Chapter 6: Flow Measurements Using the Capture Hood
57
Note
It is important that the capture hood see the same flow for both parts of the backpressure
compensated flow measurement. It is best to keep the Capture Hood in place for both
measurements, but it is alright to remove and replace the Capture Hood between the two
readings. However, if the flow is changed or changing between the two measurements, the
measurement results will be inaccurate.
“ERROR” Display
For the backpressure compensation measurement to be meaningful, the measurement in the flap
“
OPEN
” position must be higher than the measurement in the flap “
CLOSED
” position. If this is not true,
the ProHood meter will display an error: backpressure open greater than closed.
Summary of Contents for Airflow Proood PH730
Page 2: ......
Page 8: ...vi This page intentionally left blank...
Page 14: ...6 Airflow Instruments ProHood Capture Hoods PH730 PH731 This page intentionally left blank...
Page 24: ...16 Airflow Instruments ProHood Capture Hoods PH730 PH731 This page intentionally left blank...
Page 28: ...20 Airflow Instruments ProHood Capture Hoods PH730 PH731 This page intentionally left blank...
Page 50: ...42 Airflow Instruments ProHood Capture Hoods PH730 PH731 This page intentionally left blank...
Page 62: ...54 Airflow Instruments ProHood Capture Hoods PH730 PH731 This page intentionally left blank...
Page 66: ...58 Airflow Instruments ProHood Capture Hoods PH730 PH731 This page intentionally left blank...
Page 70: ...62 Airflow Instruments ProHood Capture Hoods PH730 PH731 This page intentionally left blank...
Page 74: ...66 Airflow Instruments ProHood Capture Hoods PH730 PH731 This page intentionally left blank...
Page 78: ...70 Airflow Instruments ProHood Capture Hoods PH730 PH731 This page intentionally left blank...