Alpha Communications AlphaRefuge 2100 Series Installation, Use And Wiring Instructions Download Page 8

8

System Operation & Testing

A. Once finished, the following 

Refuge Command Center 

LEDs should be lit:

•  Power LED, located on bottom edge of the faceplate, will be constant lit green

•  Battery LED, also located on bottom edge of the faceplate, will be constant lit.

•  Red = Low level charge

•  Yellow = Mid level charge

•  Green = Full Charge

B. Initiate a Call to an Emergency Phone or Sub-Master from the Refuge Command Center:

•  Lift handset on Refuge Command Center

•  Press the Talk button for the corresponding Refuge Call Box or Sub-Master you wish 

to call into

•  The green LED will light next to that button

•  You should have two-way communication to that device

•  You can place the device on hold by pressing the Talk button a second time

•  To resume communication, press the Talk button a third time

•  To disconnect, hang up the 

Refuge Command Center 

handset

C. Emergency Phone places a call into the Base Station:

•  You will hear an alternating audible tone at the Refuge Command Center indicating a 

call has been initiated by one of the phones

•  The corresponding green LED will light on the Refuge Command Center next to the 

phone that placed the call

•  Lift the handset and there is two-way communication between the 

Refuge Command 

Center

 and the 

Refuge Call Box

. The handset can be hung up on the 

Refuge Command 

Center 

at any time to end the call

D. Refuge Call Box places a call to the Refuge Command Center then an Outside Number, or 

Just to an Outside Number:

•  You will hear an alternating audible tone at the Refuge Command Center indicating a 

call has been initiated by one of the Refuge Call Boxes (if programmed to call outside 

line only, no tone)

•  The corresponding green LED will light on the Refuge Command Center next to the 

Refuge Call Box that placed the call

•  If call is not answered at the Refuge Command Center, the Refuge Call Box will hang 

up and dial the second number programmed into the phone

•  The CO Line LED, located next to the red button, will also be lit indicating that the 

outside line is active. Two-way communication can then take place between the outside 

line and the Refuge Call Box once the call is answered

•  The Refuge Command Center can join the conversation by lifting the handset

•  To talk to rescue services 

only

 from the Refuge Command Center, place the Refuge 

Call Box on hold by pressing the corresponding Talk button. To bring them back into 

the conversation, press the Talk button again.

•  To disconnect rescue services, press the red button at the top of the Refuge Command 

Center faceplate. The Rescue Services LED will go off and leave you communicating 

with the Refuge Call Box only.

•  Handset on the Refuge Command Center can be hung up at any time to end the call.

If above testing works and voice communication is clear, congratulations, 

you have successfully installed the system!

Summary of Contents for AlphaRefuge 2100 Series

Page 1: ...uires use of Alpha Model ABL VOIP to connect Master to VoIP phone system 3 Internal Intercom no offsite calling requires Alpha Model 2100 LINESIM Twisted shielded 22 or 24 AWG wire cabling to connect each Refuge Call Box RCB to the Refuge Command Center RCC Use 24V 18 2 wire for powering the Emergency Phones from the 24VDC Power Supply NOTE Terminals and markings shown in this manual may not be in...

Page 2: ...he wall using suitable mounting screws not included Step 2 Punch out the conduit knockouts for the analog phone line and phone cabling runs Step 3 Connect an analog phone line to the outside phone line Diagram A Step 4 Connect the backup battery cable to the battery terminal battery included Diagram A DIAGRAM A ...

Page 3: ...ect the hot wire of the 120vac to the L screw Connect the neutral wire of the 120vac to the N screw Connect the ground wire of the 120vac to the ground screw Connect one lead of the DC power connection to the V screw and the other to the V screw polarity is not important Connect the DC power connection to the SmartRescue The power connection is on the lower left hand side of the board ...

Page 4: ...uge Command Center Insert 4 wires for each phone as shown below To Refuge Call Box Wire out to a standard 2 pair RJ11 phone jack Connect this jack to the 5 cord supplied by Alpha Refuge Command Center The Refuge Call Boxes come with a 5 cord with an RJ11 on both ends If you received a spade connector your company requested it Wire ac cording to your company guidelines Shields from the cabling runs...

Page 5: ...is not manned 24 7 to answer calls onsite Option 2 Program the Refuge Command Center to Allow the Emergency Phones to call it first then outside number s Used when staff are available at certain times to answer calls 1 Hold down Red Disconnect and Submaster 1 buttons for 5 seconds 2 Release buttons you will hear a confirmation tone 3 Press Phone 2 button then Red button and then the Phone 1 button...

Page 6: ...ten Refuge Call Boxes via PWR2410A Power Supply Use 1 pair 18 AWG wire for power maximum distance of 5 100 Do NOT wire more than 3 devices per wire run and a maximum of 10 devices per Power Supply Option 1 Transformers Only if your phone comes with one supplied by Alpha Requires 120VAC Option 2 Powered Directly by Elevator Car Requires 120VAC ...

Page 7: ... to get into program mode Press 1 Enter Emergency Number Stop Press 2 Enter same Emergency Number as entered in b Stop To exit programming mode Press and hold Stop for 2 3 seconds until warble sound Step 10b Program the Location Message NOTE This Should ALWAYS be done unless your call center requests otherwise Press Enter to get into program mode To turn on message press 1 3 Enter 2 For no message...

Page 8: ...at any time to end the call D Refuge Call Box places a call to the Refuge Command Center then an Outside Number or Just to an Outside Number You will hear an alternating audible tone at the Refuge Command Center indicating a call has been initiated by one of the Refuge Call Boxes if programmed to call outside line only no tone The corresponding green LED will light on the Refuge Command Center nex...

Page 9: ...9 1 6 all primary and secondary power supplies shall be monitored for the presence of voltage at the point of connection to the system 10 6 9 1 1 Failure of either the primary or secondary power supply shall result in a trouble signal in accordance with section 10 14 10 6 7 2 1 The secondary power supply battery back up shall have sufficient capacity to operate the system under quiescent load syst...

Page 10: ...t detected it will trigger the onboard relay Connect the relay to an alarm device for notification Appendix Adjusting Volume on Refuge Call Boxes Locate the silver VR1 port on the bottom right corner of the Refuge Call Box board Using a fine Philips Head screwdriver turn the VR1 clockwise to increase the volume and counterclockwise to decrease the volume ...

Page 11: ...otification means Appendix Restoring Refuge Command Center Factory Default Settings Hold down Red Disconnect and Submaster 1 buttons for 5 seconds Release buttons you will hear a confirmation tone Press Phone 2 button then Red button then Submaster 2 button and then the Phone 5 button Press Submaster 2 button then Submaster 1 button you will hear a confirmation tone ...

Page 12: ...t Two way communica tion from Refuge Call Box is poor There is likely feedback on the line Adjust the VR1 and VR2 Verify wiring is not spliced onto the phone line cord Refuge Command Cen ter will not dial phones Verify wires are connected properly from the Refuge Command Center to the Refuge Call Box es Refuge Command Cen ter will dial Refuge Call Boxes but Call Boxes will not dial Command Center ...

Page 13: ...13 ...

Page 14: ...14 ...

Page 15: ...15 ...

Page 16: ...16 ...

Page 17: ...17 RCB2100SF Flush Mount St Steel Remote Call Box Station ...

Page 18: ...18 RCB2100SF Flush Mount St Steel Remote Call Box Station ...

Reviews: