Specifications
Performance data
UNIT
ALLPH90R410 - INV
ALLPH120R410 - INV
Operating air temperature
°C
-15 to 43
Heating Capacity
kW
2.2 – 9.0
3.77 – 16.9
Consumed power
kW
0.16 – 1.60
0.3 – 3.02
COP
13.75 – 5.63
12.57 – 5.63
Power supply
230V~/ 50Hz
Nominal Heating Capacity
kW
4.29
9,7
Nominal power input
kW
0.74
1.38
Max power input
kW
1.97
3.2
Nominal Running current
A
3.35
6
Current range
A
1.29 – 6.86
1.3 – 13.1
Max Current
A
8.62
13.96
Compressor quantity
1
1
Compressor type
Rotary
Rotary
Refrigerant
R410a
Fan quantity
1
1
Fan power input
W
100
120
Fan rotary speed
RPM
500 - 750
600 - 750
Fan direction
Horizontal
Horizontal
Noise
dB(A)
40
44
Water connection
mm
50
50
Nominal water flow
m3/h
2.0
5.3
Water pressure drop (max)
kPa
4.0
5
Unit net dimensions (L*W*H)
mm
1003*396*767
1117*430*868
Unit shipping dimensions (L*W*H)
mm
1130 *460*780
1210*510*880
Net weight
kg
50
77
Shipping weight
kg
60
90
Test conditions - Air 27°C / Water 26°C / Humidity 80%
2
Summary of Contents for ALLPH120R410-INV
Page 27: ...25 ...