System Overview
The basic system configuration is called out by Alpha part number 053-996-20-000; which includes:
•
300A DCP03 distribution center
•
Cordex Integrated System Controller (CXCI/CXCI+)
•
One (1) Cordex 24-48/2kW 4-module converter shelf
•
Kydex rear covers
•
19” rack mount rails (center and flush mount)
•
19” to 23” rack mount adaptors
•
System integration cabling.
2.2
Distribution Center
2.2.1
Distribution Configurations
The DCP03 contains 18 total AM-type plug-in breaker positions with two-hole connection points for both load (hot)
output and the ground return bus. The breaker distribution, for the CXPS 24-48-i, is configured for 18 load breaker
positions.
Figure 2–DCP03 configured for 18 load breakers
2.2.2
Internal Alarm Card
The DCP03 includes a standard alarm card providing a common interface point to internal system I/O connections
and LED indication of breaker trip.
The alarm card provides terminal block access to internal signals such as binary alarms for breaker trip and
analog input for voltage measurement. The terminal blocks provide a single point of access to these signals for
connecting to an external system controller. Refer to the customer connections (“–08”) drawing at the rear of this
manual for details on terminal block assignments.
Figure 3–Internal alarm card
I/O customer connection points