LiftCallLineC 

– User guide

 

32 

2.2.4  End of calling 

– call confirmation 

The BraveLLW enables to program at every number if will be confirm or 

not.  Every call needs authorisation if it was succesfull or not. Therefore analog 
line doesnt support any kind of authorisation (signalling) we can define success 
of  call  by  2  ways.  The  BraveLLW  needs  this  info  to  not  dial  further  telephone 
numbers.   
First  way  (

no  confirmation

)  is  detection  that  call  was  succesfull  on  the  base 

control ringing tone (CRT). It is tone which we are hearing in handset when 
make call to other subscriber. Thed BraveLLW detects this tone and when 
is  missing  for  certain  time  then  evaluate  the  call  was  succesfull  (Green 
indicator  light  up    and  yellow  light  down).  The  time  which  define 
undetection of CRT ( called part picks up) is adjustable because each type 
of  PBX  can  be  different.  Usually  should  be  5  seconds  as  the  best 
(parameter 56). At this call authorisation stays possibility confirm the call 
by dial confirmation characters (kxxxx, where xxxx is 1-4 numerals). After 
dialling of confirmation characters BraveLLW reply and reactions are four 
possibilities  for  the  confirmation  of  four  different  confirmation  codes  - 
specified below. 

Second way (

with confirmation

) is detection that call was succesfull only by dial 

confirmation characters (kxxxx, where xxxx is 1-4 numerals). This way is 
most reliable but requires trained people in service department (they must 
be able insert confirmation characters when call is pick up), or at service 
department  must  be  used  evaluation  software.  After  dialling  of 
confirmation  characters  the  BraveLLW  reply  and  reactions  are  four 
possibilities  for  the  confirmation  of  four  different  confirmation  codes  - 
specified below. 

Types confirmation codes (all is same principe   - call  kxxxx where xxxx is 1-4 
numerals - numbers 0-9): 

 

par.  47

  -  return  DTMF  serial  number  of  the  BraveLLW  lift 

communicator.  By  this  way  is  detected  where  from  is  coming  a  call 
even when more BraveLLW is installed behind PBX. In this case is not 
possible detect it by CLIP because all BraveLLW communicators have 
the same CLIP due the same telephone line use for outgoing calls. The 
same  is  the  case  with  parallel  connection  communicators  in  one 
telephone line. 

 

par.  48

  -  return  DTMF  state  of  counter  of  move  lift  cabin.  This 

parameters is on Option module!  

 

par. 49

 - react on this confirmation is hangup and dial Emergency call 

like as after press bytton BTN1 (without function of filtering) 

 

par.  40

  -  return  DTMF  last  two  dial  numbers  (separate  by  special 

DTMF tone "D"), first is last and second is pre last dialing telephone 
numbers

 

 

 

par. 07

 - react on this confirmation is hangup and dial Service call like 

as after time expires for Service call (must be set Service call (par.31) 
and call is after timeout for Service call (par. 32) 

Summary of Contents for BraveLLW

Page 1: ...BraveLLW Lift communicator USER GUIDE...

Page 2: ......

Page 3: ...tion module is powered only from 12 24V and it s galvanicaly isolated from telephone line including inputs and otputs on the Option board The BraveLLW has adjustable parametres saved in internal memor...

Page 4: ...MODULE V1 24 1 8 CONNECTION OPTION MODULE V2 25 1 9 CONNECTION FLOORTALKER 25 1 10 CONNECTION TALKER MODULE 25 1 11 INSTALLATION 27 1 12 ACOUSTIC PATH SETTING 28 2 BRAVELLW SERVICE 29 2 1 SIGNALLING O...

Page 5: ...4 PARAMETERS DESCRIPTION 43 4 1 PHONE NUMBERS MEMORY 43 4 2 LIFT OPERATION 45 4 3 BASIC PARAMETRES 47 4 4 TIME PARAMETRES 50 4 5 SYSTEM PARAMETERS 54 4 6 HANDSFREE PARAMETRES SETTING 57 4 7 OPTION MOD...

Page 6: ...lel from one telephone line The possibility up to 3 communicators paralel from SwitchBoard for communication with machine room Automatic control of system functionality Service call automatic calling...

