background image

 

DNP3 Manual 

 

M6xxD/EN M/B

 
M6xx  

Page 10

 

 

 

1.5.3  Tag Registers 

 
The M6xx meters provide a "TAG" BINARY OUTPUT for user identification purposes. DNP sessions 
have an additional tag register (“Tag Register 1”). An 

ANALOGUE OUTPUT BLOCK

 can be issued to 

either point to write a number from 0 to 65,535 in a tag register. Tag registers are also writeable 
through the web interface. 
 
 

1.6  Converting Data to Engineering Units  

 
As mentioned in Section 1.5, the majority of the data is stored in a normalized 2's complement format. 
When displaying these values at another location, it may be desirable to convert this format into 
engineering units.  This conversion is readily accomplished using the following simple scaling 
equations: 
 

BASIC EQUATION FOR NORMALIZED ANALOGUE INPUTS: 

 

 

32768

SEC O N D ARY

Value

N orm alized Scale Factor

Engineering U nits

D efault Full Scale

Scale Factor D ivisor

 
 

The 

Value

 referred to in the equations would be the value stored in the point that you wished to 

convert to engineering units.  For example if you wanted to convert Phase A Amperes into engineering 
units, Value would be the value in ANALOGUE-INPUT point. 
 

ENERGY

 is stored as 32-BIT values in static COUNTER points.  Energy values are in units of 

PRIMARY kWh or kVARh. 
 

FREQUENCY

 is stored as a single binary value that is the actual frequency times 100. 

 

POWER FACTOR

 is stored as the value times 1000.  Negative power factors indicate that the VARs 

are positive.  The sign of the Power Factor is the inversion of the Exclusive-OR of the Watts and VARs 
(i.e. if either or both of the Watts or VARs are negative, then the Power Factor will be negative). 

Summary of Contents for M65B

Page 1: ...ty of their respective companies The technical and other data contained in this document is provided for information only Neither ALSTOM its officers or employees accept responsibility for or should b...

Page 2: ......

Page 3: ...1 5 Configuration 9 1 5 1 Setting CT and VT Ratios 9 1 5 2 Resetting Energy and Demands 9 1 5 3 Tag Registers 10 1 6 Converting Data to Engineering Units 10 1 7 Primary Units 12 1 8 Data Sets and Data...

Page 4: ...ER ETHERNET TCP 21 3 1 DNP IP 21 4 0 DNP3 EVENTS OVERVIEW 22 4 1 ANALOGUE CHANGE EVENTS 22 4 2 FROZEN COUNTER EVENTS 23 4 3 BINARY INPUT CHANGE EVENTS 23 Appendix A Bitronics Legacy DNP3 Point Assignm...

Page 5: ...lation and maintenance As with any product of this nature installation and maintenance can present electrical hazards and should be performed only by properly trained and qualified personnel If the eq...

Page 6: ...d Bethlehem PA 18017 Schneider Automation Inc One High Street North Andover MA 01845 Triangle MicroWorks Inc 2213 Middlefield Court Raleigh NC 27615 Freescale Semiconductor Inc 6501 William Cannon Dri...

Page 7: ...ULD NOT be written continuously Four legacy values are also presented They are CT Scale Factor Normalized Ratio and Divisor and VT Scale Factor Normalized Ratio and Divisor They are derived from the P...

Page 8: ...th status word The DNP protocol allows each device to determine the best method of data transfer The M6xx meters support this by selecting the most appropriate response variation when either the reque...

Page 9: ...aturation 4500 Float Value Integer Value 32768 Scale 4500 Example 90 0 kW stored as 8192 when Volt Scale 20 1 Amp Scale 4 1 T7 Signed 16 Bit Integer 2 s Complement 3 Decimal Places Example 12 345 stor...

Page 10: ...ation 15 Float Value Integer Value 2047 2048 Scale 15 Example 11 79 A stored as 2369 when Amp Scale 5 1 T18 Unsigned 16 Bit Integer 12 Bit Offset Binary 1 Decimal Place Float Value Integer Value 2047...

Page 11: ...te a CT and VT ratio for Phase A from the data stored in the M6xx meters use the following equation RA T IO RA T IO Phase A C T V alue A O 21 Phase A C T Phase A C T Ratio D ivisor A O 22 Phase A V T...

Page 12: ...equations BASIC EQUATION FOR NORMALIZED ANALOGUE INPUTS 32768 SECONDARY Value Normalized Scale Factor Engineering Units Default Full Scale Scale Factor Divisor The Value referred to in the equations w...

Page 13: ...Value x 150 x VOLTs PT 32768 Min Max Min Max RATIO t Demand RATIO RATIO TOTAL Inst Demand PER PHASE Inst Value SCALED x 150 x x 3 VOLTs PT 32768 Value WATTs VARs VAs x x x 4500 CT PT 32768 Value WATTs...

Page 14: ...ull scale and therefore independent of CT and VT settings The Primary Units mode creates protocol values that include CT and VT settings which requires the user to choose a scaling factor in multiples...

Page 15: ...n types are unaffected as they represent their values such as Frequency Power factor in primary units even in Optimal Resolution mode Also since the 12 bit calculation types are not included in the su...

Page 16: ...emulate the response of a Bitronics MultiComm or PowerPlex unit 1 8 1 Configuring the Class 0 Response The Class 0 request is a very short request to give all essential data Since the M6xx is capable...

Page 17: ...58 AO 0 3 10 14 Bit 14 Include all data in Class0 poll Include all data in Class0 poll 1 8 2 Configuring Class 1 Class 2 and Class 3 Events ANALOGUE INPUT points can be monitored for ANALOGUE CHANGE...

Page 18: ...ibration of inputs 12 Indicates firmware download in progress and measurements are offline 15 Protocol configuration error 1 10 Heartbeat State Counter M6xx meters provide a Heartbeat State Counter Re...

Page 19: ...17 The DNP Points List Configuration summary page is displayed by object Select the DNP object you would like to edit from the DNP Type dropdown box The properties of the selected object appear in se...

Page 20: ...DNP3 Manual M6xxD EN M B M6xx Page 18 Click on the Edit List button to modify the list...

Page 21: ...ighlighted item If no items are highlighted in the Selected list items are added to the end of the list NOTES Highlights all measurement data items in Available list Places highlighted measurement dat...

Page 22: ...The physical layer is responsible for transmission of raw 8 bit bytes octets across the network medium The data link layer is responsible for reliably maintaining connectivity between two devices The...

Page 23: ...ers share an IP address each Master must connect to a unique IED Listen port For each protocol session the Master IP address and the IED Listen Port number may be specified The current Settings for ea...

Page 24: ...iggered by any change of an enabled binary input point Each of the three DNP sessions has storage for 200 Analogue Input Events 100 Frozen Counter Events and 20 Binary Input events Events can be repor...

Page 25: ...his communication session allocates a dedicated set of FROZEN COUNTERs specifically for the new DNP3 master When the DNP3 master issues a FREEZE or FREEZE AND CLEAR command only the FROZEN COUNTERs al...

Page 26: ...Amp Scale Data 0 32767 1 32768 10 Amp Scale A Always AI 02 Amps B T2 Amp Scale Data 0 32767 1 32768 10 Amp Scale A Always AI 03 Amps C T2 Amp Scale Data 0 32767 1 32768 10 Amp Scale A Always AI 04 Vo...

Page 27: ...10 100 1000 3 AI 19 Amps Residual T3 Amp Scale Data 0 32767 1 32768 15 Amp Scale A Always CT 0 Watt Hrs Normal High Word T1 Data 0 65536 65536 KiloWattHours 0 CT 1 Watt Hrs Reverse High Word T1 Data 0...

Page 28: ...cale Data 0 32767 1 32768 10 Amp Scale A 2 AI 34 Demand Max Amps C T2 Amp Scale Data 0 32767 1 32768 10 Amp Scale A 2 AI 35 Demand Amps Residual T3 Amp Scale Data 0 32767 1 32768 15 Amp Scale A 2 AI 3...

Page 29: ...55 Meter Type T1 600 Legacy points list Data 600 602 0 3 AI 56 Protocol Version T21 Data 0 65536 0 001 3 AI 57 Factory Version Software T21 Data 0 65536 0 001 3 AI 58 Reserved T21 Data 0 65536 0 001 3...

Page 30: ...00 Volt Scale V Never AI 75 Demand Max Volts AB T23 Volt Scale Data 0 32767 1 32768 300 Volt Scale V Never AI 76 Demand Max Volts BC T23 Volt Scale Data 0 32767 1 32768 300 Volt Scale V Never AI 77 De...

Page 31: ...1500 Amp Scale Volt Scale VAs Never AI 92 Max Average VAs C T6 Amp Scale Volt Scale Data 0 32767 1 32768 1500 Amp Scale Volt Scale VAs Never AI 93 Average Watts A T5 Amp Scale Volt Scale Data 32768 3...

Page 32: ...olt Scale Data 32768 32767 1 32768 1500 Amp Scale Volt Scale VARs Never AI 106 Min Average VARs B T6 Amp Scale Volt Scale Data 32768 32767 1 32768 1500 Amp Scale Volt Scale VARs Never AI 107 Min Avera...

Page 33: ...ether or not to validate source address in received frames DNP3 frames contain both a source address field and a destination address field If the box is not checked DNP3 does not validate the source a...

Page 34: ...mary Units mode deadbands are in per count integers 1 00 Power Reactive In Optimal Resolution mode deadbands are in percents with a minimum value of 01 In Primary Units mode deadbands are in per count...

Page 35: ...ed before an unsolicited response is generated Default is 5 maximum is 255 Class2 Timeout ms When unsolicited response is enabled the maximum amount of time in ms after an event before an unsolicited...

Page 36: ...CRCs Default is 292 max Receive Frame Timeout ms Maximum amount of time ms to wait for a complete frame after receiving valid frame sync characters Default is 15 000 milliseconds First Character Timeo...

Page 37: ...stination IP address for UDP broadcast requests This is only used by a DNP Master when TCP and UDP are supported If UDP ONLY is configured IP Address will be used as destination for all requests Defau...

Page 38: ...equested Frozen Counter Events may be requested The read function code for Object 50 Time and Date variation 1 is supported Maximum Data Link Frame Size octets Transmitted 292 Received 292 Maximum App...

Page 39: ...any operation Reports Binary Input Change Events when no specific variation requested Never Only time tagged Only non time tagged Configurable Reports time tagged Binary Input Change Events when no sp...

Page 40: ...DNP3 Manual M6xxD EN M B M6xx Page 38 BLANK PAGE...

Page 41: ......

Page 42: ...for information only Neither ALSTOM its officers or employees accept responsibility for or should be taken as making any representation or warranty whether express or implied as to the accuracy or com...

Reviews: