background image

507787-01

Issue 2007

Page 17 of 22

Air Handler Model

Blower Speed

.10

"

 WC

.20

"

 WC

.30

"

 WC

.40

"

 WC

.50

"

 WC

-018

LOW

538

525

503

471

418

MED

688

670

639

603

548

HIGH

919

881

855

788

710

-024

LOW

677

673

657

629

592

MED

1011

979

942

803

742

HIGH

1106

1045

999

917

857

-030

LOW

871

870

853

812

769

MED

1078

1057

1024

987

936

HIGH

1311

1261

1214

1154

1086

-036

LOW

1020

972

956

909

806

MED

1276

1240

1191

1148

1086

HIGH

1559

1521

1446

1395

1327

-042

LOW

1300

1273

1250

1211

1155

MED

1527

1493

1452

1390

1345

HIGH

1816

1756

1693

1605

1528

-048

LOW

1257

1212

1157

1116

1053

MED LOW

1486

1448

1411

1364

1330

MED

1721

1675

1630

1594

1553

MED HIGH

1721

1675

1630

1594

1553

HIGH

1840

1794

1754

1721

1681

-060

LOW

1098

1049

1001

926

831

MED LOW

1624

1594

1565

1520

1492

MED

1815

1783

1758

1730

1685

MED HIGH

1903

1869

1837

1809

1764

HIGH

1981

1957

1923

1893

1861

Blower Performance (CFM vs. ESP in. w.c.)

• 

Cooling speeds should not be reduced below factory setting. 

• 

All units with electric heat approved at 0.5” maximum and medium blower speed minimum. 

• 

All downflow applications run on high speed when utilizing electric heat.

Table 4. BCE5C 

Blower Performance (3-Speed PSC) – 240V (CFM @ ESP. – in. W. C.)

Summary of Contents for BCE5C Series

Page 1: ...8 Operation 18 Repairing or Replacing Cabinet Insulation 19 Professional Maintenance 20 Homeowner Maintenance 20 Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a licensed professional HVAC installer or equivalent service agency or the gas supplier WARNING The Clean Air Act of...

Page 2: ...4 121 4 3 8 111 2 3 8 60 CONDENSATE DRAINS 2 Upflow and Downflow SUCTION LINE CONDENSATE DRAIN PIPING PLATE 3 2 1 4 x 3 3 4 BCE5C Unit Dimensions Upflow Inches mm Dimensions 018 024 030 036 042 048 060 in mm in mm in mm in mm in mm in mm A 43 1 2 1105 45 1 2 1156 47 1194 53 5 8 1362 55 1397 59 3 4 1518 B 18 1 2 470 18 1 2 470 18 1 2 470 21 1 2 546 21 1 2 546 21 1 2 546 C 16 1 2 419 16 1 2 419 16 1...

Page 3: ...fore starting the installation In addition to conforming to manufacturer s installation instructions and local municipal building codes installation of air handler units with or without optional electric heat MUST conform with National Fire Protection Association NFPA standards Standard for Installation of Air Conditioning and Ventilation Systems NFPA No 90A and Standard for Installation of Reside...

Page 4: ...e air handler evaporator coil supply fan assembly and duct system must be thoroughly cleaned following final construction clean up All air handler operating conditions must be verified according to these installation instructions EQUIPMENT MAY EXPERIENCE PREMATURE COMPONENT FAILURE AS A RESULT OF FAILURE TO FOLLOW THE ABOVE INSTALLATION INSTRUCTIONS FAILURE TO FOLLOW THE ABOVE INSTALLATION INSTRUC...

Page 5: ... coil may tip into the drain pan once it is clear of the cabinet Support the coil when removing it IMPORTANT NOTE When the unit is installed in horizontal applications a secondary drain pan is recommended Refer to local codes NOTE This unit may be installed in left hand or right hand air discharge horizontal applications Adequate support must be provided to ensure cabinet integrity Ensure that the...

Page 6: ...r The 90º bend must be on the same side as the horizontal drain pan as illustrated in Detail A in Figure 5 NOTE Be very careful when reinstalling the screws into the coil end plate engaging holes Misaligned screws may damage the coil 9 From the upflow position flip cabinet 90º to the left and set into place Replace blower assembly Secure coil in place by bending down the tab on the cabinet support...

Page 7: ...heet metal screws 14 If suspending the unit it must be supported along the entire length of the cabinet If using chain or strap use a piece of angle iron or sheet metal attached to the unit either above or below so that the full length of the cabinet is supported Use securing screws no longer than 1 2ʺ to avoid damage to coil or filter as illustrated in Figure 3 Connect return and supply air plenu...

Page 8: ...m Insulate the drain lines where sweating could cause water damage Test Condensate Drain Test the drain pan and drain line after installation 1 Pour several quarts of water into drain pan Use enough water to fill both the drain trap and the line 2 Check the installed drain pan Drain pan must be draining completely Drain line fittings must not be leaking Water must be draining from the end of the p...

Page 9: ...n the summer resulting in an increase in the number of service calls Before using any filter with this system check the specifications provided by the filter manufacturer against the data given in the appropriate Product Specifications Additional information is provided in Service and Application Note ACC002 August 2000 IMPORTANT Installing Duct System Connect supply air duct to the flange on top ...

Page 10: ...SION VALVE CAPILLARY TUBE IS NOT TOUCHING METAL EDGES OR COPPER TUBING REMOVE RUBBER PLUG FROM BOTH LIQUID AND SUCTION LINES NOTE BCE5C SERIES UNITS USE NITROGEN OR DRY AIR AS A HOLDING CHARGE IF THERE IS NO PRESSURE WHEN THE RUBBER PLUGS ARE REMOVED CHECK THE COIL FOR LEAKS BEFORE INSTALLING EITHER REMOVE OR PUSH PIPE WRAPPING BACK THROUGH HOLE IN PIPING PLATE BEFORE LINE SET CONNECTION AND BRAZI...

Page 11: ...e set is required contact Technical Services NOTE Sealing the Unit Seal the unit so that warm air is not allowed into the cabinet Warm air introduces moisture which results in water blow off problems This is especially important when the unit is installed in an unconditioned area If installed in an unconditioned space sealant should be applied around the electrical wires refrigerant tubing and con...

Page 12: ...s in accordance with tables 310 16 and 310 17 in the National Electric Code ANSI NFPA No 70 or tables 1 through 4 in the Canadian Electric Code Part I CSA Standard C22 1 The power supply must be sized and protected according to the specifications supplied on the product This air handler is factory configured for 240 volt single phase 60 cycles For 208 volt applications see 208 Volt Conversion late...

Page 13: ...result in death or electrical shock WARNING 208 240 VOLT TRANSFORMER PRIMARY SECONDARY 240 Volts 208 Volts Figure 14 Converting Unit from 240VAC to 208VAC Figure 15 Thermostat Designations Non Communicating 1 Refer to thermostat installation instructions 2 If applicable 3 Refer to indoor unit installation instructions 4 L is used for any accessories e g diagnostic warning alarm used to activate th...

Page 14: ...507787 01 Issue 2007 Page 14 of 22 4KW 5KW Figure 16 Typical Wiring Diagram BCE5C Air Handler with Electric Heat PSC 018 024 030 036 042 models ...

Page 15: ...507787 01 Issue 2007 Page 15 of 22 4KW 5KW Figure 17 Typical Wiring Diagram BCE5C Air Handler with Electric Heat CT 048 and 060 models ...

Page 16: ...oling blower speed is factory configured to provide correct air flow for an outdoor unit that matches the cooling capacity rating of the air handler If the outdoor unit is smaller than the maximum cooling capacity rating for the air handler the cooling blower speed may need to be changed Refer to blower performance chart in Table 4 Electric shock hazard Disconnect all power supplies before servici...

Page 17: ...52 1390 1345 HIGH 1816 1756 1693 1605 1528 048 LOW 1257 1212 1157 1116 1053 MED LOW 1486 1448 1411 1364 1330 MED 1721 1675 1630 1594 1553 MED HIGH 1721 1675 1630 1594 1553 HIGH 1840 1794 1754 1721 1681 060 LOW 1098 1049 1001 926 831 MED LOW 1624 1594 1565 1520 1492 MED 1815 1783 1758 1730 1685 MED HIGH 1903 1869 1837 1809 1764 HIGH 1981 1957 1923 1893 1861 Blower Performance CFM vs ESP in w c Cool...

Page 18: ...cycle off Check Electric Heat If Used 1 Set thermostat to call for auxiliary heat approximately 5 F above ambient temperature The indoor blower and auxiliary heat should come on together Allow a minimum of 3 minutes for all sequencers to cycle on 2 Set the thermostat so that it does not call for heat Allow up to 5 minutes for all sequencers to cycle off Operation Time Delay Relay Blower time delay...

Page 19: ... unit is put back into operation Insulation loses its insulating value when wet damaged separated or torn IMPORTANT Matte or foil faced insulation is installed in indoor equipment to provide a barrier between outside air conditions surrounding ambient temperature and humidity and the varying conditions inside the unit If the insulation barrier is damaged wet ripped torn or separated from the cabin...

Page 20: ...nance Do not operate system without a filter A filter is required to protect the coil blower and internal parts from excessive dirt and dust The filter is placed in the return duct by the installer IMPORTANT Inspect air filters at least once a month and replace or clean as required Dirty filters are the most common cause of inadequate heating or cooling performance Replace disposable filters Clean...

Page 21: ...ing Mode Return Duct Temperature ___________ THERMOSTAT Adjusted and Programmed Return External Static ______ ______ Total External Static ______ ______ 6 Supply Duct Temperature ___________ Temperature Drop ___________ TEMPERATURE RISE Heating Mode Return Duct Temperature __________ Supply Duct Temperature __________ Temperature Rise __________ Operation Explained to Owner 9 Explained Operation o...

Page 22: ...______ Total External Static ______ ______ 6 6 Supply Duct Temperature ___________ Temperature Drop ___________ TEMPERATURE RISE Heating Mode Return Duct Temperature __________ Supply Duct Temperature __________ Temperature Rise __________ Operation Explained to Owner 9 Electric Heat Amps 7 Explained Operation of System to Homeowner Technician s Name _______________________Date Start Up Performanc...

Reviews: