012-554-B2 Rev D
Page 12 of 16
6.4
DC Output
6.4.1
Shelf Connection
The 10-module shelf has a 3-position Molex style connector for the –48V and +Gnd output terminations. Refer to
drawing 030-831-08, at the rear of this manual, for pin out assignments and mating connector requirements.
6.4.2
Wire Harness Options
The 10-module shelf has two (2) options for DC output wiring:
Shelf List Option 84:
provides a wire harness two (2) feet long with a 3-position Molex connector on the
customer connection end. Refer to drawing 877-593-04, at the rear of this manual, for pin out assignments.
Shelf List Option 85:
provides a wire harness six (6) feet long with a 2-position Anderson style connector on the
customer connection end. Refer to drawing 877-621-04, at the rear of this manual, for pin out assignments.
6.5
Alarm (Relay) Outputs
The 10-module shelf system can extend both major and minor alarm outputs via Form C relays; which are
socketed and field replaceable (See 1.3 Part Numbers and List Options for ordering information).
Each relay output can be wired for NO or NC operation during an alarm or control condition. See Figure 7.
Figure 7–Showing relay connections
6.5.1
Shelf Connection
The 10-module shelf has a 6-pin Molex style connector for the major and minor alarm relay terminations. Refer to
drawing 030-831-08, at the rear of this manual, for pin out assignments and mating connector requirements.
6.5.2
Wire Harness Options
The 10-module shelf has two (2) options for factory alarm wiring:
Shelf List Option 87:
provides a wire harness two (2) feet long with a 16-position Molex connector on the
customer connection end. Refer to drawing 877-594-04, at the rear of this manual, for pin out assignments.
Shelf List Option 88:
provides a wire harness six (6) feet long with unterminated wires (flying leads) on the
customer connection end. Refer to drawing 877-622-04, at the rear of this manual, for pin out assignments.