WARNING - In order to protect personnel responsible for operation , service 

and maintenance of this Power Supply and to protect equipment within the 
network, all installation sites MUST be provided with  an earth ground bonding 
connection to the Power Supply bonding terminal. A reliable ground bonding 
connection also helps to protect the  Power Supply from damage of high-energy 
transients, e.g. lightning strike.   

The impedance between the  Power Supply enclosure and earth must be 25 Ohms or 
less. Soil conditions may affect the grounding system meeting the 25 Ohm 
(maximum) resistance specified above. Please contact a local grounding system 
expert if required. 

AC Output Connection: 

Output  connection  of  the  power  supply  is  made  through  the 

5/8”  x  24  coaxial  female 

connector located on the bottom panel of the Power Supply . 

A mating male cable connector  appropriate for the coaxial hardline to be used must have 
the center pin prepared as follows:  

Screw the male cable connector (external  

fitting)  into  the  5/8”  female  connection. The 

center pin is automatically seized by the female connector. Prepare and attach the coax

 

ial 

hardline 

feeding  the  HFC  plant  to  the  male  cable  connector  as  per  the  manufacturer’s 

instructions. 

AC Input Connections: 

An external  service disconnect (UL listed) MUST be installed between the Utility  power 
and APX2

PLUS

-615G Power Supply. The disconnect device is provided by the user. Please 

consult the local supplier, supplier of the service disconnect and your  local utility for 
specific installation instructions and guidelines. All electric al codes apply. 

Before attempting to connect the input supply wiring, ensure that the disconnect is in the 
disconnect (off) position. Using a n RMS voltmeter, confirm that no voltage exists at the 
disconnect output. 

The Utility power connection is made through the Power Supplies cable gland to the 
input terminal block. Ensure that no strands of bare wire are outside of the terminal 
block. Tighten each terminal screw with sufficient torque to ensure a good electrical and 
mechanical connection. 

2.3 Electrical Connection

Summary of Contents for APX2PLUS-615G

Page 1: ...Page 1 of 8 APX2PLUS 615G Non Standby Cable TV Power Supply USER MANUAL...

Page 2: ...s Do NOT connect the AC input while servicing the unit or installing the unit The unit must be well grounded before proceeding with installation or operation Failure to do so can cause electrical shoc...

Page 3: ...y as described in the installation instructions otherwise it may fall causing serious personal injury and or damage the unit Use only the bracket supplied with the product Do not use attachments not r...

Page 4: ...ed mounting bracket 1 2 Specifications Input Voltage 230VAC 20 to 15 50Hz Sine Wave Power Factor 0 90 at Full Load Output Voltage 63VAC 50Hz Quasi Square Wave Output Voltage Regulation 5 Output Curren...

Page 5: ...Ferro Resonant Transformer Locking Hasp Product Label Utility Input Cable Gland 5 8 x 24 Coaxial Cable AC Output Connector Cable Connector Pin Length Cut Guide Earth Ground Bonding Terminal Power On...

Page 6: ...cket using the M8 seizure hex bolt bottom to the bracket using the M8 seizure hex bolt SECTION 2 INSTALLATION 2 1 Pre Inspection Upon receipt of the APX2PLUS 615G Power Supply inspect the carton for a...

Page 7: ...s follows Screw the male cable connector external fitting into the 5 8 female connection The center pin is automatically seized by the female connector Prepare and attach the coaxial hardline feeding...

Page 8: ...es Headquarter Germany Hansastrasse 8 D 91126 Schwabach Tel 49 9122 79889 0 Fax 49 9122 79889 21 Mail info alpha outback energy com Eastern Europe ee alpha outback energy com Middle East me alpha outb...

Reviews: