background image

INSTALLATION OF THE SUPER 

STATION

 

OR A STANDARD WALL PUSH 

BUTTON  

 

The Super Station (Deluxe Wall Pushbutton Station) is 

a 7 function station designed to work with and 

maximize the operation of your  opener.  Connection 

to any other operator may damage the operator and/or 

the Super Station.  Only connet one Super Station to 

the operator.  Do not connect more than one Super 

Station to the Operator. 

If desired, a standard wall push button may be 

installed and connected to your opener as an alternate 

to the Super Station or in addition to the Super Station.  

A standard wall push button is not included in your 

hardware package, it can be purchased from your 

professional installing dealer or a door bell button 

[without light] can be substituted. The operating 

parameters for the standard wall push button are 

outlined on a page that  follows to see if that mode of 

operation is right for you. The Super Station is 

included with your opener and it’s installation is 

recommended, the Super Station will provide full 

control over the garage door at all times. 

 

YOU MAY CONNECT ONLY ONE SUPER 

STATION PER OPERATOR - 

ADDITIONAL STANDARD WALL PUSH 

BUTTONS MAY BE CONNECTED TO THE 

OPERATOR 

STEP 1: 

 

After determining a suitable location, 

usually near the access door and at least 5 feet above 

the floor to prevent use by children, use the Super 

Station or the standard wall push button as a guide to 

mark the mounting holes.  Drill holes for drywall 

anchors or screws.  NOTE: Do not mount directly to 

masonry walls.  Use backer board.

 

of 2-conductor, #22 gauge wire (or heavier) is 

required to connect either control to the garage door 

operator.  Strip approximately 2” of the wire jacket 

from one end and 1/2” of insulation from each wire.  

Carefully connect one wire to each of the two 

terminals. Carefully tuck the loose wires into the case 

and mount the unit using appropriate screws.

 

 

STEP 3: 

 

Run the wire from the control to the 

operator, supporting it at 18” intervals with suitable 

staples.  Leave a sufficient length to make the 

necessary connections to the operator terminal strip.

 

WARNING:  SOME LOCAL BUILDING CODES 

DO NOT ALLOW SURFACE WIRING.  BE 

SAFE AND CHECK WITH YOUR LOCAL 

BUILDING INSPECTOR FIRST. 

 

STEP 4:

  

Ensure power is OFF to the opener or 

disconnect the power from the opener.  Strip 

approximately 4” of jacket from the end of the wire 

and 1/2” insulation from each wire.  

Connect to terminals 0 and 1 as shown in 

the illustration at left. Support the wire near 

the 

operator 

with wire 

ties.

 

See Step 5, 
next page. 

 

 

WARNING 

A CHILD OPERATING THE DOOR 

CONTROLS RISKS INJURY — OR 

DEATH — TO HIMSELF AND OTHERS. 

DO NOT ALLOW CHILDREN TO 

OPERATE 

ANY 

DOOR CONTROLS.   

MOUNT THE PUSHBUTTON AT LEAST 

5 FT FROM THE FLOOR, OUT OF 

REACH OF CHILDREN. 

CONTROL AND AUXILIARY EQUIPMENT 

WARNING 

IMPROPER DOOR OPERATION 

COULD CAUSE INJURY OR DEATH.  

WARNING LABEL MUST BE 

MOUNTED ON WALL NEAR  THE 

PUSHBUTTON.  ALL WARNINGS AND 

INSTRUCTIONS ON THE LABEL 

SHOULD BE STRICTLY ADHERED TO. 

!

Child can be pinned under automatic garage 
door. 

Death or serious injury can result.

• 

Never let child walk or run under moving door.

• 

Never let child use door opener controls.

• 

Always keep moving door in sight.

• 

If person is pinned, push control button or use 

emergency release.

• 

Test door opener monthly:

Refer to your owner’s manual

Place one-inch object (or 2x4 laid flat) on floor.

If door fails to reverse on contact, adjust opener.

If opener still fails to reverse door, repair or replace opener.

W AR N I N G  

104350 

CONTROL BUTTON 

WARNING LABEL 

PUSHBUTTON

4

3

2

1

0

TWO WIRE

OPERATOR

RECEIVER

TRANSMITTER

(DELUXE PUSHBUTTON)

SUPER STATION

T2

T1

PHOTOCELL SERIES CONNECTION (RECEIVER FIRST)

SAFE FINISH PHOTOSYSTEM

CONNECTIONS

WIRE NUT

IMPORTANT: DO NOT CONNECT SAFE

FINISH PHOTOSYSTEM AND EDGE SYSTEM

AT THE SAME TIME.  THE SYSTEMS MUST

BE USED INDEPENDANT OF EACH OTHER.

CONTACT THE FACTORY FOR EDGE SYSTEM

CONNECTION.

108387 

Summary of Contents for SUPER BELT MVP-SB

Page 1: ...ndicates a MECHANICAL hazard of INJURY OR DEATH Gives instructions to avoid the hazard Operation and Adjustment Instructions 12 Basic Operating Parameters 12 Door Arm Connection 13 Programming The Rad...

Page 2: ...manual operation of the door when desired as in the event of a power failure The trolley release can be set to lock out automatic reconnection if desired Page19 Automatic Reconnection Once power is re...

Page 3: ...FINISH PHOTOSYSTEM WARNING SPRINGS PULLEYS CABLES AND MOUNTING HARDWARE USED TO BALANCE YOUR GARAGE DOOR ARE UNDER EXTREME TENSION AT ALL TIMES AND CAN CAUSE SEVERE INJURY OR DEATH IF DISTURBED DO NO...

Page 4: ...TORMOREABOVETHEFLOOR MOUNT THEEMERGENCYRELEASE6FTABOVETHE FLOOR REINFORCELIGHTWEIGHTFIBERGLASS ALUMINUMANDSTEELDOORTOPSECTIONS TOAVOIDDAMAGEANDTOINSUREPROPER OPERATIONOFTHESAFETYREVERSE SYSTEM CONTACT...

Page 5: ...oward the Door Front Idler see Illustration B Lock the Trolley Outer Half onto the Inner Half STEP 4 Remove and discard the tape used to keep the belt looped at the one end on the rail assembly during...

Page 6: ...mper into its mounting hole on the Tee Rail see Illustration E for location Secure the Bumper to the bottom of the Tee Rail using one 5 16 18 x 1 hex head bolt and one 5 16 18 washered nut supplied Ti...

Page 7: ...not rub on the Tee Rail and that you have allowed the proper clearances before proceeding STEP 4 MountPower HeadtoCeiling Since there is such variety in ceiling structures all the mounting possibiliti...

Page 8: ...e rubber jacket of the Line Cord and wire in permanently employing proper wiring practices Discard Strain Relief It is not used with permanent wiring Step 10 Install a Rough Service lamp bulb 75 Watt...

Page 9: ...mount the unit using appropriate screws STEP 3 Run the wire from the control to the operator supporting it at 18 intervals with suitable staples Leave a sufficient length to make the necessary connect...

Page 10: ...ted to the jamb with a 1 flat head nail provided using the small hole above the slot Using two 5 16 X 1 1 2 lag screws provided permanently mount the L bracket to both door jambs STEP 3 Connect the Ph...

Page 11: ...PEOPLE AND OBJECTS AWAY FROM THE DOOR AREA UNTIL THE DOOR IS COMPLETELY CLOSED NO ONE SHOULD CROSS THE PATH OF A MOVING DOOR NEVER GO UNDER A STOPPED PARTIALLY OPEN DOOR TEST THE DOOR OPENER MONTHLY...

Page 12: ...will then automatically turn off At this time before connecting the door arm activate the door operator through 2 cycles of operation to verify proper limit function The trolley should stop at a mini...

Page 13: ...Align connecting hole in the door arm to middle hole in the door bracket insert 3 8 diameter bolt and tighten locking nut allowing for free pivot of the arm Note Do not overtighten locking nut as thi...

Page 14: ...tton Continue to hold both the and buttons until the LED starts to blink approximately 5 seconds When the LED starts to blink IMMEDIATELY release both the and buttons The LED will blink two times and...

Page 15: ...location of the transmitter and receiver antenna will affect distance If the opener doesn t activate check if the power head unit has been programmed to accept the transmitter signal The red LED on t...

Page 16: ...a stiff cardboard carton placed in the door s downward path to indicate the force the Opener is exerting If the force adjustment screws are properly set the door should stop if opening and reverse if...

Page 17: ...up Used to start the door upward This button will also stop and reverse a door that is closing The button has no effect on a door that is opening The function of this pushbutton is automatically disa...

Page 18: ...om all of these devices are locked out by the operator Such devices will continue to work until the door is fully closed allowing you to set the switch when leaving on vacation for example leave the g...

Page 19: ...ON RED LED GREEN LED Normal Operation OFF OFF Learn Mode ON OFF Memory Full ON FOR 25 SEC AUTO OFF OFF Decode RF Signal SHORT FAST BLINK OFF Shorted Push Button or Wire to Button OFF ON Photobeam Obst...

Page 20: ...ithin the warranty period which upon receipt by Linear are confirmed to be defective and covered by this limited warranty will be repaired or replaced at Linear s sole option at no cost and returned p...

Reviews: