that there is no break in the battery connection wires.

Note:

 Maximum charging current under discharges is 0.7A.

Note:

 Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.

LED Diagnostics:

AL1012XB220 - Power Supply Board

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

PD4/PD4CB/PD8/PD8CB - Power Distribution Module

Green

Power Distribution Module Status

ON

Normal operating condition.

OFF

No Power Output.

Terminal Identification:

AL1012XB220 - Power Supply Board

Terminal Legend Function/Description

L, N

Connect 220VAC (working range 198VAC - 256VAC), 50/60Hz to these terminals: 

L to Hot, N to Neutral. Do not use the [G] terminal.

---  DC +

12VDC @ 10A continuous non power-limited output. 

AC FAIL

NC, C, NO

Indicates loss of AC power, e.g. connect to annuciator/alarm panel. Relay normally energized when 

AC power is present. Contact rating 1A @ 30VDC. AC Fail condition will report approximately 

one (1) minute after the loss of AC. To delay report for 6 hours cut jumper J1 on the Power Supply 

Board (AC trouble output delay option). If this mode is selected, the Power Supply Board must be 

reset by removing all power to it for 30 seconds.

BAT FAIL

NO, C, NC

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC 

power is present. Contact rating 1A @ 30VDC. Low battery conditions will report approximately 

10.5VDC. Battery presence detection will report approximately 1 minute after battery remains unde-

tected (missing or removed).

+ BAT --- 

Stand-by battery connections. Maximum charge rate 0.7A.

PD4/PD4CB/PD8/PD8CB - Power Distribution Module

Terminal Legend

Function/Description

PD4/PD4CB

PD8/PD8CB

1P to 4P

1P to 8P

Positive DC power outputs.

1N to 4N

1N to 8N

Negative DC power outputs.

Summary of Contents for AL1012X220 Series

Page 1: ...t 220VAC 50 60Hz as follows Green branch wire connects to earth safety ground lug Line and Neutral to the connector on power supply board marked L N respectively Fig 1 pg 3 Use 14 AWG or larger for all power connections Battery DC output AC input Use 22 AWG to 18 AWG for power limited circuits AC Fail Low Battery reporting 3 Mea sure output voltage before connecting devices This helps avoiding pot...

Page 2: ...n AC Power Supply Status ON ON Normal operating condition ON OFF Loss of AC Stand by battery supplying power OFF ON No DC output OFF OFF Loss of AC Discharged or no stand by battery No DC output PD4 PD4CB PD8 PD8CB Power Distribution Module Green Power Distribution Module Status ON Normal operating condition OFF No Power Output Terminal Identification AL1012XB220 Power Supply Board Terminal Legend...

Page 3: ...AIL AC FAIL VR1 15 5A 250V AC DELAY Provide 0 25 separation between all other circuits 12VDC Rechargeable Battery optional Ground Lug Fig 1 INPUT LED PD4 POWER DISTRIBUTING UNIT 1P 2P 3P 4P FUSED OUTPUTS 1N 2N 3N 4N COMMON OUTPUTS F1 F1 F2 F3 F4 COMMON POWER OUTPUTS 1P 1N 2P 2N 3P 3N 4P 4N DC Output to devices From Power Supply Board Factory Installed Used on PTC Models PD8 N COMMON POWER OUTPUTS ...

Page 4: ...ER Enclosure Dimensions BC400 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm 1 75 44 45mm 1 75 44 45mm 4 5 114 3mm 1 25 31 75mm 4 5 114 3mm 1 25 31 75mm 1 25 31 75mm 1 25 31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm...

Reviews: