Alpha InTec S - Installation
10. Secure the flue assem ly to the bend with the clamp ensuring it is positioned centrally over the joint, ensuring the 'TOP'
marked on the outer duct is positioned at the top.
Note:
Check the flue te minal protrudes 120 mm out of the wall and that the inner duct of the terminal is positioned
correctly, i.e. the inner duct within the terminal is at the top. See Fig. 20.
11. Make good the outside wall by fitting the outside sealing collar ( lack) onto the location provided immediately behind the
flue te minal grille. Make good the inside wall using the inside sealing collar (white) if required.
4.9. FIT PLUME MANAGEMENT COMPONENTS - (OPTIONAL)
The following procedures detail the options for management of the exhaust flue gas/plume emitted from the te minal.
a. The terminal supplied with the Easy-Flue can be altered to divert exhaust flue gas/plume at an angl .
This can be achieved by simply turning the end section of the terminal to the desired angle.
b.
The CD Easy-Flue can be converted to allow the inner flue duct to be xtended so as to position the terminal in an area
where the exhaust flue gas/plume will not cause a uisance. This can be done before or after installation of the flu ,
providing there is access to the terminal from outside.
i. Remove the screws (1 in Fig. 21) securing the terminal and remove the terminal by pulling it from the flue assem ly.
Remove the screw (2 in Fig. 21) securing the terminal end section and remove the end section from the terminal.
ii. Locate a 93° Plume Management bend into the flue assem ly and rotate it to the direction required.
iii. Connect to the 93° bend the required Plume Management components as detailed and refer to Fig. 21.
Notes:
1. The wall support brackets must be used to secure the Plume Management pipework to the wall and
prevent disconnection of the 93° bend from the flue assem ly or any other component.
2. Each joint must be secured with one of the screws provided to prevent accidental disconnection.
3. Ensure there is always a slight slope towards the flue assem ly fitted in the all and there is no part
of the plume management pipework where condensate/rain will collect and cause a blockage or any
restriction.
iv. Terminate the Plume Management pipework by fitting the te minal end section (push-fit) pr viously removed. Refer
to Fig. 22.
v. The Plume Management components available for extending the inner flue duct are as ollows:-
Plume Management 93° bend 60 mm dia. (each 93° bend equivalent to 1.3 m flue length
Plume Management 45° bend 60 mm dia. (each 45° bend equivalent to 0.9 m flue length
Plume Management 1000 mm extension 60 mm dia. (equivalent to 1 m flue length
60 mm dia. wall bracket
Fig. 21