Table 5.
96G1UHE Maximum Allowable Intake or Exhaust Vent Length in Feet
Standard Termination at Elevation 0 - 4,500 ft
Number
of 90°
Elbows
Used
1-1/2” Pipe
2” Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
Capacity
030
045
070
090
110
030
045
070
090
110
030
045
070
090
110
030
045
070
090
110
1
25
20
15
n/a
n/a
76
61
39
19
110
95
63
38
132
132
113
113
2
20
15
10
71
56
34
14
105
90
58
33
127
127
108
108
3
15
10
n/a
66
51
29
9
100
85
53
28
122
122
103
103
4
10
n/a
61
46
24
n/a
95
80
48
23
117
117
98
98
5
n/a
56
41
19
90
75
43
18
112
112
93
93
6
51
36
14
85
70
38
13
107
107
88
88
7
46
31
9
80
65
33
8
102
102
83
83
8
41
26
n/a
75
60
28
n/a
97
97
78
78
9
36
21
70
55
23
92
92
73
73
10
31
16
65
50
18
87
87
68
68
Standard Termination at Elevation 4,501 - 10,000 ft
Number
of 90°
Elbows
Used
1-1/2” Pipe
2” Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
Capacity
030
045
070
090
110
030
045
070
090
110
030
045
070
090
110
030
045
070
090
110
1
25
20
15
n/a
n/a
76
61
39
n/a
110
95
63
38
132
132
113
113
2
20
15
10
71
56
34
105
90
58
33
127
127
108
108
3
15
10
n/a
66
51
29
100
85
53
28
122
122
103
103
4
10
n/a
61
46
24
95
80
48
23
117
117
98
98
5
n/a
56
41
19
90
75
43
18
112
112
93
93
6
51
36
14
85
70
38
13
107
107
88
88
7
46
31
9
80
65
33
8
102
102
83
83
8
41
26
n/a
75
60
28
n/a
97
97
78
78
9
36
21
70
55
23
92
92
73
73
10
31
16
65
50
18
87
87
68
68
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and
Exhaust must be same pipe size.