Page 16
3.19 SETTING ALARM TEMPERATURE SET POINTS
In the program menu, select F1 SET UP RTD.
3.20 RTD CHANNEL ADDRESS
Enter a valid RTD address from 1 to 4. Select PgDn for next
menu. An RTD does not have to be connected to the chan-
nel to acquire the address.
3.21 RTD NAME
Select F1 to enter an RTD name, up to 19 characters for
this channel. This name will appear in the alarm menu and
history reports. Select PgDn for next menu.
3.22 RTD TYPE
Select F1 to acquire the RTD characteristics that match the
RTD that is connected to this channel. The RTD selections
are Platinum #8, Platinum #11, Nickel #1, Nickel #7 and
Copper #15. Select PgDn for next menu.
3.23
RTD RELAY MODE
Select F1 to change the relay from non-latching to latching.
When this channel temperature attains its set point, the
alarm designated for this relay will latch until reset by an ad-
ministrator.
Select F2 to change the relay from non-failsafe to failsafe.
When selected for failsafe, the relay is energized. Durng an
alarm temperature or if the monitor loses power, this relay
will change state.
3.24 ENABLE or DISABLE an RTD
Toggle the F1 key to select whether this channel will be ena-
bled (to monitor for alarms) or disabled (to be kept off line).
NOTE: If this channel is in alarm (set point attained) then the
word “ALARMS” will flash and appear as indicated in the
menu, whether enabled or disabled. It is recommended to
eliminate the alarm prior to placing the monitor online by
changing the temperature set point or the monitored RTD
temperature.
NOTE: If this channel is selected for disable, information will
still be available to view or change data, whether the RTD is
connected to the monitor or not.
* RTD PROGRAM *
ENTER RTD ADDRESS>
ADDRESS>
PGDN-NXT
* RTD 1 NAME *
Pump Room #5
PLATINUM #8
F1-CHNG PGDN-NXT
* RTD 1 RELAY MODE *
F1 NON-LATCHING
F2 NON-FAILSAFE
Fx-CHNG PGU/D-NXT
* RTD 1 ALARM *
F1 STATUS: DISABLED/ENABLED
F2 MODE: RISING/FALLING
Fx-CHNG
*ALARM*
PGU/D-NXT
* RTD 1 RTD TYPE *
PLATINUM #8
F1-CHNG PGDN-NXT
* PROGRAM MENU *
F1 SET UP RTD
F2 SET UP SYSTEM
F3 CHANGE PASSWORD
CAUTION: MAKE SURE THE RTD SENSOR
TYPE CONNECTED TO THE MONITOR
MATCHES THE TYPE ON THE MONITOR DIS-
PLAY MENU OR INCORRECT TEMPERA-
TURES WILL BE UTILIZED, RESULTING IN ER-
RONEOUS ALARMS.