Page 7: ...sal inputs o Include 3 4 universal outputs open collector o Special input INP3 for connection to door contact for count of move the cabin o Special relay otput for connection parallel to button of lif...

Page 8: ...om call it is calling between lift cabin and machine room in machine room must be SwitchBoard Incoming call it is calling coming from outside into BraveLLW unit The BraveLLW pick up you can programm p...

Page 9: ...odule The BraveLLW is compact solution of communicator it means that contains speaker microphone connector for PC connection configuration At picture 1 and 2 is picture of BraveLLW basic board Functio...

Page 10: ...nce on over or under cabine In this connectors RJ45 is possibility connect speaker microphone LEDs and push button BTN1 Caution on polarity of microphone because is powered Here you can see that when...

Page 11: ...are directly in programming mode In programming mode you can change all parametres includes new password as well 4 connector for connection Speaker Standard is connected internal speaker On picture i...

Page 12: ...lephone line For actiavate use voltage 5 24V independent of polarity 11 input BLK for signal block of dial from button BTN2 this input is gavanicaly connect with telephone line Use only contact withou...

Page 13: ...W 2 PC connection by special USB cable KAB The cable is galvanicaly isolated convertor USB and BraveLLW interface 3 Inp3 input for counter of cabine moving 4 Otput3 NC COM NO relay output for simulate...

Page 14: ...llector switch max 48V 0 5A 10 12V 24V external power supply DC attention on polarity 11 Input for acoustic signal from Floor Talker to telephone line galvanic isolate 1 3 4 Description of Option modu...

Page 15: ...at the main is always 1 Telephone line interface has following typical parametres The voltage in Hang up status disconnect loop 20 60V DC during connection not depends on polarity when BraveLLW pick u...

Page 16: ...switch NC buttons serial Control of type buttons use is possible programming by parameter 33 for BTN2 and parameter 39 for BTN1 1 or 0 Use only contact without voltage potential and galvanic isolate...

Page 17: ...t dial If you press longer then 2sec so BraveLLW dial Emergency call and if you press BTN1 longer then 16 sec 8 x 2sec so BraveLLW dial Technical call Resolution is 8 times set time in parameter 52 BT...

Page 18: ...uiped by call status indication It is by yellow and green status indicator Connection LEDs is external without rezistors and without power voltage connection The switcher outputs for those indicators...

Page 19: ...ible use for activate by external voltage 5 24V connector with symbol Isol isolate by optocoupler From Version of Firmware V4 5 is new feature of this input If we set parameter 34 2 so system of Block...

Page 20: ...e is available button BTN1 for emergency call without possibilities of filterinkg BLK Use only contact without voltage potential can be used NO or NC contacts programable For connection over under cab...

Page 21: ...one line and lift communicator only two wires For correct function just more connect 12V or 24V DC Power is independent of the polarity Consumption is 10mA in an inactive state at communication consum...

Page 22: ...tant time detection 51 maximum call duration Indication Green LEDs light green button switch address where do will be called Switches in the order 1 2 3 1 2 1 2 3 Function Select the address by green...

Page 23: ...hout changes to the SwitchBoard so this is all This setings we recommended save to the PC for next other possible future servicing Programming SwitchBoard need if you want to maintain good cooperation...

Page 24: ...e used NO or NC contacts This inputs react on change of status with programable filter time filter Otputs OUT1 OUT2 is open collector otputs with parameters Umax 48V and Imax 0 5A Attention of polarit...

Page 25: ...e speek green LED is light the message is play only one This message can be invoked at any time the conversation by DTMF dial Message H2 must be allowed in par 01 H3 is message befor hangup the commun...

Page 26: ...mming BLLW i Talker module in the same USB cable cable phone and the same program BraveLLWSet Attention USB cable for recording messages to Talker module contains the external power switch Power Talke...

Page 27: ...min 30 35 mm View is to the bottom side of panel in the cabin The lift cabin panel should be equiped by acoustic holes in microphone as same as speaker part It should be also provides by 2 screws M3 M...

Page 28: ...d a quiet environment at the communicator In this case we keep the value of parameter 72 7 and 73 and 71 parameters should be set as follows for example parameter 71 11 14 and 73 2 4 The principle of...

Page 29: ...k up OFF HOOK type 2 800 1067 1200 1333 Line hang up ON HOOK type2 1333 1200 1067 800 Command confirmation by phone 800 Alerting knocking into call Call ending alert 1333 Relay activation signal Modul...

Page 30: ...n filtering is not active Please note that filtering might be either by close contact or by open contact of switch connect to the connector BLK Second condition is that button BTN2 you must hold enoug...

Page 31: ...meter You also define if this parameter is activated since first connection of BraveLLW to telephone line This service calling is adjustable from 1 to 59 day period for example 03 means that BraveLLW...

Page 32: ...ion characters kxxxx where xxxx is 1 4 numerals This way is most reliable but requires trained people in service department they must be able insert confirmation characters when call is pick up or at...

Page 33: ...re is possibility call directly from BraveLLW to the machine room This call is make from BTN1 button three times press the button 2 2 6 Incoming call Incoming call is coming from outside to BraveLLW A...

Page 34: ...here is no distortion of detection If disagree received numbers With each communicator with the number of communicator so the time constant of 5 x 4 parameter the line will be hanging and not connecti...

Page 35: ...LiftCallLineC User guide 35...

Page 36: ...e nnnnnnnn is change to inactive of 8 inputs on Option module and iiiiiii is ste of 8 inputs on Option module call from not move cabine option module C call if acoustic path is bad 0 call if is perman...

Page 37: ...ng tone and the BraveLLW will come back to this state always after time expiration 5 seconds even you started to program anything When programming two types of parameters will occur Partly they are pa...

Page 38: ...the cable from BraveLLW connect it again the BraveLLW will answer and if BraveLLWSet program runs he will report his conversion to programming mode In BraveLLWSet program is this connection indicated...

Page 39: ...ou select path to the driver and clik OK YES Driver is not signed electronically it must agree with the installation In Windows 8 is need allow the installation of unsigned drivers Program BraveLLWSet...

Page 40: ...not be used in same time for CallCentrum For next step you must fill the telephone number of communicator and password in communicator for programming Number of communicator fill only if you call to p...

Page 41: ...tting is recommended for this procedure First original data of the specified communicator you should be stored on the PC Second make a change the parameter value Third save it back to the PC 4th remot...

Page 42: ...This communication is slow and therefore you can choose which part of the communicator data to write Other data do not replace and remain original Unable to remotely delete the number of resets time s...

Page 43: ...irm so programming sequence 110 0 0213658 waiting tone 121 54 23 78 091 4 and waiting tone Example Erase the telephone number on second position so programming sequence is 12 and waiting tone Service...

Page 44: ...le Erase the telephone number so programming sequence is 22 and waiting tone Counter is full number max starts from input INP3 Option m Parameter Value Description Default 23 p nn Number nn with confi...

Page 45: ...ult 33 i Polarity of buttons BTN2 0 1 0 i 0 buttons connected is type NO normaly open parallel connection 1 buttons connected is type NC normaly close serial connection Use only contact without voltag...

Page 46: ...is higher then preset value parameter 097 Parameter Value Description Default 38 ee Number of repeat service call 00 99 00 ee 00 unlimited service call is repeated until the call is confirmed 2 digit...

Page 47: ...1 digit then you have possibility insert a where a is just one number which hang up line star represents empty character and must be on first position Parametr Value Description Default 44 xxxx Servic...

Page 48: ...an use 1 4 digits long code but befor code you must dial common character k parameter 4 Parameter Value Description Default 49 oooo Confirm code BraveLLW answer redial emergency telephone numbers 0 99...

Page 49: ...F address of communicator 10 49 25 kk 10 49 this time is need for answer DTMF address in parallel mode 1 4digits Time is in 0 1 sec 10 is 1sec 25 is 2 5sec Explain of this constant is on page 33 Param...

Page 50: ...cy call activation 00 39 02 w 00 time 0 5sec for emergency call activation 01 39 minimal in sec time for which must be button BTN1 hold pressed to start emergency call procedure Note for Technical cal...

Page 51: ...e Time without ringing tone call detection 1 0 5 e 1 10 sec 0 10 sec is time for which is not detected ringing tone after dialling of number If is set at number dial without confirmation then is set...

Page 52: ...ty The time from last call is display in Lift set programm Parametr Value Description Default 500 x Middle frequency of tones detector 1 0 3 375 475Hz 501 y Number of busy tones 2 0 4 502 z Time of pe...

Page 53: ...d number x 100 Flash duration time ms range 1 6 tj 100 600ms p Time of pause duration is calculated inserted number x 100 400 pause duration time ms range 1 0 tj 500 1400ms time p is also time of paus...

Page 54: ...hook on hook 0 1 2 1 In default is signalling pick up and hang up of the line If you identify some problems at certain PBXs you can switch it off by parametr v The possible values are v 0 signalling...

Page 55: ...all if push button is permanent activate 4 call if lift cabin not move option module 5 call if counter of maximum set move of cabin is oveflow option module Another function of this parameter is mute...

Page 56: ...on and call is established as normal dialled number Caution first 10sec of call is not active tone detector it waits on reaction of PBX and number dialling by PBX Parametr Value Description Default 6...

Page 57: ...and you hear confirmation tone Note After confirmation tone is 5 sec open acoustic way with new acoustic parameters for short test CAUTION We dont recommend factory setting if neccessary Principe of s...

Page 58: ...environment we recommend higher value with combination of parametrs 71 75 77 Parametr Value Description Default 77 s Fast switching voice automatic 1 4 4 is slowest 2 At parametres 75 76 is descriped...

Page 59: ...ent I0 k dial Feature is off 0 20mA 50mA 1 45mA 75mA 2 Parametr Value Description Default 70 uu Transmission signalling level in dBm 04 16 04 uu transmission signalling level to the line range 4 to 16...

Page 60: ...sage to cabin waiting 2 enable message H2 H2 is message to the line place 3 enable message H1 H2 4 enable message H3 H3 is message end of call 5 enable message H1 H3 6 enable message H2 H3 7 enable me...

Page 61: ...n Default 05 a Enable test of acoustic path 0 1 0 a 0 disable 1 enable test of acoustic path This test is automatic activate service call par 31 with interval par 59 If use confirm code par 07 so test...

Page 62: ...ode is dialed to the call from telephone or Call centrum this confirmation authorize call LED yellow is light off and LED green is light on You can use 1 4 digits long code but before code you must di...

Page 63: ...le memory Parametr Value Description Default 094 ii Time ii sec activation output OUT4 00 99 00 ii time t3 for which is OUT3 closed 2 digits 00 99 where time 00 means 0 5sec This parameter is saved in...

Page 64: ...ounter of INP3 call 2 digits Parametr Value Description Default 099 hh Time limit for cabin without moving hours 01 99 04 hh If the cabin is not moving for more than timeout hh hours so will activate...

Page 65: ...ly 86 Default setting for parametres 6x only 6 only 87 Default setting for parametres 7x only 7 only 80 Default setting for parametres 0x only 0 only Parameter 81 82 perform erasing of all numbers sav...

Page 66: ...9 1 38 ee Number of repeat service call 00 99 00 39 i Polarity of buttons BTN1 0 1 0 41 v Dial type v tone pulse 0 1 0 42 z Character to prolong the call 43 bb Command to hang up communicator by phon...

Page 67: ...sy tones 2 0 4 502 z Time of permanent tone duration 1 5 3 3s 503 tt Time of tone duration DTMF tone dial 04 16 10 100ms 504 mm Time of space duration between DTMF tones 04 16 10 100ms 505 f Time of F...

Page 68: ...tion module 0 1 2 3 4 5 6 7 0 02 tt Time delay befor dial emergency call 00 99 40 03 s uu Switch on by code ss otput OUT s s 1 4 uu 00 99 0 9 151 252 353 454 04 s vv Switch off by code ss otput OUT s...

Page 69: ...lift cabine 1 9 4 8 Default perform 82 Erase all another phone numbers 2 only 83 Default setting for parametres 3x only 3 only 84 Default setting for parametres 4x only 4 only 85 Default setting for p...

Page 70: ...evel 16 to 4 dBm 20 60 mA Tone dial sensitivity 40 dB 20 60 mA Tone detection sensitivity 30 dB 20 60 mA Internal speaker impedance 8 ohms Speaker over under cabin impedance 45 ohms Microphone interna...

Page 71: ...LiftCallLineC User guide 71 Notes...

Page 72: ...JR 2011 16 version V4 8 VIII 2016 Produced by Distributed by Date of sales...

Reviews: