Page 13 of 75
Outdoor Unit Connections and Line Set Usage
Description
Catalog
No.
Size
09
12
18
24
36
OUTDOOR UNIT
Line Sets
1/4 in. x 3/8 in. x 25 ft.
90X53
•
N/A
1/4 in. x 3/8 in. x 50 ft.
X0258
•
N/A
1/4 in. x 1/2 in. x 25 ft.
90X52
N/A
•
•
N/A
1/4 in. x 1/2 in. x 50 ft.
X0259
N/A
•
•
N/A
3/8 in. x 5/8 in. x 25 ft.
X8406
N/A
•
•
3/8 in. x 5/8 in. x 50 ft.
X8407
N/A
•
•
Table 2.
Outdoor Unit Connections and Line Set Usage
Indoor Unit
Extension Pipe Diameter (mm/inches)
Model
Pipe Diameter (mm/inches)
9K
Liquid
6.35 (1/4)
Liquid
6.35 (1/4)
Gas
9.52 (3/8)
Gas
9.52 (3/8)
12K and 18K
Liquid
6.35 (1/4)
Liquid
6.35 (1/4)
Gas
12.7 (1/2)
Gas
12.7 (1/2)
24K
Liquid
9.52 (3/8)
Liquid
9.52 (3/8)
Gas
15.9 (5/8)
Gas
15.9 (5/8)
36K
Liquid
9.52 (3/8)
Liquid
9.52 (3/8)
Gas
15.9 (5/8)
Gas
15.9 (5/8)
Table 3.
Pipe Diameter - MM (Inches)
Refrigerant pipe diameter is different according to indoor unit to be connected. When using the extension pipe, refer to
When refrigerant pipe diameter is different from that of the outdoor unit connector (18K indoor unit) an additional adapter
is required.
CAUTION
Outside Diameter
Torque
Additional Tightening
MM
Inches
v.cm
N.cm
Ф6.35
1/4
1500 (153kgf.cm)
1600 (163kgf.cm)
Ф9.52
3/8
2500 (255kgf.cm
2600 (265kgf.cm)
Ф12.7
1/2
3500 (357kgf.cm)
3600 (367kgf.cm)
Table 4. Torque Requirements