- 32 -
EXTRACTION
PRIOR TO EXTRACTION OF A BU, OPEN THE SWBATT BATTERY DISCONNECTION SWITCH OF
THE BATTERY CABINET!
NOTE: when a BU is replaced, it is required to replace also the other BU of the same A or B string.
To extract the BU from the cabinet, reverse the procedure described above. Briefly:
1.
Ensure that the SWBATT is open.
2. If present, remove the locking bracket and store it together with the fastening screws.
3. Carefully extract the BU from its housing. This operation requires two persons.
4.
Caution
: when the BU is not inserted, uncovered parts with dangerous voltage are present on the corresponding
backplane. Therefore, in the case where a new BU is not immediately inserted, install the supplied protection cover using
the dedicated screws.
B
ATTERY MAINTENANCE
CAUTION: DANGEROUS VOLTAGE INSIDE!
Never open the BU for any reason, if any anomaly is noted, contact the assistance service.
Batteries, in order to maintain a high efficiency and durability must be regularly charged using the HIMOD HP UPS System itself.
Batteries are subject to the self-discharge phenomenon. In the case where BU or Battery Box are stored and not immediately
installed, an appropriate recharge must be planned.
To recharge the batteries, just connect the Battery Cabinet/Battery Box to a HIMOD HP System in “NORMAL OPERATION” for
at least 24 hours.
For long storage periods, contact the assistance service.