.7 Emergency stop
The emergency stop becomes active when all following conditions are true:
• The emergency stop is not blocked
• T
supply
< +5˚C (Emergency stop temperature #20)
!
!
NOTE:
The emergency stop can only be cleared by a power down. (power cut off).
6.8 Auto return to auto mode
Parameter Auto return to auto mode (#60) is normally disabled. If you enable this option (only by authorized
service personnel), unit returns to auto mode automatically after set value.
NOTE:
Auto mode works only when you have minimum one VMS sensor (CO2 or RH) paired with HRU.
6.9 Filters
The unit is delivered from the factory equipped with two filters: ISO Coarse 70% (G4) filter - optionally ISO
ePM1 55% (F7) on the supply side, and ISO Coarse 70% (G4) filter, optionally ISO ePM1 55% (F7) on the
exhaust side.
It is also possible to install an ISO Coarse 70% (G4) filter, optionally ISO ePM1 55% (F7) on the exhaust side
and ISO Coarse 70% (G4) filter, optionally ISO ePM1 55% (F7) on the supply side as an accessory.
NOTE:
Please remember
that additional
filters increase
pressure drop
in all ventilation system.
!