RELAY TEMP
55
120/60/N
LINE
6.2.3
Controlling the external fan by temperature triggered dry contact
The Temperature trigger has a user configurable range of +20°C to +55°C (68 to 131 °F). When the battery
temperature (monitored by the Battery Temperature Probe) reaches the threshold, the assigned relay closes and
turns on the external fan.
Procedure
From the Logo screen, navigate to
Control Menu
>
RELAY TEMP
. Press the
SELECT
button and the current
temperature display will start flashing. Use the
Scroll
button to change the temperature in 5°C increments. Press
SELECT
to accept the changes or
CANCEL
to abort.
Dry contact functions are not programmable through the LCD. Use the Web GUI or HyperTerminal instead.
6.2.4
Making Measurements
The System Status menu lets you make measurements of various Alpha FXM inputs, outputs, temperatures and
other values.
Procedure
1. From the Logo screen go to the System Status menu.
2. Press the SELECT button to enter the submenu (Table E).
3. Press the SCROLL button to move between items in the submenu. Stop at the item you want to measure.
The measurement is displayed on the LCD and automatically updated every 0.5 second.
Table C — System Status Menu
LCD display
Meaning
Description
VIN
Input Voltage
Line input voltage into the Alpha FXM
VOUT
Output Voltage
Alpha FXM output voltage (true RMS)
IOUT AC
Output Current
(AC)
Alpha FXM AC output current (true RMS)
BATT TEMP
Battery
Temperature
Battery temperature (°C)
FREQ IN
Input Frequency
Frequency of line power into the Alpha FXM (Hz)
OUTPUT PWR
Output Power
Alpha FXM output power in VA (true RMS)
BATT VOLT
Battery Voltage
Battery output voltage (Vdc)
CHGR CUR
Charger Current
Alpha FXM battery charging current (Amps)
DATE
Current date
Displays in the format set by the user
TIME
Current time
Displays in the format set by the user
INV COUNT
# of line failures
Shows how many times the inverter has been active since the last time
the inverter counter was cleared. See INV RECORD description in Table
B.