Caution:
Torque the battery terminals according to the
manufacturer’s specifications as given on the name plate or data
sheet.
Wire the batteries as shown in Figure
3.
3.11. If used, install the in-
line fuse as shown.
Verify battery connector polarity and DC voltage with a DC volt-
4.
meter. If correct, attach it to the FXM’s external battery connec-
tor. Otherwise, perform troubleshooting before connecting it to
the FXM.
Route the sensor end of the battery temperature cable to the
5.
batteries. Tape it to the side of battery as shown in Figure 3.11.
If multiple battery strings are used, repeat steps 1 to 4 as re-
6.
quired.