NEC Power-Limited Wiring Requirements for Maximal11EV:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet . All power-limited 
circuit wiring must remain at least 0 .25” away from any non power-limited circuit wiring . Furthermore, all 
power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through differ-
ent conduits . One such example of this is shown below . Your specific application may require different conduit 
knockouts to be used . Any conduit knockouts may be used . For power- limited applications, use of conduit is 
optional . All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or 
equivalent substitute) .
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 3a).

External

Jacketed

Shield

Incorrect Wire

Handling

Correct Wire

Handling

Pull back

external jacketed

shield approx. 1/2”.

Wire

Insulation

Solid Copper

Conductors

Fig. 3

Fig. 3a

Supervisory Connections

(power-limited)

Input

220VAC 50/60Hz

(non power-limited)

Optional Battery

Enclosure

(non power-limited)

DC Output

Wiring

Battery

Connections

(non power-limited)

Summary of Contents for Maximal11EV

Page 1: ...upply 2 12VDC or 24VDC 6A Maximal37EV Power Supply 1 24VDC 10A Power Supply 2 12VDC or 24VDC 6A Maximal75EV Power Supply 1 12VDC 10A Power Supply 2 24VDC 10A Maximal13EV Power Supply 1 12VDC or 24VDC...

Page 2: ...tion pg 5 Power Supply Board Stand by Battery Specifications pg 5 Power Supply Board Output Voltage Settings pg 5 NEC Power Limited Wiring Requirements for Maximal11EV pg 7 NEC Power Limited Wiring Re...

Page 3: ...AL1012XB220 2 3A 5A 250V 12VDC 6A 12VDC 10A 24VDC 6A 12VDC 10A Maximal37EV AL600XB220 AL1024XB2V 2 5A 5A 250V 12VDC 6A 24VDC 10A 24VDC 6A 24VDC 10A Maximal55EV AL1012XB220 AL1012XB220 2 3A 5A 250V 12V...

Page 4: ...batteries are optional When batteries are not used a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired they must be lead acid or gel type Connect batte...

Page 5: ...0 7A AL1024XB2V Power Supply Board maximum charge current is 3 6A Power Supply Board Stand by Battery Specifications Altronix Model Power Supply Board Battery 20 min of Backup 4 hr of Backup 24 hr of...

Page 6: ...l 12VDC Rechargeable Battery Optional 12VDC Rechargeable Battery Optional Line Neutral Line Neutral Input 220VAC 50 60Hz Ground Lug BAT FAIL L G N DC NO C NC NO C NC BAT AC FAIL BAT FAIL Power Supply...

Page 7: ...e different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge...

Page 8: ...re different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge...

Page 9: ...ion may require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing s...

Page 10: ...ay require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitab...

Page 11: ...re different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge...

Page 12: ...0 8mm 6 25 158 75mm 6 25 158 75mm 4 101 6mm 4 101 6mm 2 50 8mm 4 101 6mm 8 9 226 06mm 8 4 213 36mm 7 177 8mm 7 177 8mm 7 177 8mm 8 4 213 36mm 8 5 215 9mm 8 5 215 9mm 7 5 190 5mm 10 254mm 1 5 38 1mm 1...

Reviews: