5. MAINTENANCE AND INSPECTION

5.1 Malfunction table

You can refer to the malfunction table to find out the failure cause and solution.

Power on

P01

P02

P15(system1),P25(system2)
P35(system3),P45(system4)

P04

Malfunction

Display

Reason 

Resolution

Normal working

Outlet temp. Sensor failure

Inlet temp. Sensor failure

Water flow is not enough 

and low differential pressure

Communication failure between 

wire controller and main board

The protection system is failure

Water flow is not enough

The ambient temp. Is low

No water/little water in water

 system

The high-preesure switch is broken

Electrical-heat is over heat

The temp. Sensor is broken or 

short circuit

Check or change the   temp. Sensor

Check or change the   temp. Sensor

Check or change the   temp. Sensor

Check or change the   temp. Sensor

Check or change the   temp. Sensor

Check or change the   temp. Sensor

Check or change the   temp. Sensor

Check or change the   temp. Sensor

The low-preesure switch is broken

Water flow is not enough

The ambient temp. Is low

Check the pressure switch and cold circuit

Check the pressure switch and cold circuit

Check the pipe water flow and water pump

Check or change electrical-heat

Check the pipe water flow and whether 

water system is jammed or not 

Check the pipe water flow and whether 

water system is jammed or not 

Check the pipe water flow and whether 

water system is jammed or not 

Check each protection point of the system

Check the wire connection  between 

remote wire controller and main board 

/

/

The temp. Sensor is broken or 

short circuit
The temp. Sensor is broken or 

short circuit

The temp. Sensor is broken or 

short circuit

The temp. Sensor is broken or 

short circuit

The temp. Sensor is broken or 

short circuit

The temp. Sensor is broken or 

short circuit

The temp. Sensor is broken or 

short circuit

Ambient  temp. Failure

System 1/2/3/4 
Coil temp. Failure
System 1/2/3/4 absorb 
Temp. Failure

System 1/2/3/4 anti-freeze 
Temp. Failure

Using side system 1 /2/3/4
Anti-freeze temp. Failure

System 1/2/3/4 coil inlet 
Temp. Failure

System 1/2/3/4 high 
Pressure protection

System 1/2/3/4 low 
Pressure protection

Water flow failure

Electric-heater 
Overheat protection

Water inlet and outlet 
Temp. Too big

System 1/2/3/4 anti-freeze 
Protection

System 1/2/3/4 source side 
Anti-freeze protection

System 1/2/3/4 using side 
Anti-freeze protection

Anti-freeze protect  level 1

Anti-freeze protect  level 2

System protection

Communication failure

P17(system1),P27(system2)

P37(system3),P47(system4)

P19(system1),P29(system2)
P39(system3),P49(system4)

P191(system1),P291(system2)
P391(system3),P491(system4)

P151(system1),P251(system2)
P351(system3),P451(system4)

E11(system1),E21(system2)
E31(system3),E41(system4)

E12(system1),E22(system2)
E32(system3),E42(system4)

E03

E04

E06

E06

E17(system1),E27(system2)
E37(system3),E47(system4)

E171(system1),E271(system2)
E371(system3),E471(system4)

E19

E29

E05

E08

Water flow is not enough 

and low differential pressure

Check the pipe water flow and whether 

water system is jammed or not 

5.2 BHB10 malfunction  Table

21

5. MAINTENANCE AND INSPECTION

System 2 economizer 

outlet temp.failure

System 1 anti-freeze protection

System 2 anti-freeze protection

Malfunction

Ambient temp.sensor failure

Communication failure

System 1 exhaust temp.failure

System 2 exhaust temp.failure

System 1 anti-freeze temp.failure

System 2 anti-freeze temp.failure

System 1 economizer 

inlet temp.failure

System 2 economizer 

inlet temp.failure

System 1 economizer 

outlet temp.failure

P202

P29

Detector
 display

P04

E08

P181

P281

E171

E271

P101

P201

P102

Water flow volume not enough

Canse

Communication failure  between 

remote wire controller and main board 

The sensor is open or short circuit

Solution

Check the wire connection  between 

remote wire controller and main board 

Check or change the sensor

Check the flow volume,water 
system is jammed or not

System 1 current protection

E151

Current through compressor too heavy  Check through the power supply for 

compressor or short circuit

E251

Current through compressor too heavy 

Water flow volume not enough

Check the flow volume,water 
system is jammed or not

The sensor is open or short circuit

Check or change the sensor

The sensor is open or short circuit

Check or change the sensor

The sensor is open or short circuit

Check or change the sensor

The sensor is open or short circuit

Check or change the sensor

The sensor is open or short circuit

Check or change the sensor

The sensor is open or short circuit

Check or change the sensor

The sensor is open or short circuit

Check or change the sensor

The sensor is open or short circuit

Check or change the sensor

System 2 current protection

Check through the power supply for 

compressor or short circuit

P19

P182

Compressor exhaust temp.too high 

System 1 exhaust high 

temp.protection

Check through the refrigerant system

P282

System 2 exhaust high 

temp.protection

Compressor exhaust temp.too high 

Check through the refrigerant system

 Digital
display

81

81

4

9

9

01

01

02

02

71

71

\

51

51

82

82

Malfunction

System 1 failure

Ambient  failure

Indicator light

1 on 1 off

5.2.2 The indicator light  display of failure cause.

System 1 failure

2 on 1 off

3 on 1 off

5.2.1 The common  failure cause and solution.

Summary of Contents for ALLPH 91Kw

Page 1: ...Swimming Pool Heat Pump Installation Operation Manual Model ALLPH 91Kw ...

Page 2: ...Initial Start up of the Unit 4 Usage and Operation 4 1 Function of the controller 4 2 Usage of the controller 4 3 The operation of mode switching 4 4 The operation of system state checking 4 5 The operation of parameter setting 4 6 The operation of clock setting 4 7 The operation of timer setting 4 8 Keyboard lock 4 9 Malfunction display 4 10 Parameter table 5 Maintenance and Inspection 5 1 Malfun...

Page 3: ...ut according to the recommended time and frequency as stated in this manual Use genuine standard spare parts only Failure to comply with these recommendations will invalidate the warranty Swimming Pool Heat Pump Unit heats the swimming pool water and keeps the temperature constant For split type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has f...

Page 4: ... Speed Fan Direction Noise Water Connection Water Flow Volume Water Pressure Drop MAX Unit Net Dimensions L W H Unit Shipping Dimensions L W H Net Weight Shipping Weight Model kW BTU h kW A W RPM dB A mm kPa mm mm kg kg 3 m h ALLPH91Kw 91 310000 17 5 31 2 380 415V 3N 50Hz 4 scroll 3 200 3 830 vertical 61 63 28 16 see the drawing of the units see package label see nameplate see package label Heatin...

Page 5: ...3 Unit Structure and Dimensions 2 2 The dimensions for Swimming Pool Heat Pump Unit 2 SPECIFICATION Models ALLPH91Kw Airflow direction 1920 Water Inlet φ110 Water Outlet φ110 240 160 1070 2170 174 ...

Page 6: ...necessary spare parts for the water system that provided by users or the installer Attention Please follow these steps when using for the first time 1 Open valve and charge water 2 Make sure that the pump and the water in pipe have been filled with water 3 Close the valve and start the unit Chlorinator cell Water outlet Pool Valve Water supply Water inlet Water pump Sand filter or other type filte...

Page 7: ...ir which reduces it efficiency and may prevent adequate heat delivery 3 2 Swimming Pool Heat Pumps Location Normally the pool heat pump is installed within 7 5 metres of the pool The longer the distance from the pool the greater the heat loss from the piping For the most part the piping is buried Therefore the heat loss is minimal for runs of up to15 meters 15 meters to and from the pump 30 meters...

Page 8: ...into the basepan and drain out through the barbed plastic condensation drain fitting on the side of the basepan This fitting is designed to accept 3 4 clear vinyl tubing which can be pushed on by hand and run to a suitable drain It is easy to mistake the condensation for a water leak inside the unit NB A quick way to verify that the water is condensation is to shut off the unit and keep the pool p...

Page 9: ...set temperature Time Delay The unit is equipped with a 3 minute built in solid state restart delay included to protect control circuit components and to eliminate restart cycling and contactor chatter This time delay will automatically restart the unit approximately 3 minutes after each control circuit interruption Even a brief power interruption will activate the solid state 3 minute restart dela...

Page 10: ...rent mode page up or confirm current operation ON OFF Press this button to start up shut off the unit cancel current operation or back to upper interface HELP MODE CLOCK Button Name Function 4 1Function of wire controller Press this key to select the upward option or increase the parameter value Press this key to select the downward option or decrease the parameter value Up Down 4 USAGE AND OPERAT...

Page 11: ...means you can page up 2 Pressing this key could select the upward option or increase the value of a certain parameter 3 Pressing this key could select the downward option or decrease the value of a certain parameter 4 Pressing this key could switch unit mode enter into the next interface or save settings 5 Pressing this key could set the system time or time for regular shutdown or restart 6 Pressi...

Page 12: ...shutting down Press in the shutdown state for 1s to start up the system Press in the startup state for 1s to shut down the system For example Press for 1s Running state MODE By actual state Month Date Time Week ON Eco heating Inlet temp 25 0 Outlet temp 25 0 31 03 2011 09 10 THU ON Eco heating Inlet temp 25 0 Outlet temp 25 0 31 03 2011 09 10 THU OFF Heating Inlet temp 25 0 Outlet temp 25 0 31 03 ...

Page 13: ...ss pageup or pagedown to select the needing parameter press to enter and press to exit For example Press Temperature Switch Output Press T01 Inlet water 25 0 T02 Outlet water 25 0 T03 Coil 1 30 5 T04 Coil 2 32 5 T05 Ambient 23 5 T06 Deice 1 4 5 T07 Deice 2 4 5 T08 Suction 1 20 5 Press Press Press ON Cooling Inlet temp 25 0 Outlet temp 25 0 31 03 2011 09 10 THU ON Eco heating Inlet temp 25 0 Outlet...

Page 14: ...f clock setting At main interface press to enter clock setting interface select the needing parameter and press at this time parameter value flashing press increasing or Decreasing can change parameter value then press to save press can cancel the setting or back to the main interface timer setting refer to timer operation Press to enter clock interface ON Cooling Inlet temp 25 0 Outlet temp 25 0 ...

Page 15: ...ing automatic and back to the main interface As follows Date 31 01 2011 Time 05 55 Week Thursday Timer Date format Date 31 0 2011 Time 05 55 Week Thursday Timer Date format Date 31 01 20 Time 06 55 Week Thursday Timer Date format Date 31 0 2011 Time 06 55 Week Thursday Timer Date format Date 31 01 2011 Time 06 41 Week Thursday Timer Date format Date 31 01 2011 Time 06 41 Week Thursday Timer Date f...

Page 16: ...to Sunday the operation is the same with clock setting For example Hour bit flashing No operation in 10s It has been changed Press to enter clock interface Press to select Timer Timer zone Daily timer Press to enter Timer interface A Timer setting Date 31 01 2011 Time 06 55 Week Thursday Timer Date format ON Cooling Inlet temp 25 0 Outlet temp 25 0 31 01 2011 06 55 THU ON Cooling Inlet temp 25 0 O...

Page 17: ...mer1 00 00 00 00 Timer2 00 00 00 00 Timer3 00 00 00 00 Timer4 00 00 00 00 Timer1 07 00 00 00 Timer2 00 00 00 00 Timer3 00 00 00 00 Timer4 00 00 00 00 Timer1 07 00 00 00 Timer2 00 00 00 00 Timer3 00 00 00 00 Timer4 00 00 00 00 Timer1 07 30 00 00 Timer2 00 00 00 00 Timer3 00 00 00 00 Timer4 00 00 00 00 Timer1 07 30 22 00 Timer2 00 00 00 00 Timer3 00 00 00 00 Timer4 00 00 00 00 Timer1 07 30 22 00 Tim...

Page 18: ...enter clock interface Press to select Timer Press to enter timer interface B The operation of daily timer Timer1 07 30 22 00 Timer2 00 00 00 00 Timer3 00 00 00 00 Timer4 00 00 00 00 Timer zone Daily timer ON Cooling Inlet temp 25 0 Outlet temp 25 0 31 01 2011 06 55 THU Date 31 01 2011 Time 05 55 Week Thursday Timer Date format ON Cooling Inlet temp 25 0 Outlet temp 25 0 31 01 2011 06 55 THU Date 3...

Page 19: ...i Timer4 Sat Timer2 Timer4 Sun OFF Mon Timer1 Tue Timer1 Timer3 Wed ON Thu Timer3 Timer1 Fri Timer4 Sat Timer2 Timer4 Sun OFF Mon Timer1 Tue Timer1 Timer3 Wed ON Thu Timer3 Timer1 Fri Timer2 Sat Timer2 Timer4 Sun OFF Mon Timer1 Tue Timer1 Timer3 Wed ON Thu Timer3 Timer1 Fri Timer2 Timer4 Sat Timer2 Timer4 Sun OFF Mon Timer1 Tue Timer1 Timer3 Wed ON Thu Timer3 Timer1 Fri Timer2 Timer3 Sat Timer2 Ti...

Page 20: ...t 24 00 on Sunday then it will be running the whole day on Monday and vice versa Wednesday ON means system will be running the whole day on Wednesday Thursday OFF means system will be off the whole day on Thursday Saturday Timer1 Timer2 means the time to start up and to shut down is according to Timer1 and Timer2 If there is no operation in 10s system will memory the parameter setting automaticly ...

Page 21: ...ill be malfunction code showing on the controller screen when relative malfunction occurs You can refer to the malfunction table to find out the failure cause and solution For example P01 Inlet water temp Failure Failure number 1 Malfunction code Malfunction Failure number press or can check next malfunction ON Cooling Inlet temp 25 0 Outlet temp 25 0 31 01 2011 06 55 THU ON Cooling Inlet temp 25 ...

Page 22: ...Check each protection point of the system Check the wire connection between remote wire controller and main board The temp Sensor is broken or short circuit The temp Sensor is broken or short circuit The temp Sensor is broken or short circuit The temp Sensor is broken or short circuit The temp Sensor is broken or short circuit The temp Sensor is broken or short circuit The temp Sensor is broken or...

Page 23: ...r too heavy Water flow volume not enough Check the flow volume water system is jammed or not The sensor is open or short circuit Check or change the sensor The sensor is open or short circuit Check or change the sensor The sensor is open or short circuit Check or change the sensor The sensor is open or short circuit Check or change the sensor The sensor is open or short circuit Check or change the...

Page 24: ...t System 4 low pressure protection input Water flow switch protection input Electric heater overload protection input Symbol L N RO 01 RO 02 RO 03 RO 04 RO 05 RO 06 RO 07 RO 08 RO 09 RO 10 RO 11 DI DO 1 DI DO 2 DI DO 3 DI 01 DI 02 DI 03 DI 04 DI 05 DI 06 DI 07 DI 08 DI 09 DI 10 NO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 Meaning System protection signal Water input temp...

Page 25: ...RLY3 RLY4 CN5 CN6 12V NET GND DI01 AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 CT1 CN4 GND GND GND GND GND GND GND GND GND CC01 AI09 GND CC02 RO01 RO02 RO03 RO04 CC03 CC04 CT2 CN2 Wire controller NET GND 12V DI01 GND AI01 GND AI02 GND AI03 GND AI04 GND AI05 GND System 2 economizer inlet temp failure input System 1 economizer inlet temp failure input System 1 economizer outlet temp failure input System...

Page 26: ...cting a crossed out waste bin that is underneath the appliance indicates that this product at the end of its useful life must be handled separately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs This product is compliant with directive 2002 95 EC RoHs concer...

Page 27: ...ase line MCB Creepage protector Signal line 2 n 0 5mm Nameplate maximum current Earth line No more than 10A 20A 32A 40A 40A 63A 80A 100A 125A 160A 225A 250A 280A 2 1 5mm 2 2 5mm 2 4mm 2 6mm 2 10mm 2 16mm 2 mm 25 2 mm 25 2 35mm 2 50mm 2 70mm 2 95mm 2 Three phas nit 2 3 1 5mm 2 3 2 5mm 2 3 4mm 2 3 6mm 2 3 10mm 2 16mm 3 2 25mm 3 2 3 25mm 2 3 35mm 2 3 50mm 2 3 70mm 2 3 95mm 30mA less than 0 1 sec 30mA...

Page 28: ...Code 20160606 0009 ...

Reviews: