6.5.6 Adjusting and Controlling the Alpha FXM
Use submenu #3, the Maintenance submenu (Figure 54 and Figure 55) to control the Alpha FXM and change
selected items to meet your operational needs.
From the Main menu (Figure 54), type
3
and press
Enter
.
Table I — Maintenance Submenu
30 Battery Test Options
Starts the battery test and sets how long the test will run. The default setting for
the test depth-of-discharge is 20%, but this can be adjusted from 0 to 100%. For
a description of the battery test, see BATT TEST in Figure 2.
31 Inverter On/Off
Switches the inverter on or off to allow you to prevent a damaging deep battery
discharge or to provide backup battery power to the load. For a description, see
INVERTER in Figure 2.
You can set a delay before the inverter switches off to allow time for switching
off critical loads. The Set Inverter ON/OFF delay is only available when the
Alpha FXM is in the Battery or Standby modes.
The delay can be adjusted in 1 second steps with a default setting of 0 seconds
to a maximum of 600 seconds (10 minutes). The delay is only available in the
Standby or Inverter modes. Once the Alpha FXM returns to the Line mode, the
delay resets itself to 0 seconds.
32 Change Password
Changes the Alpha FXM password. The factory set password is 1111, which
can only be changed when the Alpha FXM is in Line mode. The password is
limited to 4 alpha- numeric characters in length.
34 Line Qualify Time
Lets you set the delay when the Alpha FXM goes from Inverter mode to Line
mode after the line becomes re-qualified. The purpose of this delay is to make
sure the line is stable before the Alpha FXM switches back to it. The default
setting is 3 seconds, but user adjustable in increments of 1 sec until 1 minute,
and then in increments of 1 minute to 15 minutes max.
35 Low Battery Warning
Voltage
Lets you set the Alpha FXM low battery warning voltage by typing in the %
battery voltage level where you want the warning to be triggered. Adjust the
setting to match the batteries you are using and the actual operating conditions.
48V
:
Default 40% -47 Vdc
Adjusted in 1% increment – 0.05 Vdc Minimum 0% - 45.0
Maximum 100% - 50.0 Vdc
24V
:
Default 40% - 23.5 Vdc
Adjusted in 1% increment – 0.025 Vdc Minimum 0% - 22.5 Vdc
Maximum 100% - 25 Vdc
36 Load Shed Timer
On/Off
Lets you switch the timer contacts on or off while the timer is counting down.
This feature has no effect if the timers are not counting. See "Contacts C1 to
C2”.in Table C.
From the Main menu, type
4
and press
Enter
.
Table J — Maintenance Submenu
40 Quality mode high limit
Changes the upper limit of the Power Quality mode threshold
41 Quality mode low limit
Changes the lower limit of the Power Quality mode threshold