GENERAL SYSTEM SETTINGS
Only
“
Expert
”
level users can access this page. It enables additional system configuration.
With the
“Expert”
access level enabled, tap the Main Setup icon.
Main setup page in the
“
Expert
”
mode (with additional “General” icon)
General system settings pages
General configuration
Enables various options for the UPS:
General configuration page 1: operating mode configuration
Operating mode
The user can choose the operational mode (refer to the Chapter “Operating modes” for further details regarding
these modes).
Auto restart
If during battery operation the system switches off due to the end of autonomy, a remote shutdown command or
due to a self-shutdown, when the power is restored the system automatically switches on if the function is
enabled.
It remains in standby if the function is disabled [Default
→
Function ENABLED].
The user can specify how long the UPS will wait (after the mains supply restore) before turn on [Default
→
5 sec].
If more than one unit is connected to the same supply, selecting a different time for each UPS will avoid any
nuisance breaker trips due to excessive current absorption.