Installation and assembly
The following applies to all work to be done:
NOTE.
Always comply with the relevant local accident
prevention regulations, statutory regulations,
guidelines and directives.
NOTE.
Note the sound information for the respective model.
“Technical data/scope of supply” overview, “Sound”
section and “Sound pressure level” overview.
INSTALLATION LOCATION
ATTENTION
Install the unit outside buildings only.
Dimensioned drawing and installation plan for the
respective model.
TRANSPORT TO THE INSTALLATION LOCATION
To prevent damage during transport, transport the packed
unit to its final installation location using a pallet truck,
forklift truck or crane.
WARNING!
Risk of tilting and overturning on lifting the
unit from the wooden pallet and during trans-
port! People can be injured and equipment
damaged; always work with several people.
– Take suitable precautions to prevent the
risk of overturning.
ATTENTION
Never use components and hydraulic connections
on the unit for transport purposes.
ATTENTION
Do not tilt the unit by more than 45° maximum (in
any direction).
INSTALLATION
Place the unit on a load-bearing, firm and horizontal
foundation. Make sure that the foundation is designed
for the weight of the heat pump. Materials that fulfil this
requirement can be used for the foundation (concrete,
paving slabs, etc.). The surface in the air outlet area of the
heat pump must be permeable to water.
CAUTION!
In the air outlet area the air temperature is
approx. 5 K below the ambient temperature.
Under certain climatic conditions an ice
layer can therefore form in the air outlet
area.
Install the heat pump so that the air is not
blown out in the area of footpaths.
NOTE.
Always refer to and follow the installation plan for
the respective model. Note the size and minimum
clearances.