pag. 29
MDE/A133 2295 001
MX3EG1A
WARNING:
Factory settings may prove not to suit the plant. Therefore, the device must be configured anew on installation.
SPARE
ON
OFF
VALUE
/
/
/
100.0 V
100.0 V
0.30 s
0.10 s
1
2.00 s
15 min
0.2 s
2 %
15 %
4 %
80 %
NORM
0.10 Hz
5 %
10 °
X
0.02 Ubn
PULSE
0.20 s
2.00 s
30.00 s
X
0.50 s
CONT
0.20 s
2.00 s
6000 V
6000 V
/
/
/
/
/
/
TABLE OF SETTINGS
DESCRIPTION
FUNCTION
MAIN
ON
OFF
VALUE
rated
frequency
fn
50
Hz
bar
rated
voltage
Ubn
100.0
V
generator
rated
voltage
Ugn
100.0
V
closing
pulse
time
tc
0.30
s
breaker
closing
time
tr
0.10
s
max. number of parallel sequence attempts
Ns
1
closing interval min. time
twc
2.00 s
parallel
sequence
max.
time
ts
15
min
stability
time
td
0.2
s
max. deviation bar frequency/rated frequency
Dfb
(±)
2
%
max. deviation generator frequency/rated frequency
Dfg
(±)
15
%
max. deviation bar voltage/rated voltage
DUb
(±)
4
%
min.
generator
voltage/rated
voltage
DUg
80
%
live
bar
mode
(LB)
LB
NORM
max.
frequency
difference
Df
(±)
0.10
Hz
max.
voltage
difference
DU
(±)
5
%
max.
phase
difference
Dp(±)
10
°
dead
bar
mode
(DB)
DB
X
dead
bar
level
Ud
0.02
Ubn
frequency regulation mode
CPf
PULSE
frequency
regulation
pulse
time
tfpu
0.20
s
frequency
regulation
min.
pause
time
tfpa
2.00
s
frequency
regulation
max.
pause
time
tfpm
30.00
s
load
pulse
mode
LP
X
load
pulse
time
tlp
0.50
s
voltage regulation mode
CPU
CONT
voltage
regulation
pulse
time
tupu
0.20
s
voltage
regulation
min.
pause
time
tupa
2.00
s
bar
primary
rated
voltage
Ub
TV
6000
V
generator
primary
rated
voltage
Ug
TV
6000
V
oscilloperturbography
trigger
SINC.
OK
oscilloperturbographt
pretrigger
time
2
s
settings in use: MAIN
LCD timed backlighting: OFF
Table C
- FACTORY SETTINGS
/ not to be allocated: the same values as MAIN
settings apply