Operation
Alpha Technologies
3.8
Normal / Generator Parameter Toggling
This procedure toggles the input parameters between normal and generator to let the unit oper-
ate with a generator or a noisy line (Section 3.9.8, “Generator”).
Procedure:
Parameter Changing Finished
Start
Simultaneously hold
down the
Mute
and
% Load
buttons for
at least 2 seconds.
The 100% (Test)
LED flashes during
this procedure.
2
Sec
2
Sec
The unit is operating on
generator
parameters.
The unit is operating on
normal
parameters.
One of these two
combinations of
25%,
50%
and
100%
LEDs
appears.
To toggle between
parameters, press the
% Batt
button
within
30 seconds
of press-
ing the Mute and %
Load buttons. The
new parameter takes
effect after the unit
returns to Line mode.
If the parameters are
unchanged, the unit
automatically returns
to Line mode after 30
seconds.