background image

TPM 083/12

7

Tab. 3.2.1.  Weight and  effective area

 Size

  D

a

Weight

Effective area

 S

ef

 [m

2

]

Actuating mechanism

100

-

3,1

0,0036

BLF

125

-

3,4

0,0068

BLF

140

-

3,6

0,0092

BLF

150

-

3,7

0,0109

BLF

160

-

3,8

0,0129

BLF

180

-

4,1

0,0172

BLF

200

-

4,4

0,0222

BLF

225

-

4,7

0,0293

BLF

250

9

5,5

0,0374

BLF

280

24

6,0

0,0484

BLF

315

41,5

6,6

0,0630

BLF

350

59

7,0

0,0793

BLF

355

61,5

7,3

0,0821

BLF

400

84

8,2

0,1065

BLF

3.2.  

Weight and  effective area

4. Placement and Assembly

4.1.  

Fire dampers are suitable for installation in arbitrary position in vertical and horizontal passages 
of  fire  separating  constructions.  Damper  assembly  procedures  must  be  done  so  as  all  load 
transfer  from  the  fire  separating  constructions  to  the  damper  body  is  absolutely  excluded. 
Back-to-back air-conditioning piping must be hung or supported so as all load transfer from the 
back-to-back piping to the damper is absolutely excluded.

3.3.  

For fire damper the open damper blade overlaps the damper body from dimension    250 by the 
“a” value. These values are specified in the Tab. 3.2.1

 

Value has to be respected when projecting related air-conditioning piping.

Fig. 4 

Value “a”

Summary of Contents for MANDIK FDMC

Page 1: ...0 1 0 A L N O RS y s t e myWe n t y l a c j i S p z o o A l e j aK r a k o w s k a1 0 0 5 5 5 2Wo l aMr o k o w s k a t e l 2 27 3 7 4 0 0 0 f a x 2 27 3 7 4 0 0 4 w w w a l n o r c o m p l F I R E D...

Page 2: ...tement of installations 9 III TECHNICAL DATA 10 6 Pressure loss 10 7 Coefficient of local pressure loss 11 8 Noise data 11 9 Electrical Components Connection Diagrams 13 IV ORDERING INFORMATION 16 10...

Page 3: ...mum pressure difference 1200 Pa b Dampers could be displaced into position CLOSED only in case that ventilator or Air Handling Unit is switched off The goal is the securing of proper closing and safe...

Page 4: ...whole system Nonpotential auxiliary contacts enable connection to the master control system signalisation of the damper position failure reports release of the ventilators etc While a flashing green...

Page 5: ...LURE If the fire dampers do not reach the given position in time tolerable for displacing the appropriate light diode FAILURE starts to flash and K1 contact is opened current failure In case that the...

Page 6: ...3 12 6 Fig 1 Fig 2 Fire damper FDMC 3 Dimestions weights 3 1 Dimensions Position 1 Damper body 4 BAE 72B S thermoelectrical starting mechanism 2 Damper blade 5 Inspection hole covering 3 Actuating mec...

Page 7: ...ampers are suitable for installation in arbitrary position in vertical and horizontal passages of fire separating constructions Damper assembly procedures must be done so as all load transfer from the...

Page 8: ...ng or closing 4 6 Installation opening dimensions 4 2 To provide needed access space to the control device all other objects must be situated at least 350 mm from the control parts of the damper Inspe...

Page 9: ...een damper and wall is filled by mortar gypsum EIS 60 8 Damper installed in a ceiling wall construction min thickness 150 mm Space between damper and wall is filled by mortar gypsum EIS 60 9 Position...

Page 10: ...6 2 1 Pressure losses for air density 1 2 kg m 3 6 Pressure loss 6 1 Pressure loss calculation III TECHNICAL DATA 6 2 Determination of pressure loss by using diagram 6 2 1 1 2 kg m 3 p w2 2 p Pa pres...

Page 11: ...53 3 55 1 56 5 57 7 6 34 8 40 2 43 3 45 6 48 7 51 0 52 7 55 8 58 1 59 8 61 2 62 4 7 38 8 44 2 47 3 49 6 52 7 55 0 56 7 59 9 62 1 63 8 65 2 66 4 8 42 3 47 7 50 8 53 1 56 2 58 4 60 2 63 3 65 6 67 3 68 7...

Page 12: ...b 8 3 2 Correction to the weight filter A w m s 1 2 3 4 5 6 7 8 9 10 11 12 KA dB 15 0 11 8 9 8 8 4 7 3 6 4 5 7 5 0 4 5 4 0 3 6 Tab 8 3 3 Relative level expressing the shape of the spectrum Lrel f Hz w...

Page 13: ...s Protection Class III II Degree of protection IP 54 Running time motor spring return 40 75 s 20 s Ambient Temperature normal duty safety duty non operating temperature 30 C 50 C The safe position wil...

Page 14: ...lug of 26 type 6 pole plug 3 pole plug screw terminals for conductor 2x1 5 mm2 9 2 Communication and Supply Device Fig 15 Communication and Supply Device BKN 230 24 9 3 Communication and Control Devic...

Page 15: ...l Device BKS 24 9A Communication and Control Device BKS 24 9A Nominal voltage AC 24 V 50 60Hz Power consumption 3 5 W operating position Dimensioning 5 5 VA Protection Class III safe small voltage Deg...

Page 16: ...Device BKS 24 9A technical specifications design acc dle Tab 2 3 1 size type FDMC 180 TPM 083 12 40 V DATA OF THE PRODUCT 11 Data label 11 1 Data label is placed on the body of fire damper Fig 18 Data...

Page 17: ...ulated During transportation the damper blade must be in the CLOSED position VIII TRANSPORTATION AND STORAGE 14 2 Dampers are stored indoor in environment without any aggressive vapours gases or dust...

Page 18: ...off the actuating mechanism supply e g by pressing the RESET button at the thermoelectrical starting mechanism BAE 72B S or cutting off the supply from ELECTRICAL FIRE SIGNALISATION Check of blade di...

Page 19: ...TPM 083 12 19...

Page 20: ...z o o A l e j a K r a k o w s k a 1 0 0 5 5 5 2Wo l a M r o k o w s k a P o l s k a T e l 4 82 2 7 3 7 4 0 0 0 F a x 4 82 27 3 7 4 0 0 4 E M a i l a l n o r a l n o E M a i l a l n o r a l n o r c o m...