20 / 55
•
earthquake areas
–
additional security measures are required here;
•
sites that are higher than 3000 meters above the sea level;
•
sites with explosive atmosphere;
•
sites with direct sunlight;
•
sites with extreme change of ambient temperature;
•
wet rooms;
•
sites with highly flammable materials or gases; or
•
sites with a potentially explosive atmosphere;
2.1.2
Restricted Locations
Where the SMILE-T10 is located on or within 300mm of the wall or structure
separating it from the habitable room, the barrier shall extend
—
(i)
1000 mm beyond the vertical sides of the SMILE-T10;
(ii)
300 mm above the SMILE-T10; and
(iii)
to the extent of the bottom of the SMILE-T10.
Please refer to Figure 12.
Figure 12 Distancelimit of Installation to Neighboring Objects
Where the top of the SMILE-T10 is within 300 mm of the ceiling or structure above
the SMILE-T10, the ceiling or structure surface shall be suitably non-combustible for
an area of 600 mm past the extremities of the SMILE-T10.