![Alpha ESS SMILE-G3-B5 Manual Download Page 39](http://html.mh-extra.com/html/alpha-ess/smile-g3-b5/smile-g3-b5_manual_2905573039.webp)
ELECTRICAL CONNECTION
38
7.4.2
Grid and Backup Connection
Grid Connection
1.
Unscrew the swivel nut and take out the Seal ring from the threaded sleeve,
Insert the crimped conductors L, N and PE into the corresponding terminals
and tighten the screw with torque 2.0Nm
2.
Assemble the socket element, adapter and swivel nut together.
3.
Plug the AC connector into the socket for the AC connection and screw tight, When
doing so, align the AC connector so that the key on the inverter AC socket is inserted
into the keyway on the AC connector bush.
Backup Connection
1.
Unscrew the swivel nut and take out the Seal ring from the threaded sleeve,
Insert the crimped conductors PE, L, and N into the corresponding terminals
and tighten the screw with torque 1.2Nm.
ELECTRICAL CONNECTION
40