4
If the AT-304 is used with wireless Visonic
detectors
(PIR, smoke detector, gas detector, water detector or vibration
sensor), the relay output with pulse for approximately 2 seconds when the detector sends a wireless signal to the
AT -304 receiver.
If the AT-304 is used with a Visonic wireless
magnetic contact
, the relay output will toggle as soon as the wireless
magnetic contact is opened. The relay output remains toggled if the wireless magnetic contact is open, making the
AT-304 ideal for door / window position signalling. As soon as the wireless magnetic contact is closed, the relay
output will toggle back again.
Some Visonic wireless
magnetic contacts
are also equipped with an extra hardwired input. This hardwired input
can
only be used with PowerCode 868MHz
magnetic contacts on the AT-304 PowerCode! This input must be
enrolled as a separate device (contact) on the AT-304! The hardwired input of a PowerG (PG2) magnetic contact
CANNOT
be used! Regardless of the position of dipswitch 2 on dipswitch 1-8, the relay output only works as a
toggle contact and not as a pulse contact.
If the AT-304 is used with a Visonic
panic button/keyfob
(MCT-132, MCT-134, MCT-234, PB102, KF-234 and KF-
235), the relay output of the AT-304 can be toggled
on and off with the “lock ope
n
”
and "lock closed" buttons on
the device. The other buttons have no function.
If the AT-304 is used with a Visonic
1-button panic button
(MCT-101, MCT-201WP, MCT-241, MCT-211, MCT-
211RL, MCT-220, PB-101), the relay output will be activated when the user presses the button. Depending on the
setting of dipswitch 2 the relay output will pulse for approximately 2 seconds or toggle.
If the AT-304 is used with a Visonic PowerCode
1-button transmitter including man-down
(MCT-241 MD), the
relay output will be activated when the user presses the button. Depending on the setting of dipswitch 2 on
dipswitch 1-8 the relay output is pulsed for approximately 2 seconds or toggled. The MCT-241 MD also features a
fall detection (man down) function. To be able to use the fall detection function this signalling must be enrolled as
a separate device on the AT-304. Fall detection of the MCT-241 MD activates the relay output on the AT-304.
Regardless of the position of dipswitch 2 the relay output will always toggle. The output therefore remains
activated if the person is lying on the floor and the transmitter is in a horizontal position. Only after the transmitter
returns to the vertical position the relay output switches back again.
It is also possible to use a Visonic multi-button transmitters (MCT-102, MCT-104, PB-102) in combination with the
AT-304 receiver. Depending on the setting of dipswitch 2 on dipswitch 1-8, the control of the relay output is a pulse
for approximately 2 seconds or switched over (toggle).