Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 5 - Installation
5.3. Module Insertion and Removal
The rectifier is plug and play. When a rectifier module is added to the system, the controller will detect and
update the inventory automatically. Replacing an installed rectifier requires a manual
Inventory Update
at the controller to clear the removed rectifier from its current list of rectifiers.
Insert rectifiers by placing the module on the shelf bottom and sliding the module into the rear connector
(inside of the shelf). Apply pressure on the front of the module to engage the rear connector in the shelf
receptacle. A thumbscrew is provided to secure the rectifier into the shelf.
Note:
Do not force a module into position if it does not seat properly. All modules are keyed to ensure
that the correct module (polarity/voltage) type is used.
5.4. Removing a CXRC Rectifier
1. To remove a module, loosen the screw on the bottom of the faceplate.
Thumb Screw
2. Grasp the handle and pull out, sliding the module away from the rear connector and out of the
shelf.
3. Place the new rectifier module on the shelf bottom and slide the module into the rear connector
(inside the shelf).
4. Apply pressure to the module front panel to engage the rear connector in the shelf receptacle.
5. Tighten the thumb screw to secure the rectifier to the shelf.
6. Refer to the respective controller software manual to perform an inventory update or module
assignment.
5.5. Removing the CXCi HP and CXCi+ Controller
To remove the controller:
1. Remove at minimum the left most rectifier adjacent to the controller.
2. Remove the controller mounting screws as highlighted in figure below.
Page 22
9400021-J0 Rev B