ACM4E/ACM4CBE Installation Guide
Overview:
Altronix ACM4E and ACM4CBE Access Power Controllers convert one (1) 12 to 24 volt AC or DC input into four (4)
independently controlled fused or PTC protected outputs. These power outputs can be converted to dry form “C”
contacts (ACM4E only). Outputs are activated by an open collector sink or normally open (NO) dry trigger input from
an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. The units will route power to a variety of
access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will
operate in both Fail-Safe and/or Fail-Secure modes. Units are designed to be powered by one common power
source which will provide power for both the board operation and locking devices, or two (2) totally independent
power sources, one (1) providing power for board operation and the other for lock / accessory power. The FACP
Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire
alarm disconnect feature is individually selectable for any or all of the eight (8) outputs.
ACM4E and ACM4CBE Configuration Reference Chart:
Altronix
Model
Number
Fuse Protected Outputs
PTC Protected Power-Limited Outputs
Input Fuse Rating
Output Ratings
Class 2 Rated Power- Limited Outputs
Agency Listing
UL Listings and
File Numbers
ACM4E
P
–
10A/
250V
3.0A
*
UL 294** (File # BP6714)
UL Listed for
Access Control System Units.
“Signal Equipment” Evaluated to CSA
Standard C22.2 No.205-M1983
ACM4CBE
–
P
2.5A
P
*When used with Class 2 Rated Power-Limited power supply.
**ANSI/UL 294 7th Ed. Access Control Performance Levels:
Destructive Attack - I; Endurance - IV; Line Security - I; Stand-by Power - I.
Specifications:
• 12 to 24 volt AC or DC operation (setting not required).
(0.6A @ 12 volt, 0.3A @ 24 volt current consumption with all relays energized).
• Power supply input options:
a) One (1) common power input (board and lock power).
b) Two (2) isolated power inputs (one (1) for board power and one (1) for lock/hardware power).
• Four (4) Access Control System trigger inputs:
a) Four (4) normally open (NO) inputs.
b) Four (4) open collector sink inputs.
c) Any combination of the above.
• Four (4) independently controlled outputs:
a) Four (4) Fail-Safe and/or Fail-Secure power outputs.
b) Four (4) dry form “C” 5A rated relay outputs (ACM4E only).
c) Any combination of the above (ACM4E only).
• Four (4) auxiliary power outputs (unswitched).
• Output ratings:
-
ACM4E:
Fuses are rated 3.0A each.
-
ACM4CBE:
PTCs are rated 2.5A each.
• Main fuse is rated at 10A.
Note:
Total output current is determined by the power supply, not to exceed a maximum of 10A total.
• Red LEDs indicate outputs are triggered (relays energized).
• Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the eight (8) outputs.
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC) dry contact input.
b) Polarity reversal input from FACP signaling circuit.
• FACP output relay (form “C” contact rated @ 1A 28VDC, not evaluated by UL).
• Green LED indicates when FACP disconnect is triggered.
• Removable terminal blocks facilitate ease of installation.
Enclosure Dimentions (H x W x D): 8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm).