background image

506471-01

Page 31 of  41

Issue 1034

Sequence of Operation (see Figures 33 – 37)

Heating

On a call for heat from the room thermostat, the control board
performs a 1 second self check.  Upon confirmation that the
pressure switch contacts are in an open position, the control
energizes the combustion blower on high speed.  The control
then checks for adequate combustion air by making sure
the low-fire pressure switch contacts are closed.

The igniter energizes and is allowed to warm up for 7
seconds before the gas valve energizes on 1

st

 stage and

burners ignite.  45 seconds after the control confirms ignition
has occurred, the control drops the combustion blower to
low speed.

The circulating blower ramps up to 50% of 1

st

 stage heat speed

and operates at that speed for one minute (including ramp up
time), then at 75% of 1

st

 stage heat speed for an additional

minute.  After that, the circulating blower operates at full 1

st

stage heat speed until either the heat call is satisfied or the
thermostat initiates a call for 2

nd

 stage heat.  On a call for 2

nd

stage heat, the control energizes the circulating air blower on
full CFM 2

nd

 stage heat.

If the automatic heat staging option is being used (see Single
Stage Thermostat Operation on page 27), the furnace does
not switch to 2

nd

 stage heat in response to a call from the

thermostat but instead operates at 1

st

 stage heat for the

duration of the selected time before automatically switching
to 2

nd

 stage heat.

When the call for heat is satisfied, the gas valve and
combustion air blower shut down.  The control board shuts
off the gas valve and runs the combustion blower for an
additional 15 seconds.  The circulating air blower continues
to run for 2 minutes at 82% of the selected heating speed
(low fire or high fire) before ramping down.

In the event the unit loses ignition, the control will attempt to
recycle up to five times before it goes into a 1 hour lockout.
Lockout may be manually reset by removing power from
the control for more than 1 second or removing the
thermostat call for heat for more than 3 seconds.

If during a heating cycle the limit control senses an abnormally
high temperature and opens, the control board de-energizes
the gas valve and the combustion blower while the circulating
blower ramps up to 2

nd

 stage heat speed.  The circulating blower

remains energized until the limits are closed.

Fan On

When the thermostat is set for continuous fan operation and
there is no demand for heating or cooling, a call for fan closes

OPERATION

the R to G circuit and the circulating blower motor runs at
50% of the selected cooling CFM until switched off.  When
the call for fan is turned off, the control de-energizes the
circulating blower.

Cooling

The unit is set up at the factory for single stage cooling.  For
two stage cooling operation, clip the jumper wire located
between the Y to Y2 terminals on the integrated ignition/
blower control board.

If the active dehumidification feature is enabled, the
circulating blower runs at 82% of the selected cooling speed
as long as there is a call for dehumidification.

Single Stage Cooling

A call for cooling from the thermostat closes the R to Y circuit
on the integrated ignition/blower control board.  The control
waits for a 1-second delay before energizing the circulating
blower to 82% of the selected cooling CFM (passive
dehumidification  mode).  After 7.5 minutes, the circulating
blower automatically ramps up to 100% of the selected cooling
airflow.  When the call for cooling is satisfied, the circulating
blower  ramps back down to 82% of the selected cooling
airflow for 1 minute, then shuts off.

Two Stage Cooling

A call for 1

st

 stage cooling from the thermostat closes the R

to Y circuit on the control board.  The control waits for a 1-
second delay before energizing the circulating blower.  The
blower motor runs at 57% of the selected air flow for the first
7.5 minutes of the 1

st

 stage cooling demand (passive

dehumidification mode).  After 7.5 minutes, the blower motor
runs at 70% of the selected cooling air flow until 1

st

 stage

cooling demand is satisfied.

A call for 2

nd

 stage cooling from the thermostat closes the R to

Y2 circuit on the control board.  The blower motor ramps up to
100% of the selected cooling air flow.  When the demand for
cooling is met, the blower ramps down to Y1 until satisfied,
then ramps down to 57% for 1 minute, then turns off.

Heat Pump

For heat pump operation, clip the jumper wire located below
the O terminal on the integrated ignition/blower control board.
In heat pump mode, a call for heat  will result in the circulating
air blower operating at the selected cooling airflow after a
brief ramp-up period.

 IMPORTANT

The system must not be in either the passive or active
dehumidification mode when charging a cooling system.

Summary of Contents for 80G1UH2V

Page 1: ...omeowner for future reference INSTALLATION INSTRUCTIONS A80UH2V 80G1UH2V Warm Air Gas Furnace Upflow Horizontal Left and Right Air Discharge TABLE OF CONTENTS Unit Dimensions 2 A80UH2V 80G1UH2V Parts Arrangement 3 A80UH2V 80G1UH2V Gas Furnace 4 Shipping and Packing List 4 Safety Information 4 Use of Furnace as a Construction Heater 5 General 6 Combustion Dilution Ventilation Air 6 Setting Equipmen...

Page 2: ... L s or greater must have one of the following 1 Return air from single side transition will accommodate 20 x 25 x 1 in 508 x 635 x 25 mm cleanable air filter Required to maintain proper air velocity 2 Single side return air with optional RAB Return Air Base 3 Return Air from bottom and one side 4 Return air from both sides 5 Return air from bottom 2 Flue outlet may be horizontal but furnace must ...

Page 3: ...1 Page 3 of 41 Issue 1034 EXPLODED VIEW CONTROL BOX BLOWER ASSEMBLY ACCESS PANEL BURNER BOX ROLLOUT SWITCH GAS VALVE COMBUSTION AIR INDUCER PRESSURE SWITCH COMBUSTION AIR INDUCER HEAT EXCHANGER CABINET Figure 1 ...

Page 4: ... must conform with local building codes In the absence of local codes units must be installed according to the current National Fuel Gas Code ANSI Z223 1 The National Fuel Gas Code is available from the following address American National Standards Institute Inc 11 West 42nd Street New York NY 10036 Clearances Adequate clearance must be made around the air openings into the vestibule area In order...

Page 5: ...st control the furnace The use of fixed jumpers that will provide continuous heating is not allowed The return air duct must be provided and sealed to the furnace Return air temperature range between 60 F 16 C and 80 F 27 C must be maintained Air filters must be installed in the system and must be maintained during construction Air filters must be replaced upon construction completion The input ra...

Page 6: ...t pipe or chimney As a result combustion gases enter the living space creating a potentially dangerous situation In the absence of local codes concerning air for combustion and ventilation use the guidelines and procedures in this section to install these furnaces to ensure efficient and safe operation You must consider combustion air needs and requirements for exhaust vents and gas piping A porti...

Page 7: ...aining the furnace the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room Even a small leak around the base of the unit at the platform or at the return air duct connection can cause ...

Page 8: ... area of at least one square inch per 2 000 Btu 645 mm per 59 kW per hour of the total input rating of all equipment in the enclosure If the equipment room is located against an outside wall and the air openings communicate directly with the outdoors each opening shall have a free area of at least 1 square inch per 4 000 Btu 645 mm per 1 17 kW per hour of the total input rating of all other equipm...

Page 9: ...washer have been removed the rigid leg will not touch the blower housing Setting Equipment WARNING Do not install the furnace on its front or its back Do not connect the return air ducts to the back of the furnace Doing so will adversely affect the operation of the safety control devices which could result in personal injury or death Upflow Applications Allow for clearances to combustible material...

Page 10: ... velocity See Figure 9 2 Single side return air with optional return airbase See Figure 10 3 Bottom return air 4 Return air from both sides 5 Bottom and one side return air Figure 9 Single Side Return Air with transition and filter Optional Return Air Base Upflow Applications Only For use with A B C and D cabinets NOTE Optional Side Return Air Filter Kits are not for use with Return Air Base 1 Bot...

Page 11: ...r ceiling joists When straps are used to suspend the unit in this way support must be provided for both the ends The straps must not interfere with the plenum or exhaust piping installation Cooling coils and supply and return air plenums must be supported separately NOTE When the furnace is installed on a platform in a crawlspace it must be elevated enough to avoid water damage and to allow the ev...

Page 12: ...own the vent pipe and into the room This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas This toxic gas might then be distributed throughout the house by the furnace duct system In upflow applications the return air can be brought in through the bottom or either side of the furnace If a furnace with bottom return air is installed on a platf...

Page 13: ...ressure switch assembly to the orifice plate Lift the assembly and rotate it 90 clockwise or counter clockwise to either the 3 o clock position or 9 o clock position Resecure with four secrews Gasket should be left in place 2 Use tin snips to cut preferred opening on the cabinet for repositioning the flue outlet Use the cut out piece as a cover plate to patch unused opening on cabinet Figure 17 Re...

Page 14: ...ssembly 2 screws and cut wire tie to free make up box wires Reinstall make up box on other side of cabinet Resecure make up box wires Either pull excess wires through the blower compartment and secure using supplied wire tie or coil excess wire and secure to the gas manifold HORIZONTAL RIGHT POSITION Side Vent Discharge Figure 22 HORIZONTAL LEFT POSITION Side Vent Discharge Figure 20 Disconnect pr...

Page 15: ...ING Use self drilling sheet metal screws or a mechanical fastener to firmly secure the vent pipe to the round collar of the flue transition If self drilling screws are used to attach the vent pipe it is recommended that three be used Drive one self drilling screw through the front and one through each side of the vent pipe and collar See Figure 23 Install the first vent connector elbow at a minimu...

Page 16: ...ney Never connect a Category I appliance to a chimney that is servicing a solid fuel appliance If a fireplace chimney flue is used to vent this appliance the fireplace opening must be permanently sealed Atype B or listed chimney lining system that passes through an unused masonry chimney flue is not considered to be exposed to the outdoors General Venting Requirements Vent these furnaces according...

Page 17: ...ints between sections of single wall connector piping shall be fastened by screws or other approved means 13 When the vent connector used for Category I appliances must be located in or pass through a crawl space attic or other areas which may be cold that portion of the vent connector shall be constructed of listed doublewall type B vent material or material having equivalent insulation qualities...

Page 18: ...configureations with zero lateral lengths are assumed to have no elbows in the vent system For all other vent configurations the vent system is assumed to have two 90 elbows For each additional 90 elbow or equivalent for example two 45 elbows equal one 90 elbow beyond two the maximum capacity listed in the venting table should be reduced by 10 percent 0 90 x maximum listed capacity ...

Page 19: ...configureations with zero lateral lengths are assumed to have no elbows in the vent system For all other vent configurations the vent system is assumed to have two 90 elbows For each additional 90 elbow or equivalent for example two 45 elbows equal one 90 elbow beyond two the maximum capacity listed in the venting table should be reduced by 10 percent 0 90 x maximum listed capacity ...

Page 20: ... Capacity Type B Double Wall Vents with Type B Double Wall Connectors Serving Two or More Category I Appliances Common Vent Capacity Type B Double Wall Vents with Type B Double Wall Connectors Serving Two or More Category I Appliances Table 5 Table 6 ...

Page 21: ... Two or more Category I Appliances Table 8 NOTE Single appliance venting configureations with zero lateral lengths are assumed to have no elbows in the vent system For all other vent configurations the vent system is assumed to have two 90 elbows For each additional 90 elbow or equivalent for example two 45 elbows equal one 90 elbow beyond two the maximum capacity listed in the venting table shoul...

Page 22: ...m are located and other spaces of the building Turn on clothes dryers and any appliances not connected to the common venting system Turn on any exhaust fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Follow the lighting instructions Turn on the appliance that is being inspected Adjust the thermostat ...

Page 23: ...e The piping must be supported at proper intervals every 8 to 10 feet 2 44 to 3 01 m with suitable hangers or straps Install a drip leg in vertical pipe runs to the unit 5 A 1 8 N P T plugged tap or pressure post is located on the gas valve to facilitate test gauge connection See Figure 38 6 In some localities codes may require the installation of a manual main shut off valve and union furnished b...

Page 24: ...e 24 of 41 Issue 1034 NOTE BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET Figure 26 Horizontal Applications Possible Gas Piping Configurations NOTE BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET Figure 27 ...

Page 25: ...e to protect the furnace s electronic controls Precautions will help to avoid control exposure to electrostatic discharge by putting the furnace the control and the technician at the same electrostatic potential Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface such as the gas valve or blower deck before performing any service procedure CAUTION The unit is...

Page 26: ...ated up to 0 5 amp can be connected to this terminal with the ground leg of the circuit being connected to either ground or the C terminal See Figure 41 for control configuration 10 Install the room thermostat according to the instructions provided with the thermostat If the furnace is being matched with a heat pump refer to the instruction packaged with the dual fuel thermostat Indoor Blower Spee...

Page 27: ... 10 minutes The furnace will start on 1st stage heat and stay at 1st stage heat for the duration of the selected time before switching to 2nd stage heat W1 on the control board must be connected to W1 on the thermostat Humidifier Terminals are provided on the integrated ignition blower control board for connection to a 120 volt humidifier The HUM terminal is energized whenever the thermostat calls...

Page 28: ...et to run at the middle of the heating rise range as shown on the unit rating plate If higher or lower rise is desired change the airflow 15 up or down by movingtheADJUSTjumperplug seeFigure32 fromtheNORM positiontothe or position Thisadjustmentwillalsocause the cooling airflow to be raised or lowered by 15 The TEST position on the ADJUST tap is not used The jumper plug on the HEAT tap should rema...

Page 29: ...506471 01 Page 29 of 41 Issue 1034 ADJUSTING AIRFLOW Table 11 ...

Page 30: ...Set the room thermostat to lowest setting 2 Remove burner access door 3 Move the gas control knob to the ON position Use only your hand to turn the gas control knob Never use tools If the knob will not turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or explosion 4 Replace the burner access door 5 Turn on the electrical power to...

Page 31: ...heatspeed Thecirculatingblower remains energized until the limits are closed Fan On When the thermostat is set for continuous fan operation and there is no demand for heating or cooling a call for fan closes OPERATION the R to G circuit and the circulating blower motor runs at 50 of the selected cooling CFM until switched off When the call for fan is turned off the control de energizes the circula...

Page 32: ... Stage Cool st y1 Y2 2 Stage Cool Demand Present nd 2 Demand Satisfied nd Stage Cool y2 1 min 70 Y1 y2 Y1 Y2 y1 57 1 min 57 Figure 33 1st Stage 2nd Stage W1 W2 Heat Call W1 100 CALL W2 High Heat Demand Present High Heat Demand Satisfied w2 50 75 Percentage of High Fire CFM 1 min W1 Heat Demand Present Heat Demand Satisfied w1 Percentage of Low Fire CFM 100 82 2 min OFF W1 W2 w1 w2 82 2 min w1 1 mi...

Page 33: ...missible gas supply pressure for the purpose of input adjustment is 5 w c for natural gas or 11 w c for propane gas This furnace requires conversion for use with propane see Accessories section on page 26 for correct kit The maximum inlet gas supply pressure is 10 5 w c for natural gas and 13 w c for propane Gas input must never exceed the value shown on the furnace rating plate These units are eq...

Page 34: ...eet fill in the appropiate information on the furnace label that has the words This furnace was converted on Emergency Replacement Motor Operation If the variable speed motor needs to be replaced in an emergency situation such as no heat and an exact replacement motor is not immediately available a standard PSC motor of equivalent frame size voltage rotation and horsepower can be temporarily insta...

Page 35: ...atural gas burner flame or long yellow tips on propane may be caused by lint accumulation or dirt inside the burner or burner ports at the air inlet between the burner and manifold pipe or obstructions over the burner orifice Use a soft brush or vacuum to clean the affected areas MAINTENANCE Failure to follow the safety warnings exactly could result in dangerous operation serious injury death or p...

Page 36: ...est fault code is flashed last To clear the fault code history press and hold the pushbutton switch in for more than 5 seconds before releasing High Heat State LED On A80UH2V and 80G1UH2V models a green LED is provided on the control board to indicate high heat state see Table 14 CFM LED On A80UH2V and 80G1UH2V models equipped with a variable speed motor an amber LED is provided on the control boa...

Page 37: ...me rollout protector switch Hot surface igniter Input choke REPAIR PARTS The following repair parts are available from the local distributor When ordering parts include the complete furnace model number and serial number which are printed on the rating plate located on the furnace Heat Exchanger Group Heat exchanger Blower Group Blower housing assembly Blower wheel Blower mount Blower motor Blower...

Page 38: ...TORY LOW VOLTAGE FIELD PRESSURE SWITCH LOW PRESSURE SWITCH DRAIN IF USED ROLLOUT SWITCH IF USED ROLLOUT SWITCH NONE 10 5 P5 AUX LIMIT SWITCH IF USED WHT BLK SW1 GREEN LED RED LED AMBER LED FAULT CODE HISTORY BUTTON SEE NOTE 1 AUTOMATIC HEAT STAGING JUMPER NOTES 1 PRESS AND RELEASE FAULT CODE HISTORY BUTTON TO DISPLAY FAULT CODES TO ERASE CODES PRESS AND HOLD BUTTON IN FOR MORE THAN 5 SECONDS 2 IF ...

Page 39: ...506471 01 Page 39 of 41 Issue 1034 Typical Field Wiring Diagram Figure 41 ...

Page 40: ...506471 01 Page 40 of 41 Issue 1034 START UP PERFORMANCE CHECK LIST UNIT SET UP ...

Page 41: ...506471 01 Page 41 of 41 Issue 1034 UNIT OPERATION ...

Reviews: