CIRCULATION AIR BLOWER DATA (CFM#)

*9UHX060F12 (1)(2) * Denotes Brand

Exterrnal

 Static Pressure

(in wc/Pa)

Speed

Tap

HI

MED H

MED L

LO

in wc

Pa

CFM

L/s

CFM

L/s

CFM

L/s

CFM

L/s

0.1

25

1478

697

1204

568

901

425

703

332

0.2

50

1418

669

1154

545

864

408

649

306

0.3

75

1350

637

1103

521

818

386

588

277

0.4

100

1280

604

1053

497

765

361

538

254

0.5

125

1201

567

993

469

720

340

488

230

0.6

149

1116

527

924

436

672

317

459

217

0.7

174

1023

483

846

399

620

293

408

193

0.8

199

931

439

764

361

558

263

365

172

0.9

224

825

389

683

322

489

231

317

150

1

249

730

345

590

278

428

202

233

110

*9UHX080J12 (1)(2) * Denotes Brand

Exterrnal

 Static Pressure

(in wc/Pa)

Speed

Tap

HI

MED H

MED L

LO

in wc

Pa

CFM

L/s

CFM

L/s

CFM

L/s

CFM

L/s

0.1

25

1456

687

1326

626

1123

530

976

461

0.2

50

1440

680

1312

619

1112

525

941

444

0.3

75

1420

670

1280

604

1085

512

909

429

0.4

100

1379

651

1241

586

1043

492

870

411

0.5

125

1325

625

1209

571

1002

473

818

386

0.6

149

1261

595

1155

545

952

449

784

370

0.7

174

1208

570

1082

511

893

421

714

337

0.8

199

1115

526

1001

472

792

374

640

302

0.9

224

1007

475

868

410

702

331

567

268

1

249

830

392

746

352

608

287

491

232

NOTE:

(1) Data Based on Bottom Only or One Side return.
(2) Gray area is above maximum temperature rise range.

# CFM 

 Cubic Feet Per Minute airflow. Filter required for each

return

air inlet.

Airflow perfomance includes 1” (25.4mm) washable [600 FPM (3.0
m/s) max] filter media.

*9UHX080J16 (1)(2) * Denote Brand

Exterrnal

 Static Pressure

(in wc/Pa)

Speed

Tap

HI

MED H

MED L

LO

in wc

Pa

CFM

L/s

CFM

L/s

CFM

L/s

CFM

L/s

0.1

25

2032

959

1690

798

1246

588

922

435

0.2

50

1952

921

1650

779

1250

590

898

424

0.3

75

1874

884

1601

756

1226

579

872

412

0.4

100

1785

842

1533

723

1187

560

838

395

0.5

125

1688

797

1462

690

1151

543

806

380

0.6

149

1593

752

1381

652

1090

514

769

363

0.7

174

1482

699

1287

607

1014

479

711

336

0.8

199

1360

642

1182

558

918

433

643

303

0.9

224

1231

581

1053

497

790

373

570

269

1

249

1052

496

850

401

678

320

488

230

*9UHX100L20 (1)(2) * Denotes Brand

Exterrnal

 Static Pressure

(in wc/Pa)

Speed

Tap

HI

MED H

MED L

LO

in wc

Pa

CFM

L/s

CFM

L/s

CFM

L/s

CFM

L/s

0.1

25

2240

1057

2137

1008

1993

941

1820

859

0.2

50

2163

1021

2062

973

1934

913

1768

834

0.3

75

2083

983

1992

940

1872

883

1722

813

0.4

100

2002

945

1916

904

1801

850

1656

782

0.5

125

1912

902

1833

865

1723

813

1590

750

0.6

149

1821

859

1745

824

1636

772

1513

714

0.7

174

1727

815

1654

781

1547

730

1426

673

0.8

199

1618

764

1551

732

1437

678

1325

625

0.9

224

1502

709

1430

675

1315

621

1199

566

1

249

1356

640

1275

602

1159

547

1047

494

MAX CFM’s for Factory Washable  Filters

Filter  Size  (in/mm)

CFM

L/s

14

 X 25

/ 356 x 635

1400

661

16

 X 25

/ 406 x 635

1600

755

20

 X 25

/ 508 x 635

2000

944

24

 X 25

/ 610 x 635

2500

1180

Max CFM based on 600 FPM (3.0 m/s)

NOTE: Disposable filters are typically rated at 300 FPM (1.5 m/s). These filters
only allow half the airflow when compared to 600 FPM (3.0 m/s) filters.

Summary of Contents for 9UHX060F12A

Page 1: ...6 Models Dual Certified 9UHX060F12A2 9UHX080J12A2 9UHX080J16A2 9UHX100L20A2 Denotes Brand Save This Manual For Future Reference 90 Furnace Upflow Horizontal International Comfort Products LLC Lewisbur...

Page 2: ...s in wc Pa 3 2 797 2 9 722 1 9 473 2 0 498 3 2 797 2 9 722 1 9 473 2 0 498 3 2 797 2 9 722 2 3 573 2 4 598 3 3 822 2 9 722 Limits Controls Rollout Switch oF oC Limit Control Setting oF oC 350 177 250...

Page 3: ...r inlet Airflow perfomance includes 1 25 4mm washable 600 FPM 3 0 m s max filter media 9UHX080J16 1 2 Denote Brand Exterrnal Static Pressure in wc Pa Speed Tap HI MED H MED L LO in wc Pa CFM L s CFM L...

Page 4: ...47 440 01 1050 06 Specifications are subject to change without notice Wiring Diagram 9UHX...

Page 5: ...ct to change without notice 48 Parts 9UHX O F F N O O F F N O O F F N O YY WW 15 N LL BB 12 11 18 V W R S T U J L JJ Q P Y X F UU VV TT SS H RR QQ KK 5 4 3 9 10 M K 2 1 B A 7 K 25 24 75a 2 FF CC 17 GG...

Page 6: ...014823 1 1 5 Wheel Blower 1011420 1 1 1 1 6 Transformer 1172810 1 1 1 1 7 Capacitor 10Mfd 370V 1171729 1 1 7 5Mfd 370V 1171728 1 40Mfd 370V 1171982 1 8 Control Fan Timer 1172550 1 1 1 1 9 Switch Inter...

Page 7: ...ker only 1173009 1 Comfortmaker only 1173010 1 1 Comfortmaker only 1173072 1 Heil only 1173012 1 Heil only 1173013 1 1 Heil only 1173075 1 Tempstar only 1172940 1 Tempstar only 1172946 1 1 Tempstar on...

Page 8: ...CC Bottom Burner Box 1172848 1 1172849 1 1 1172850 1 DD Baffle Burner Box 1012338 1 1012339 1 1 1012340 1 EE Top Burner Box 1013702 1 1013703 1 1 1013704 1 FF Bracket Manifold Support 1012377 2 2 2 2...

Page 9: ...535 1 1 1 1 Coupling Air Intake 1012284 1 1 1 1 Coupling Discharge 1002522 1 1 1 1 Bushing Strain Relief 1945287 1 1 1 1 Gasket Air Intake 1012583 1 1 1 1 Clamp Hose 5 8 1012975 4 4 4 4 Clamp Hose 3 4...

Reviews: