88
88
88
88
Digital 8-frequency conversion
active infrared detector
Installation guide
ABH-B series
Alert distance
Model
Outdoor
Indoor
No. of beams
4 beams
Detection mode
4 beams blocked simultaneous
Optical source
Infrared digital pulse beam
Response speed
50 240msec adjustable
Alarm output
Relay contact output: NO. NC contact rating: AC/DC30V 0.5AMax
Power supply
Power consumption
Operation temperature & humidity
-25 -55 5%-95%RH(relative humidity)
Tamper output
Contact output: NC contact rating DC24V 0.3Amax
Optical axis adjustment(H)
Optical axis adjustment(V)
Material
PC resin
Net weight
2000g(retransmitter)
Gross
I. Specification
II. Parts
Wiring hole
Wiring terminal
Lens
Horizontal fine-tune knob
Vertical fine-tune knob
Housing
Features:
1. Under BUS connection mode: The digital display of RX synchronize with the TX after the RX receive the signal from BUS
2. Anti-fog function: When signal strength decrease slowly to 0.8V,the detector will active anti-fog alarm( TBL output), when
signal decrease to 0.4V, will active alarm, when signal get back to 1.2V cancel alarm.
III. Installation notice
Impediment presents during setup
ReceiverReceiverReceiverReceiver
Receiver
Transmitter
Receiver
Transmitter
Multi sensors may be used for long-distance
guarding. Please install according to the below
diagram to avoid interference between beams.
Receiver
Transmitter
Transmitter
Receiver
°
°
vertical ±10
Adjustable angle: horizontal ±90
The base is unstable
Direct sunlight,lamplight etc.
Horizontal 180 ( 90 )
vertical ±10°
Installation heigh 0.7m 1.0m
Guarding distance
Beam spread diameter
Model
Guarding distance
Beam spread diameter
IV.Installation method
1.Remove the cover
2.Attach the paper stencil onto the location
where the equipment is to be mounted, and
drill the holes in the positions on its mark.
3.Put the cable through the hole for wiring.
Wiring hole
4.Fix the main body onto the wall
5.Connect the cable to the wire terminal.
Receiver
Transmitter
BUS
BUS
6. DIP setting
Transmitter
Receiver
BUS address setting
Air terminal
Air terminal
BUS address setting
Buzzer ON/OFF setting
FRE.
Mode
Signal strength
Frequency mode
Address mode
Address/frequency alternately
display mode
Table 1
Table 2
Alarm output N.O/N.C setting
Frequency set mode
Frequency set mode
Function set mode
Function set mode
Function setting(table 2)
1. Under frequency mode: The digital display shows the frequency, Set frequency on DIP1.2.3(see table 1)
2. Under address mode: The digital display shows BUS address, set the address on DIP1.2.3.4.5.6
3.Under signal strength mode: The digital display shows the signal strength, the DIP1.2.3.4.5.6 under this mode is invalid
4.Under address/frequency alternately display mode: The digital display shows address and frequency alternately,
the DIP1.2.3.4.5.6 under this mode is invalid
Frequency setting:(First enter frequency setting mode, see table 2)
Then set DIP 1.2.3 to set detector's frequency( see table 1)
BUS address setting:(First enter address mode, see table 2)
Under address mode, Set DIP 1-6 to set the detector's zone address. first set DIP at ON,
the number of the one DIP which set ON puls the other one, then plus 1,
the final result of number is the zone number, example this is zone 18(17+1)