background image

13

We reserve the right to modify technical specifications without prior notice.
83050800aUK – Translation of the operating manual  

© Alpha-InnoTec GmbH

1  compressor power 

connection 3~pE

2  control connection
3 n/pE
4  phase sequence relay

 note.

 

The control panel of the heating and heat pump 
controller can be connected to a computer or 
network using a suitable network cable, enabling 
the heating and heat pump controller to be 
controlled remotely from there.

 

If this is required, install a shielded network cable 
(category 6, with RJ-45 connector) through the 
unit when installing the connections and run it 
through the front panel of the unit, parallel to 
the existing control cable of the heating and heat 
pump controller.

 After completing all electrical installation work, 

close the switchbox inside the unit…

  screw on the front panel of the unit, if no further 

installation work inside the unit is to be carried out 
immediately.

 

Familiarise yourself with the inside of the unit…

1  Electrical switchbox
2  Intermediate floor of the unit

  open the unit's electrical switchbox…

 

To do this, only loosen the two upper screws of 
the cover panel. Remove the remaining screws. The 
cover plate can then be removed…

  lay the load and external control and sensor cables 

through the cable duct to the terminals. Tighten the 
strain relief screws…

 Install electrical connections according to the 

terminal diagram and the circuit diagrams.

  “Terminal diagrams” and “circuit diagrams” for 

the respective model.

 attentIon!

 

Install electric connections only according to the 
terminal diagram and the circuit diagrams that 
apply to your model.

 Important

 

Ensure clockwise rotary field of the load power 
supply (compressor).

– 

operation with the incorrect rotary direction of 
the compressor can cause serious, irreparable 
damage to the compressor.

 Important

 

Ensure the power supply of the heat pump is 
fitted with a 3-pole miniature circuit-breaker 
with at least 3mm contact gap.

 

note the level of the tripping current.

 “Technical data / scope of delivery” overview, 

“Electrics” section.

Summary of Contents for WWP 1100x

Page 1: ...serve the right to modify technical specifications without prior notice 83050800aUK Translation of the operating manual Alpha InnoTec GmbH Professional Operating Manual Heat pumps Water Water UK WWP s...

Page 2: ...s that apply to the respective type of unit This operating manual is intended only for persons assigned to work on or with the unit Treat all its constituent parts confidentially They are protected by...

Page 3: ...rcuit 14 Water quality 14 Cleaning and flushing unit components 15 Insulating the hydraulic connections 16 Installing the control panel 16 Installation and removal of the screen 18 Buffer tank 19 Circ...

Page 4: ...ended use The construction and design of the unit conform to current state of the art standards all relevant DIN VDE regulations and all relevant safety regulations Every person who carries out work o...

Page 5: ...laws guidelines directives and standards concerning the recovery recycling and disposal of the operating materials and components of chillers Dismantling How heat pumps work Heat pumps operate on the...

Page 6: ...Ensure that the suction and return pipe always extends below the water level by sufficient depth to ensure that oxygen is not added to the water risk of iron oxide deposits Please discuss the problem...

Page 7: ...day reduces energy consumption and your heating bill Care of the unit You can clean the outer surfaces of the unit with a damp cloth and proprietary household cleaning products Do not use cleaning or...

Page 8: ...of delivery 1 Compact unit with hermetic compressor all safety relevant components for refrigeration circuit monitoring installed heating and heat pump controller sensors installed in the unit for re...

Page 9: ...8 kg m R 407C 0 31 kg m R 410A 0 44 kg m Technical data scope of supply overview General unit data section Minimum room volume Refrigerant capacity kg Limit kg m Note If several heat pumps of the same...

Page 10: ...e cover plates supplied Detailed drawing of concrete foundation 1 Screed 2 approx 100 mm 3 Structural borne sound insulation depending on weight of heat pump 4 Concrete foundation 5 Perimeter insulati...

Page 11: ...aulics must be equipped with a buffer tank the volume of which depends on your unit model The hydraulic connections are located at the rear of the unit Dimensioned drawings Important When installing t...

Page 12: ...he unit can occur Electrical connection work The following applies to all work to be done Danger Risk of fatal electric shock Electrical connection work must be carried out by qualified electricians o...

Page 13: ...diately Familiarise yourself with the inside of the unit 1 Electrical switchbox 2 Intermediate floor of the unit Open the unit s electrical switchbox To do this only loosen the two upper screws of the...

Page 14: ...is used to fill the heating system no scale can form This effectively and permanently prevents limescale deposits and the resulting negative effects on the entire heating system Flushing and filling...

Page 15: ...the safe side with low salt operation The problems listed above do not occur at all with low salt operation as the heating water contains neither corrosive salts such as sulphates chlorides and nitrat...

Page 16: ...ting circuit and the heat source Insulate the heat source so that it is vapour diffusion tight Installing the control panel Danger Risk of fatal electric shock Electrical connection work must be carri...

Page 17: ...ntrol panel Note A connection to a computer or a network can be made via the left socket at the bottom of the control panel thereby allowing the heating and heat pump controller to be controlled remot...

Page 18: ...s the middle of the masking plate Then release the lugs on the opposite side Installation and removal of the screen Installing the screen Note The masking plate is provided in the as delivered unit so...

Page 19: ...echnical data Scope of delivery overview Electrics For details of the minimum heating circuit heat source flow rate refer to the Technical data Scope of delivery overview Heating circuit heat source s...

Page 20: ...eat pump systems In Germany Send completion report for heat pump systems and general checklist to the manufacturer s factory customer service department Outside of Germany Send completion report for h...

Page 21: ...ing system personnel may dismantle the unit from the system Important The antifreeze mixture of the heat source must not be allowed to get into the sewers Collect antifreeze mixture and dispose of pro...

Page 22: ...ntity kg Electrics Voltage code all pole circuit breaker heat pump A Voltage code circuit breaker control voltage A Voltage code circuit breaker electric heating element A Heat pump Effective power co...

Page 23: ...2 5 5 5 5 8 0 813220 f WWP 900X 88 9 5 2 47 1 5 4 87 2 3 7 46 2 3 8 83 6 4 9 44 3 5 1 82 7 4 0 43 8 4 0 20 60 7 25 57 17600 17600 30600 0 26 17600 Grundfos SP17 3 2 31 17600 7600 8500 15500 0 06 8500...

Page 24: ...35 C 2VD 50 C 2VD 35 C 1VD 50 C 1VD COP 2 3 4 5 6 7 8 5 10 15 20 25 30 Temp C Pe kW 0 5 10 15 20 5 10 15 20 25 30 Temp C p bar 0 0 0 1 0 2 0 3 0 4 0 0 2 0 4 0 6 0 8 0 10 0 p p bar 0 0 0 1 0 2 0 3 0 4...

Page 25: ...VD 50 C 2VD 35 C 1VD 50 C 1VD COP 2 3 4 5 6 7 8 5 10 15 20 25 30 Temp C Pe kW 5 10 15 20 25 5 10 15 20 25 30 Temp C p bar 0 0 0 1 0 2 0 3 0 4 0 0 2 0 4 0 6 0 8 0 10 0 12 0 14 0 p p bar 0 0 0 1 0 2 0 3...

Page 26: ...35 C 2VD 50 C 2VD 35 C 1VD 50 C 1VD COP 2 3 4 5 6 7 8 5 10 15 20 25 30 Temp C Pe kW 5 10 15 20 25 30 5 10 15 20 25 30 Temp C p bar 0 0 0 1 0 2 0 3 0 4 0 0 5 0 10 0 15 0 20 0 p p bar 0 0 0 1 0 2 0 3 0...

Page 27: ...35 C 2VD 50 C 2VD 35 C 1VD 50 C 1VD COP 2 3 4 5 6 7 8 5 10 15 20 25 30 Temp C Pe kW 5 10 15 20 25 30 5 10 15 20 25 30 Temp C p bar 0 0 0 1 0 2 0 3 0 4 0 0 5 0 10 0 15 0 20 0 p p bar 0 0 0 1 0 2 0 3 0...

Page 28: ...ensor cables 3 Heating water outlet flow Flange 2 IG DIN 2566 4 Heat source inlet Flange 2 IG DIN 2566 5 Heat source outlet Flange 2 IG DIN 2566 6 Heating water inlet return Flange 2 IG DIN 2566 7 Str...

Page 29: ...06 12 4 2007 RA Von RA Markieton RA Erst Gep Norm A DIN Legend UK819135 c All dimensions in mm A Front view C Top view Item Designation 1 Shaded area free space for service purposes 2 Concrete foundat...

Page 30: ...20 1 50 Det Ma stab Datum Name Erstellt Gepr Norm 4 6 2004 Aepfelbach 12 4 2007 Aepfelbach toleranz Allgemein DIN ISO 2768 c Oberfl chen ArtikelNr 819136 Aufstellung_Mindestabst nde_SWP_WWP 2 Legend...

Page 31: ...N PE Verteilung f r externe 230V Ger te ZW2 SST 4 ZUP Leitungsschutzschalter Steuerung A1 VBO A3 L1 A2 L1 Bezeichnung HUP PE ZW2 SST F10 A1 F12 Aussenf hler Steuersignal zus tzlicher W rmeerzeuger 2...

Page 32: ...Brunnen Solepumpe Motorschutzschalter Brunnen Solepumpe M2 Verdichter 1 Klemmleiste in Schaltkasten W rmepumpe N PE Verteilung f r externe 230V Ger te Einspeisung Leistung Verdichter Rechtsdrehfeld is...

Page 33: ...Sch tz Verdichter 1 1 2 3 N PE Einspeisung Steuerung 1 N PE 230V 50Hz F1 DE817328 Legende EVU Durchflusschalter F6 Externer Durchflusschalter Br cke wenn kein Schalter angeschlossen wird Funktion Netz...

Page 34: ...er R9 Zubeh r Raumfernversteller R7 Vorlauff hler Zubeh r Brauchwasser Thermostat R8 R3 RFV TVL TWE W rmequelle Eintrittsf hler F hler Mischkreis 1 TWA R11 BWT R5 Heissgasf hler THG TBW SWP 270H 430 W...

Page 35: ...ichter 2 Anlaufstrom Begrenzung Verdichter 1 Anlaufstrom Begrenzung Verdichter 2 N2 F5 MOT MOT 1 F4 N1 berlastrelais Verdichter 1 3 PE 400V 50Hz DE817329 3 PE 400V 50Hz M3 X7 B1 Bypass Sch tz Verdicht...

Page 36: ...z HDP 1 F1 DE817329 Sch tz Verdichter 1 Reglerplatine Achtung I max 6A 230VAC 1 2 3 N PE Einspeisung Steuerung Betriebsmittel Energie Versorger Kontakt bei Freigabe geschlossen Br cke wenn keine Sperr...

Page 37: ...R7 Vorlauff hler Zubeh r Brauchwasser Thermostat R8 R3 RFV TVL TWE W rmequelle Eintrittsf hler F hler Mischkreis 1 TWA R11 BWT R5 Heissgasf hler THG TBW SWP 330H 500H 540 820 WWP 700X 1100X Datum 8173...

Page 38: ...WP 1100X 100 371 EC Directives Harmonised EN 2006 42 EC EN 378 EN 349 2006 95 EC EN 60529 EN 60335 1 2 40 2004 108 EC EN ISO 12100 1 2 EN 55014 1 2 97 23 EC EN ISO 13857 EN 61000 3 2 3 3 National stan...

Page 39: ...elt Ja schwingungsentkopplungen der Heizkreis und W rmequellenanschl sse montiert Ja solarthermie anlage nein Ja solarthermie Anlage bef llt luftfrei und dicht Ja Frostschutz gepr ft bis c Typ Frostsc...

Page 40: ......

Page 41: ...derte Inbetriebnahme Ibn Art nr 16002101 Ibn p5 EW Art nr 16002501 Ibn 5 Art nr 16002201 Ibn Wp lG5 Art nr 16000901 Ibn 5 EW Art nr 16002301 Ibn l Art nr 16005001 Ibn p5 Art nr 16002401 Ibn l EW Art n...

Page 42: ...E Alpha InnoTec GmbH Industriestrasse 3 95359 Kasendorf Tel 49 0 9228 990190 Fax 49 0 9228 9906199 info alpha innotec com www alpha innotec com DK ASAP Energy Tinggaardvej 7 6400 S nderborg Tel 45 0 7...

Page 43: ...ww hydro tech pl PT GudEnergy Energias Renov veis Lda Av O S culo 21 r c D to 2135 231 Samora Correia Tel 351 0 263 652 727 Fax 351 0 263 652 526 info gudenergy pt www gudenergy pt SE Bj rneroth Tekni...

Page 44: ......

Reviews: