7. TROUBLESHOOTING 

This controller has many capabilities other than those used for the Almex Temperature Control. Adjust only 
those settings described above. Other adjustments may result in the control panel being inoperable. For detailed 
instruction of the E5GN controller, refer to the OMRON manual supplied with this temperature control panel. 

7.1. 

No Display on Temperature Controller 

FAULT CORRECTION 

1. 

 

Power supply is faulty. 

1. 

 

Check the supply cables and power supply connection. 

7.2. 

Error Display on Temperature Controller 

FAULT CORRECTION 

1. 

 

Loose connection in cable or 
platen connector. 

1. 

 

Remove electrical connector insert from housing and 
tighten all connections. 

2. 

 

RTD temperature sensor is 
faulty. 

2. 

 

Measure the resistance between pins 4-5 and 4-6 on the 
platen electrical connector. Depending on the platen 
temperature, the resistance should be between 100-170 
Ohms. Replace probe as described in the vulcanizer 
manual. The leads should be protected from moisture by 
using a small amount of silicone in the back of the insert 
terminal to seal the connection. 

7.3. 

Vulcanizer Not Heating 

FAULT CORRECTION 

1. 

 

Platen switch OFF. 

1. 

 

Turn platen switch to 

1A

 or 

1M

2. 

 

Temperature set improperly. 

2. 

 

Ensure that controller set point is correct. 

3. 

 

No continuity between power 
supply and platen. 

3. 

 

Check power supply fuses or breakers and cable 
connections. 

4. 

 

Loose connection in control 
panel. 

4. 

 

Disconnect power supply, remove control panel cover 
and check for loose wire connections. 

5. 

 

Faulty temperature controller. 

5. 

 

Refer to OMRON instruction manual. 

6. 

 

Faulty relay. 

6. 

 

Disconnect power supply, and remove control panel 

cover. Very carefully connect power supply and with 
temperature controller OUT light on, check for power 
between relay terminals 2-6 and 4-8. If full line voltage is 
not measured, relay must be replaced. 

7. 

 

Loose connection in cable or 
platen connector. 

7. 

 

Remove electrical connector insert from housing and 
repair any loose connections. 

8. 

 

Faulty RTD temperature 
sensor. 

8. 

 

Measure the resistance between pins 4-5 and 4-6 on the 
platen electrical receptacle. Depending on the platen 
temperature, the resistance should be between 100-170 
Ohms. 

9. 

 

Faulty heating element. 

9. 

 

Measure the resistance between pins 1-3 on the platen 
electrical receptacle. Compare the reading with the value 
in your Record of Purchase, Element Resistance, Coils 
Connected. If the values are not close and the wires and 
connections are good, the element must be replaced. 

Summary of Contents for T1

Page 1: ...rame Mount Models TEMPERATURE CONTROL PANEL This manual was prepared to present the correct methods and procedures of operating and maintaining your ALMEX TEMPERATURE CONTROL PANEL Read this manual carefully before operating your vulcanizer SHAW ALMEX INDUSTRIES LIMITED PO Box 430 Parry Sound Ontario Canada P2A 2X4 Phone 705 746 5884 or 1 800 461 4351 Fax 705 746 9484 E mail SAIL ALMEX COM ...

Page 2: ...Temperature 7 5 1 2 Applying and Removing Protection to Settings 7 5 1 3 Setting Temperature Units to C or F 8 5 2 Heating the Vulcanizer 8 5 3 Manual Override 8 5 4 Temperature Control 8 6 MAINTENANCE 9 6 1 Opening the Control Cabinet T1R2 Models 9 6 2 Removing Control Panel from the Frame T1F2 T1F3 Models 9 6 3 Temperature Calibration 9 6 3 1 Auto Tune 10 6 3 2 Temperature Offset 10 7 TROUBLESHO...

Page 3: ...r Serial Number Weight 2 lb 1 kg Voltage Phase Single Cycle Hertz 50 60 Amperage Maximum 15 Circuit Over current Protection Required Temperature Sensor 100 Ω platinum RTD Index of Protection IP 54 Ancillary Items none Spare Parts none Operating Instructions 49900 030 R05 2005 Supplements OMRON E5GN Service Bulletins none Warranty Card yes Drawings Parts Diagrams 49950 022 T1R2 T1F2 T1F3 ...

Page 4: ...trol Model T1 Year of Design 2001 has been manufactured using the following transposed harmonized European Standards EN 60204 1 Safety EN 50081 1 Emissions EN55011 EN 50082 1 Immunity EN61000 4 2 3 4 5 and is in conformity with the following Directives 73 23 EEC Low Voltage Directive amendment 93 68 EEC 89 336 EEC EMC Directive amendment 92 31 EEC 89 392 EEC Machinery Directive Signed in Parry Sou...

Page 5: ... 1 Electrical Hazard 1 A qualified electrician should perform all maintenance of the electrical components of the temperature control panel 2 All of the electrical components contain live circuits Do not open or service the electrical equipment without disconnecting the main power supply 3 Incorrect voltage and phase may result in component damage and create a fire hazard Refer to serial plate for...

Page 6: ...carrier and or Shaw Almex Industries Limited 4 2 Temperature Control Panel Features The T1 temperature control panel is designed to control the temperature of a single platen in a vulcanizer Two T1 panels are used for independent control of top and bottom platens of a vulcanizer Saftey Each control panel may have to be plugged into a separate circuit to avoid exceeding the amperage capacity of the...

Page 7: ...r The controller displays the process value No 1 display which is the actual platen temperature and set value No 2 display which is the desired temperature 5 1 Temperature Control Settings The average user need only adjust the temperature set point The temperature controller has many other settings that have been set by the factory and these can be adjusted The controller settings can be protected...

Page 8: ... to increase as the platen temperature rises Safety The platen will begin to get hot 3 When the set point no 2 display is reached the OUT indicator will continue to flash on and off to maintain set value temperature Start timing the cure when set value is reached 4 After the cure time turn the controller switch to the OFF position 5 For minimal overshoot on the next heating cycle reset the control...

Page 9: ... the frame 4 On T1F3 models disconnect the heating element wires form the relay and the temperature sensor wires from the controller 6 3 Temperature Calibration After replacing a temperature controller a platen temperature sensor or a platen heating element the temperature controller should be calibrated to achieve the best performance Failure to calibrate the controller with the vulcanizer will r...

Page 10: ...y to wait for the At display to stop flashing before returning to the temperature display 4 Press the Level key for less than one second to return to the temperature display The no 2 display set value will flash until tuning is complete 5 If the Process Value and the temperature on the test meter are different proceed to 6 3 2 Temperature Offset to make adjustment 6 3 2 Temperature Offset If the e...

Page 11: ...connection 7 3 Vulcanizer Not Heating FAULT CORRECTION 1 Platen switch OFF 1 Turn platen switch to 1A or 1M 2 Temperature set improperly 2 Ensure that controller set point is correct 3 No continuity between power supply and platen 3 Check power supply fuses or breakers and cable connections 4 Loose connection in control panel 4 Disconnect power supply remove control panel cover and check for loose...

Page 12: ...ontroller will not maintain Set Point Temperature FAULT CORRECTION 1 Controller not calibrated properly 1 Follow calibration procedure 2 Faulty temperature controller 2 Refer to OMRON instruction manual Replace temperature controller 8 Service 8 1 Emergency Service Contact Service Department Telephone 705 746 5884 1 800 461 4351 Canada and U S only Fax 705 746 9484 Mail SHAW ALMEX INDUSTRIES LIMIT...

Reviews: