14
Fig. 8
External Alarms Connector Pin-out
(with Factory installed EPO Switch Option)
2.5
Communication / Interface Options
, continued
2. FEATURES
Pin 1
N.C.
Pin out: (RJ-45 connector, Female)
1.
LINE FAIL, COM contact
2.
LINE FAIL, N. C. contact
3.
LINE FAIL, N. O. contact
4.
LOW BATTERY, N. O. contacts
5.
LOW BATTERY, COM contacts
6.
LOW BATTERY, N. C. contacts
7.
8.
Line Present
N.C.
Battery OK
N.O.
N.C. = Normally Closed
N.O. = Normally Open
EPO
Emergency
Power OFF
Option
Emergency UPS Shutdown
Switch (Wall Mounted).
NOTE: Cable length must not
exceed 100 feet. Use twisted
or shielded wire.
External Alarms Connector,
continued
Pin out: (RJ-45 connector, centered key)
59
5. RS-232 TERMINAL COMMUNICATION
5.13 Event Descriptions (Alarms)
There are 6 alarm groups which upon activation will be displayed at the
end of the opening menu. These are:
INPUT:
BATTERY:
OUTPUT:
ENVIRONMENTAL:
SERVICE1:
SERVICE2:
The following lists the mnemonics and description for each alarm group:
INPUT:
FREQ_LO
- input line frequency low
FREQ_HI
- input line frequency high
GLITCH
- input line glitch has been detected
SPIKE
- input line spike has been detected
SAG
- input line sag has been detected
SURGE
- input line surge has been detected
BROWNOUT
- input line brownout has been detected
SLOW_SURGE
- input line slow surge has been detected
BLACKOUT
- input line blackout has been detected
BATTERY:
LO_BAT_SHTDWN - battery voltage shutdown level detected
LO_BAT_WARN
- battery voltage low warning level detected
BAT_VOLT_HI
- battery over voltage level detected *
FAIL_SELF_TEST
- failed self test *
BATT_FLT
- battery fault has been detected *
OUTPUT:
VOLT_LO
- output voltage low has been detected
VOLT_HI
- output voltage high has been detected
PWR_OVLD
- output power overload has been detected
VA_OVLD
- output VA overload has been detected
OVER_V_FLT
- output over voltage fault has been detected *
SHORT_CCT
- output short circuit has been detected *
ENVIRONMENTAL:
AMB_TEMP_HI
- high internal ambient temperature detected *
SERVICE 1:
SERV CODE 1
- phase lock loop failure has been detected *
SERVICE 2:
SERV CODE 2
- micro software reset has been activated
SERV CODE 3
- micro hardware reset has been activated
SERV CODE 4
- power board EEPROM fault has been detected *
SERV CODE 5
- power board hardware fault has been detected *
SERV CODE 6
- neg DC supply rail has been detected *
EMGNCY POFF
- emergency power off has been activated
OUTV SHTDWN
- remote shutdown feature is currently active
*(service light alarm)