Fail Secure Lock
There is no current
ß
owing through the relay on the Fail Secure lock. When the relay is activated, the
current
ß
ow is opened, and the door lock will open. If the power supply is cut o
"
due to a power
failure or an external factor, the door will remain closed.
NO - Orange/Red
COM - Brown/Red
-
!
+
Connect the two NO wires together to the + wire
on the lock.
!
Connect the two COM (Brown/Red) wires to the
+ on the power source.
!
Connect the - wire from the power source to the
- on the lock.
!
Each wire supports up to 1A, connecting
together will allow for up to 2A current to
ß
ow.
F3D100 Pigtail
Connect Power over Ethernet Cable (PoE)
The F3D100 uses 802.3at (PoE+).
!
Connect a Cat5/6 ethernet cable to the RJ45 located on the pigtail of the F3D100.
!
To setup network connection use the Alocity setup app.
!